background image

1

©2018 Lennox Industries Inc.  Dallas, Texas, USA

INSTALLATION

INSTRUCTION 

VRF SYSTEMS -- Indoor Units

507890-02

01/2019

THIS MANUAL MUST BE LEFT WITH THE OWNER 

FOR FUTURE REFERENCE

Shipping and Packing List 

Check the components for shipping damage. If you find 

any damage, immediately contact the last carrier.
Package 1 of 1 contains the following:
1 - Assembled indoor cassette unit base
8 - Nuts
8 - Washers
4 - Cover panel screws
5 - Wire ties

1 - Condensate drain flexible pipe

1 - Condensate drain insulation sleeve
1 - Clasp
1 - Cable
2 - Refrigerant pipe insulation 

2 - Brass flare nuts

1 - Template
1 - Installation manual

NOTE - 

Assembled indoor unit cover panel is required for 

complete installation and must be ordered separately.

The V33B 360º cassette indoor units are matched with an 

outdoor heat recovery or heat pump unit to create a VRF 

(variable  refrigerant  flow)  system  that  uses  HFC-410A 

refrigerant. V33B indoor units are designed for indoor 

installation only. 

Refer to the Product Specification bulletin (EHB) for the 

proper use of these indoor units with specific heat pumps, 

heat recovery units, mode switching devices, branch 

pipes, line sets and controls.
These instructions are intended as a general guide and 

do not supersede local or national codes in any way. 

Authorities having jurisdiction should be consulted before 

installation.

V33B 360º Cassette Units

These instructions are intended as a general guide and do 

not supersede local codes in any way. Consult authorities 

having jurisdiction before installation.

 WARNING

Improper installation, adjustment, alteration, ser vice or 

maintenance can cause property damage, personal 

injury or loss of life.

Installation and service must be performed by a li censed 

professional HVAC installer, service agency or the gas 

supplier.

Failure to follow safety warnings and these instruc tions 

exactly could result in property damage, dan gerous 

operation, serious injury, or death.

Any additions, changes, or conversions required in order 

for the appliance to satisfactorily meet the ap plication 

needs must be made by a licensed profes sional HVAC 

installer (or equivalent) using factory-specified parts.

Do not use this system if any part has been under water. 

A  flood-damaged  appliance  is  extremely  dan gerous. 

Immediately call a licensed professional HVAC service 

technician (or equivalent) to inspect the system and to 

replace all controls and electrical parts that have been 

wet, or to replace the system, if deemed necessary.

 CAUTION

As with any mechanical equipment, contact with sharp 

sheet metal edges can result in personal injury. Take 

care while handling this equipment and wear gloves and 

protective clothing.

To ensure proper system performance and reliability, 

Lennox does not recommend operation of VRF sys-

tems during any phase of construction. Construction 

debris, low temperatures, harmful vapors, and opera-

tion of the unit with misplaced filters can damage the 

units. Failure to follow these guidelines will result in the 

warranty being voided.

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting 

of  refrigerant  (CFCs,  HCFCs  and  HFCs)  as  of  July 

1, 1992. Approved methods of recovery, recycling or 

reclaiming must be followed. Fines and/or incarceration 

may be levied for noncompliance. These units must be 

installed as a part of a matched system as specified in 

the Product Specifications (EHB) bulletin.

General

VRF

Содержание VRF V33B Series

Страница 1: ...ce can cause property damage personal injury or loss of life Installation and service must be performed by a li censed professional HVAC installer service agency or the gas supplier Failure to follow...

Страница 2: ...s are similar in appearance but must not be connected to a Lennox VRF refrigerant circuit Please refer to model numbers to confirm compatibility Model numbers for Lennox VRF units start with a V and m...

Страница 3: ...ID PIPE 1 3 4 44 SIDE VIEW 34 5 8 879 Ceiling Opening AIR OUTLET AIR INLET AIR OUTLET LEVELING ADJUSTMENT NUT 4 INSTALLATION HANGERS 4 DIFFUSER PANEL CEILING DRAIN PIPE BOTTOM PANEL VIEW SIDE VIEW LIQ...

