background image

3DJH 

Expansion Valve Systems

Expansion valves equipped with either “Chatleff” or

flare type fittings are available from Lennox. Refer to

the indoor coil installation instructions or the engineer-

ing handbook for applicable expansion valves for use

with specific match--ups.
If an expansion valve application is desired with indoor

coil product shipped with an RFCIV orifice, the RFCIV re-

strictor must be removed before installing the expan-

sion valve.

IMPORTANT

Failure to remove RFCIV when installing an expan-

sion valve to the indoor coil will result in improper

operation and damage to the system.

0$1,)2/' *$8*( 6(7

A manifold gauge set equipped with “low loss” hoses

should be used when checking unit charge. A manifold

gauge set with anything other than “low loss” hose

should not be used.

/,48,'   68&7,21 /,1( 6(59,&( 9$/9(6

The liquid line and suction line service valves (figures 4

and 5) and gauge ports are accessible from outside the

unit. The service ports are used for leak testing, eva-

cuating, charging and checking charge.
The valve is equipped with a service port. A schrader

valve is factory installed. A service port cap is supplied to

protect the schrader valve from contamination and serve

as the primary leak seal.

To Access Schrader Port:

1-- Remove service port cap with an adjustable wrench.
2-- Connect gauge to the service port.
3-- When testing is completed, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1-- Remove stem cap with an adjustable wrench.
2-- Using service wrench and 5/16” hex head extension

back the stem out counterclockwise until the valve

stem just touches the retaining ring.

Do not attempt to backseat this valve. Attempts to

backseat this valve will cause snap ring to explode

from valve body under pressure of refrigerant.

Personal injury and unit damage will result.

'$1*(5

3-- Replace stem cap tighten firmly. Tighten finger tight,

then tighten an additional 1/6 turn.

FIGURE 4

LIQUID LINE SERVICE VALVE (VALVE OPEN)

SCHRADER

VALVE

SERVICE

PORT

SERVICE

PORT

CAP

INSERT HEX

WRENCH HERE

TO INDOOR

COIL

TO OUTDOOR

COIL

STEM CAP

SCHRADER VALVE OPEN

TO LINE SET WHEN VALVE

IS CLOSED (FRONT SEATED)

SERVICE

PORT

SERVICE

PORT CAP

RETAINING RING

STEM CAP

INSERT HEX

WRENCH HERE

LIQUID LINE SERVICE VALVE (VALVE CLOSED)

(VALVE FRONT SEATED)

TO OUTDOOR

COIL

TO INDOOR

COIL

To Close Liquid or Suction Line Service Valve:

1-- Remove stem cap with an adjustable wrench.
2-- Using service wrench and 5/16” hex head exten-

sion, turn stem clockwise to seat the valve. Tighten

firmly.

All manuals and user guides at all-guides.com

Содержание Value 10ACB Series

Страница 1: ...LHV RQGHQVLQJ 8QLWV 21 16 1 81 76 1 1 2 through 5 ton 503 800M 2 98 Supersedes 503 755M TABLE OF CONTENTS VALUE 10 CONDENSING UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFORMATION 1 10ACB UNIT DIMENS...

Страница 2: ...COIL FAN COMPRESSOR INLET AIR INLET AIR SUCTION LINE CONNECTION B 24 1 4 616 3 4 19 2 3 4 70 24 1 4 616 ELECTRICAL INLETS LIQUID LINE CONNECTION Model No A B 10ACB12 10ACB18 in 25 24 1 4 10ACB18 10AC...

Страница 3: ...on diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with nation al and local codes Electric Shoc...

Страница 4: ...SUCTION LINE L10 LINE SETS 10ACB24 10ACB30 10ACB42 3 8 in 10 mm 3 4 in 19 mm L10 41 20 ft 50 ft 6 m 15 m 10ACB18 5 16 in 8 mm 3 8 in 10 mm L10 65 30 ft 50 ft 9 m 15 m L10 21 20 ft 50 ft 6 m 15 m 5 8 i...

Страница 5: ...he primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger...

Страница 6: ...TEM USE ADJUSTABLE WRENCH ROTATE STEM CLOCKWISE 90E TO CLOSE ROTATE STEM COUNTER CLOCKWISE 90E TO OPEN BALL SHOWN OPEN TO OUTDOOR COIL TO INDOOR COIL 7 67 1 After the line set has been connected to th...

Страница 7: ...urs the leak testing procedure must be repeated NOTE The term absolute pressure means the to tal actual pressure within a given volume or sys tem above the absolute zero of pressure Absolute pressure...

Страница 8: ...t 6 1m line set 3 8 in 10mm 5 16 in 8mm 2 ounce per 5 ft 57ml per 1 5m 3 ounce per 5 ft 85ml per 1 5m If line length is greater than 20 ft 6 1m add this amount If line length is less than 20 ft 6 1m s...

Страница 9: ...e sys tem Used prudently table 4 could serve as a useful service guide Before charging the unit follow the procedure below to determine the liquid line temperature and the out door ambient temperature...

Страница 10: ...Liquid Line EF EC Out door Ambient EF EC Approach Temperature The resulting difference Approach temperature should agree with the values given in table 6 If not add refrig erant to lower the approach...

Страница 11: ...nd coils for evi dence of oil leaks 3 Check wiring for loose connections 4 Check for correct voltage at unit unit operating 5 Check condenser fan motor amp draw Unit nameplate _________ Actual _______...

Страница 12: ...H 6WDWH 6WDWH 6HUYLFH WHFKQLFLDQ PSV 6XSSO RQGHQVHU DQ RPSUHVVRU QGRRU LOWHU OHDQ QGRRU ORZHU 0 6XSSO 9ROWDJH 8QLW 2II 6 3 URS 2YHU YDSRUDWRU U RQGHQVHU QWHULQJ LU 7HPSHUDWXUH LVFKDUJH 3UHVVXUH 6XFWLR...

Отзывы: