42
Table 14. Spot Check Performance Menu in Parallel Control Mode 2, SW5-3=1
No.
Content
Note
0
Address of Sub Kit
1~3
1
--
2
Dial code of indoor unit capacity (Total of AHU Control Kits in parallel)
3
--
4
--
5
--
6
The actual evaporator inlet temperature sensor T2
7
The actual middle evaporator temperature T2A
8
The actual evaporator outlet temperature T2B
9
The actual superheat (SH) (Cooling Mode)
10
The actual subcooling (Heating Mode)
11
The opening of EXV. (multiply by 8)
12
Error code
13
Indoor software version
14
--
15
--
This Spot Check Performance table is located on the unit service panel. The diagnostic information can also be
obtained using the wired remote controller.
Check
Value
Date
Initials
0
Normal display
1
Communication address of indoor unit
2
Dial code of indoor unit capacity
3
Network address of indoor unit
4
The actual setpoint temperature
5
The actual indoor temperature T1
6
The actual evaporator inlet temperature sen-
sor T2
7
The actual middle evaporator temperature
T2A
8
The actual evaporator outlet temperature T2B
9
The actual superheat (SH) (Cooling Mode)
10
The actual subcooling (Heating Mode)
11
The opening of EXV. (multiply by 8)
12
Error code
13
Indoor software version
14
The quantity of AHU Control kits in parallel
Table 15. Spot Check Performance Tracking Register