Страница 4: ...p Ceiling 10 1 4 inches 260 mm 007 009 012 015 models 13 inches 330 mm 015 018 024 030 036 048 models Minimum Clearance to Floor 90 inches 2286 mm Maximum Clearance to Floor 160 inches 4064 mm Minimum...

Страница 5: ...ord line radio telephone security system or intercom Electrical interference and radio frequencies from any of these sources may affect operation WARNING Do not install the unit in an area where flamm...

Страница 6: ...It may be necessary to add extra support If the structural support is constructed of concrete install anchors to accept four threaded rods to suspend the cassette base If the structural support includ...

Страница 7: ...and discard the seal from each of the piping connections 4 Slide the flare nuts onto the ends of the field provided refrigerant piping before using a suitable flaring tool to flare the end of the cop...

Страница 8: ...se an appropriately sized wrench to turn an additional Inches U S 1 4 15 ft lb 1 4 turn 3 8 26 ft lb 1 2 turn 1 2 41 ft lb 7 8 turn 5 8 48 ft lb 1 full turn Table 2 Flare Nut Torque Recommendations IM...

Страница 9: ...loped no less than 1 4 inch per foot and that each individual drain is connected to the main drain exactly as shown 5 Drain should be as short as possible and should not have any droops or kinks that...

Страница 10: ...a ballast The ballast may affect remote control operation 2 Locate the terminal strip in the control box Connect the power wiring sized per NEC CEC and local codes and communications cable per Figure...

Страница 11: ...tdoor Unit Main Unit L1 L2 L3 Outdoor Unit Sub1 unit L1 L2 L3 Outdoor Unit Sub2 Unit L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 Service Disconnect Service Disconnect Service Discon...

Страница 12: ...olarity sensitive Typical Wiring Diagram NEC CEC and Local Codes apply Outdoor unit Outdoor unit sub1 unit Outdoor unit sub2 unit PQ main unit PQ MS Box PQ PQ MS Box PQ PQ H1 H2 H1 H2 H1 H2 Outdoor Un...

Страница 13: ...htening Torque Tightening torque lb ft Terminal base of remote controller Signal transmission wire X2M 0 58 0 72 Terminal base of power supply X1M 0 87 1 06 Grounding terminal M4 1 06 1 43 PQ PQ Outdo...

Страница 14: ...erials must be listed ANSI UL and ASTM E 84 approved NOTE A maximum of two sides can be blanked off 1 Remove the decorative cover panel if installed 2 Identify and measure the supply air opening that...

Страница 15: ...15 Figure 16 Three way Outlet Possible Flow Patterns Figure 17 Two way Outlet Possible Flow Patterns Typical cassette body shown actual unit may vary...

Страница 16: ...18 4 Remove any insulation 5 Connect the secondary supply duct to the cassette body using the eight screw holes shown in figure 18 6 A field supplied duct transition may be required Be sure there is a...

Страница 17: ...panel See Figure 21 Figure 21 Remove Corner Covers 4 Position the ceiling panel so that the arrow on the panel is aligned with the arrow sticker on the cassette base both arrow stickers should be on...

Страница 18: ...ake sure that the panel is properly aligned with the cassette base 9 Continue to tighten the cover panel securing screws until the insulation between the cover panel and the cassette base has been com...

Страница 19: ...nate so that all codes are shown Make note of the code E1 EE etc then reset the display by pressing the ON OFF button on the unit controller Press the ON OFF button a second time to reapply power to u...

Страница 20: ...E4 T2B Outlet of evaporator sensor malfunction E5 T2A Inlet of evaporator sensor malfunction E6 DC fan motor error E7 EEPROM failure Eb EXV malfunction Ed Outdoor unit Fault EE High Water Alarm A0 Em...

Отзывы: