Lennox X4147 Скачать руководство пользователя страница 12

Page 12

Instal-
lerSet−
Up No.

Installer
Set−Up
Name

Selection Description

(Factory setting in bold print)

Notes

0120

Date
(Year/
first)

Select first two digits of current calendar
year (

20

 for 

20

07, etc.)

Factory setting = 20.

0130

Date
(Year/
last)

Select last two digits of current calendar
year (

07

 for 20

07

, etc.); 01 to 99 available.

0140

Date
(Month)

Select number that represents current cal-
endar month.

Factory setting = 8.

0150

Date
(Day)

Select number that represents current cal-
endar date.

Factory setting = 19.

0160

Schedule
Options

0 − Non−programmable.

4 − 7−day programming. Factory setting.

0170

System
Type

1 − Single−Stage Heating and Cooling
(Conventional) −− Gas, oil or electric
heating with central air conditioning.
Factory setting.

2 − Single−Stage Heat Pump with No Back−
Up or Auxiliary Heat.

3 − Heat Only without Fan (Conventional).

4

 −

 Heat Only with Fan (Conventional).

5

 

− Hot Water Heat Only (Conventional) −−

Gas or oil hot water heat. Power open/
power close hot water zone valves or nor-
mally open valves.

6 − Cooling Only (Conventional) −− Central
air conditioning only.

7 − Two Heat / One Cool Heat Pump −−
Heat pump with auxiliary or back−up heat.

8

 

− Two Heat / Two Cool Multi−Stage (Con-

ventional).

9

 

− Two Heat / One Cool Multi−Stage (Con-

ventional).

10

 

− One Heat / Two Cool Multi−Stage

(Conventional).

11

 

− Two Heat / Two Cool Heat Pump −− No

auxiliary heat.

12 − Three Heat / Two cool Heat Pump −−
With auxiliary heat.

Available op-
tions and de-
faults vary by
system type.

System type
selection auto-
matically modi-
fies certain de-
fault settings
and installer
set−up options.

table continued on next page

Содержание X4147

Страница 1: ...Screen Thermostat INSTALLATION INSTRUCTIONS WARNING This thermostat is to be installed by a qualified service technician or other qualified agency in accordance with the manufacturer s instruc tions a...

Страница 2: ...es 24V power common from the furnace or air han dler Three AAA alkaline batteries are provided to be used as an alternate power source or as a back up in case of an interruption of power Shipping and...

Страница 3: ...same and the faceplate may fit on the existing wallplate the terminal positions may vary in important ways In addition serial number and part number information is carried on the replacement wall pla...

Страница 4: ...32 for plaster 5 Tap the provided wall anchors into the drilled holes until the back of the anchor head touches the wall surface 6 Position the wallplate over the an chors and pull the thermostat wir...

Страница 5: ...the loosened screws Securely tighten each screw C Y B O R G INSERT WIRE IN HOLE WIRE HOLE WALLPLATE SCREW TERMINALS LETTER DESIGNATIONS LABELED WIRES TERMINAL BLOCK 4 Connect wires to the correspond i...

Страница 6: ...Wiring Diagrams TYPICAL CONVENTIONAL MULTI STAGE APPLICATION TWO STAGE HEAT TWO STAGE COOL TYPICAL MULTI STAGE HEAT PUMP APPLICATION NO AUXILIARY HEAT TYPICAL MULTI STAGE HEAT PUMP APPLICATION WITH AU...

Страница 7: ...Page 7 Field Wiring Diagrams Continued TYPICAL SINGLE STAGE HEAT PUMP SYSTEM WITH AUXILIARY HEAT TYPICAL SINGLE STAGE HEAT PUMP SYSTEM WITHOUT AUXILIARY HEAT...

Страница 8: ...on power at the furnace or air handler or at the fuse or circuit breaker PINS ON BACK OF THERMOSTAT WALLPLATE TERMINAL SCREW BLOCK Set Calendar and Clock This thermostat is designed to auto matically...

Страница 9: ...is selected using Installer Set Up Num ber 0350 Heating Mode Operation Outdoor Temp below Balance Point When the outdoor temperature is be low the selected balance point only the furnace fossil fuel...

Страница 10: ...he compressor lock out tempera ture balance point only the auxiliary heat operates When the outdoor temperature is above the auxiliary lock out tempera ture balance point only the compres sor operates...

Страница 11: ...he installer set up number is dis played on the left hand side of the screen The current installer set up number is displayed on the right hand side of the screen Use the up and down arrows on the rig...

Страница 12: ...with central air conditioning Factory setting 2 Single Stage Heat Pump with No Back Up or Auxiliary Heat 3 Heat Only without Fan Conventional 4 Heat Only with Fan Conventional 5 Hot Water Heat Only Co...

Страница 13: ...outdoor temperature sensor and installer set up number 0340 must be set to selection 2 1 External fossil fuel kit is controlling heat pump auxiliary heat Factory set ting Shown only in heat pump ap pl...

Страница 14: ...higher furnaces 5 Recommended for use with standard efficiency less than 90 fossil fuel fur naces 9 Recommended for use with electric furnaces or electric auxiliary heat Fac tory setting Settings of 1...

Страница 15: ...t savings enabled using pre 2007 calendar Factory setting 2 Daylight savings enabled using 2007 DST calendar all US some Canada Set to 0 in areas that do not follow day light savings 0340 Remote Outdo...

Страница 16: ...midifier pad replacement remind er off Factory setting 1 90 run time days 2 180 run time days 3 365 run time days 0520 UV Lamp Replace ment Re minder 0 UV lamp replacement reminder off Factory setting...

Страница 17: ...eration after cooling demand satisfied Factory set ting 90 Fan operation continues for 90 sec onds after cooling demand satisfied Not shown in heat only sys tems 0670 Keypad Lock Out 0 Keypad unlocked...

Страница 18: ...gressive control Cooling may remain on after setpoint reached Applies to re covery ramp 0700 Tempera ture Dis play Off set 3 F 1 5 C 2 F 1 C 1 F 5 C 0 No difference in displayed tempera ture and actua...

Страница 19: ...e tested 5 Refer to the following table to se lect proper test options CAUTION While the system is in the test mode the compressor mini mum off time is bypassed Installer Test No Installer Set Up Name...

Страница 20: ...system to respond Heating or cooling does not come on System selection has not been set to heat or cool Select proper system mode not come on System type selection is incorrect Check installer set up...

Отзывы: