Multi Variable Air Conditioners Cassette Type Indoor Unit
7
3.4 Electric Installation
Model
Power Supply
MOP(A)
MCA(A)
VE4C007C432P
208~230V-1ph-60Hz
0.45
0.25
VE4C009C432P
0.56
0.31
VE4C012C432P
0.56
0.31
VE4C015C432P
0.56
0.31
VE4C018C432P
0.56
0.31
VE4C024C432P
0.56
0.31
VE4C030C432P
0.79
0.44
VE4C036C432P
0.79
0.44
VE4C042C432P
0.79
0.44
VE4C048C432P
0.79
0.44
NOTICE
(1)
An all-pole disconnection switch having a contact separation of at least 3mm(1/8 inch) in all
poles should be connected in fixed wiring.
(2)
The circuit breaker and power cord specification in above sheet is based on max power(max
current) of the unit.
(3)
The power cord specification in above sheet is based on ambient temperature of 40
(104°F).
(4)
The circuit breaker specification in above sheet is based on ambient temperature of 40
(104°F).
If the working condition is different, please adjust it according to the specification sheet of circuit
breaker.