Page 54
506601−01
HEAT PUMP CONTROL (A175) UNIT NOMINAL CAPACITY CODE CONFIGURATION
In a communicating system, if the room thermostat is indicating either a error code 313,
indoor and outdoor unit capacity
mismatch
error code, or error code 34,
must program unit capacity for outdoor unit (see figure 38)
.
When the required
Unit Capacity Code
is displaying on the LEDs,
remove
FIELD TEST
jumper from pins (E33).
LEDs will continue to display the
selected unit capacity code for two (2) minutes
before defaulting back to the idle mode
{simultaneous slow flash}, or
until the 24 volt
power is cycled to the air conditioner control.
START
Set room thermostat
to
OFF
Go to control terminal
strip
Remove
R
wire
from control (24 volt
AC power)
icomfort
®
enabled
Remove control
wires from
i+
and
i−
terminals
Non − icomfort
®
enabled
Remove control
wire from
Y1
terminal
Place jumper on
FIELD TEST
(E33 pins)
Connect
R
wire to control
(24 volt AC power)
DS14 (Red)
DS11 (Green)
TERMINAL
STRIP
Status LED lights
DS11
and
DS14
will
blink
and
then
on continuously
.
Once both LEDs are on
continuously then remove
jumper immediately from
E33.
Place jumper on
FIELD
TEST
(E33 pins) within 2 to 4
seconds after removal
The control´s DS11 and DS14 LEDs will
start blinking the
Unit Nominal Code
at
three (3) second intervals starting at 1−ton
through to 6−ton. If a code is not selected,
the control will cycle one more time
through the codes before defaulting back
to the idle mode (simultaneous slow
flash).
Long blink
ON
red LED (DS14) to indicate
tonnage and solid
ON
green LED (DS11)
to indicate ½ tonnage.
Model
DS11
Green
LED
Size
DS14
Red LED
−012
−018
−024
−030
−036
−042
−048
−054
−060
−066
−072
1−ton
1.5−ton
2−ton
2.5−ton
3−ton
3.5−ton
4−ton
4.5−ton
5−ton
5.5−ton
6.0−ton
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 long flash
1 long flash
2 long flashes
2 long flashes
3 long flashes
3 long flashes
4 long flashes
4 long flashes
5 long flashes
5 long flashes
6 long flashes
FINISH
Field Test
(E33)
DS12
Communicating
Status Indicator
Sensor harness
must be attached
to air conditioner
control.
Remove
R
wire from
air conditioner control
(24 volt AC power)
Connect
R
wire to
control (24 volt AC
power)
Reconnect any control
wiring previously
removed.
If jumper is not removed
immediately from E33, then DS11
and DS14 LEDs will resume
blinking again.
Remove
R
wire
from control (24 volt
AC power)
Jumper
removed
successfully
YES
NO
Figure 38. Heat Pump Control (A175) Unit Nominal Capacity Code Configuration