background image

1

©2018 Lennox Industries Inc. Dallas, Texas, USA

INSTALLATION

INSTRUCTION 

VRF SYSTEMS -- Indoor Units

507887-01

12/2018

THIS MANUAL MUST BE LEFT WITH THE OWNER 

FOR FUTURE REFERENCE

Shipping and Packing List 

General

Check the components for shipping damage. If you find 

any damage, immediately contact the last carrier.
Package 1 of 2 contains the following:
1 - Assembled indoor unit with mounting bracket
8 - Mounting bracket securing screws
8 - Plastic screw anchors
1 - Roll tape
1 - Flexible condensate drain pipe
1 - Wall sleeve
1 - Plastic cover for wall sleeve
1 - Resistor
2 - Brass flare nut
1 - Water level switch cable
1 - Installation manual

The VWMB wall-mounted indoor units are matched with 

an outdoor heat recovery or heat pump unit to create a 

VRF (variable refrigerant flow) system that uses R-410A 

refrigerant. VWMB indoor units are designed for indoor 

installation only. 
Refer to the Product Specification bulletin (EHB) for the 

proper use of these indoor units with specific heat pumps, 

heat recovery units, mode switching devices, branch
pipes, line sets and controls.
These instructions are intended as a general guide and do 

not supersede local or national codes in any way. 
Authorities having jurisdiction should be consulted before 

installation.

VWMB Wall-Mounted Units

These instructions are intended as a general guide and do 

not supersede local codes in any way. Consult authorities 

having jurisdiction before installation.

 WARNING

Improper installation, adjustment, alteration, ser vice or 

maintenance can cause property damage, personal 

injury or loss of life.

Installation and service must be performed by a li censed 

professional HVAC installer, service agency or the gas 

supplier.

Failure to follow safety warnings and these instruc tions 

exactly could result in property damage, dan gerous 

operation, serious injury, or death.

Any additions, changes, or conversions required in order 

for the appliance to satisfactorily meet the ap plication 

needs must be made by a licensed profes sional HVAC 

installer (or equivalent) using factory-specified parts.

Do not use this system if any part has been under water. 

A  flood-damaged  appliance  is  extremely  dan gerous. 

Immediately call a licensed professional HVAC service 

technician (or equivalent) to inspect the system and to 

replace all controls and electrical parts that have been 

wet, or to replace the system, if deemed necessary.

 CAUTION

As with any mechanical equipment, contact with sharp 

sheet metal edges can result in personal injury. Take 

care while handling this equipment and wear gloves and 

protective clothing.
To ensure proper system performance and reliability, 

Lennox does not recommend operation of VRF systems 

during any phase of construction. Construction debris, 

low temperatures, harmful vapors, and operation of the 

unit with misplaced filters can damage the units. Failure 

to follow these guidelines will result in the warranty 

being voided.

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting 

of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 

1992. Approved methods of recovery, recycling or 

reclaiming must be followed. Fines and/or incarceration 

may be levied for noncompliance. These units must be 

installed as a part of a matched system as specified in 

the Product Specifications (EHB) bulletin.

VRF

Содержание VRF VWMB Series

Страница 1: ...injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow safety warnings and these instruc tio...

Страница 2: ...se of a different rating Do not use a jumper wire to replace a fuse Do not insert your hands tools or any other item into the air intake or air outlet at either the indoor or outdoor unit Do not allow...

Страница 3: ...879 39 991 12 3 8 314 7 1 2 191 4 1 2 114 VWMB007H4 VWMB009H4 VWMB012H4 VWMB015H4 VWMB018H4 27 686 BOTTOM VIEW SIDE VIEW SIDE VIEW 8 7 8 225 42 1 2 1080 47 1194 13 1 2 343 10 3 8 264 VWMB024H4 VWMB030...

Страница 4: ...t of the unit Install the indoor unit a minimum of 3 feet away from any antenna power cord line radio telephone security system or intercom Electrical interference and radio frequencies from any of th...

Страница 5: ...e installed level on the wall to allow proper condensate drainage 1 Use a carpenter s level or measuring tape to verify the wall mounting plate is horizontally level 2 Secure the wall mounting plate t...

Страница 6: ...of copper pipe and wiring can deteriorate when exposed to these construction materials USE SUITABLE TOOL TO CUT PVC FOR WALL SLEEVE AT SLIGHT ANGLE AS SHOWN Figure 4 Cutting PVC for Wall Sleeve Insta...

Страница 7: ...connections should always be accessible and must be insulated to prevent condensation 9 After refrigerant piping has been installed and checked for leaks apply insulation over the connector pipe and a...

Страница 8: ...ll drain freely 4 After system installation is complete the condensate drain line must be checked for leaks This check is part of the commissioning sequence If a field provided condensate pump has bee...

Страница 9: ...X87 721 14T69 3 7 23 16 5 ft VWMB024H4 VWMB030H4 MaxiBlue w DrainStik X87 722 17A23 3 7 23 16 5 ft Optional pump maximum suction lift is measured from the pump outlet Table 3 Condensate Pump Accessory...

Страница 10: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Страница 11: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Страница 12: ...agram VRF Heat Pump System NOTE PQE Communication wiring is daisy chained from the outdoor unit to each indoor unit in one continuous run Tightening torque for the terminal screws Use the correct scre...

Страница 13: ...WIRING Display panel To Outdoor COMM BUS To wired Controller COMM BUS HA HB COM P 12V Q GRAY YELLOW BLUE WHITE BLACK RED HHE interface FAN CTON HTON AUXH NET0 NET1 Current range 0 1A Voltage range 0...

Страница 14: ...HITE BLACK RED NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING NOTE 1 REFER TO MANUAL FOR COMMUNICATION WIRING 2 PLEASE USE THE 3 CONDUCTOR SHIELDED CABLE T2A T2 T1 T2B RED WHITE BLUE BLACK Di...

Страница 15: ...le Spot Check Instructions This Spot Check Performance table is located on the unit service panel The diagnostic information can also be obtained using the wired remote controller No Content Recorded...

Страница 16: ...codes The error code will replace the temperature setting displayed on the receiver If more than one error has occurred the codes will alternate so that all codes are shown Figure 32 Receiver Display...

Страница 17: ...17 Technical Support 1 844 GET VRF1 1 844 438 8731 vrftechsupport lennoxind com www LennoxVRF com Download the app from the Apple App Store or the Google Play store...

Отзывы: