background image

Page 25

TSA*S4 SERIES

System Operation

IMPORTANT

Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.

The outdoor unit and indoor blower cycle on demand from
the room thermostat.  When the thermostat blower switch
is in the 

ON

 position, the indoor blower operates

continuously.

HIGH PRESSURE SWITCH (S4)

TSA*S4 units are equipped with a high-pressure switch
that is located in the liquid line of the compressor as
illustrated in figure 1 on page 2.

MANUAL RESET

BUTTON

Figure 22. High Pressure Switch (S4) Manual Reset

The switch is a Single Pole, Single Throw (SPST),
manual−reset switch which is normally closed and
removes power from the compressor when discharge
pressure rises above factory setting at 590 + 10 psi. The
manual−reset button can be identified by a red cap that is
press to preform the reset function.

Crankcase Heater (HR1)

Crankcase heater HR1 prevents liquid from accumulating
in the compressor. The heater is always on when the
compressor is off. An optional crankcase heater
thermostat (S40) is available.

Table 8. Crankcase Heaters

Parts

Watts

Voltage

M Voltage

40

480

T Voltage

40

240

Maintenance

DEALER

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:

WARNING

Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect
switch(es). Unit may have multiple power
supplies.

WARNING

Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.

Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.

Outdoor Unit

1. Outdoor unit fan motor is pre−lubricated and sealed.

No further lubrication is needed.

2. Visually inspect all connecting lines, joints and coils for

evidence of oil leaks.

3. Check all wiring for loose connections.

4. Check for correct voltage at unit (unit operating).

5. Check amp draw on outdoor fan motor.

Motor

 

Nameplate

:_________ 

Actual

:__________.

6. Inspect drain holes in coil compartment base and

clean if necessary.

NOTE - If insufficient cooling occurs, the unit should be
gauged and refrigerant charge should be checked.

Outdoor Coil

Clean and inspect outdoor coil (may be flushed with a
water hose). Ensure power is off before cleaning.

NOTE  It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)

Sea Coast

  Moist air in ocean locations can carry salt,

which is corrosive to most metal. Units that are located
near the ocean require frequent inspections and
maintenance. These inspections will determine the
necessary need to wash the unit including the outdoor coil.
Consult your installing contractor for proper
intervals/procedures for your geographic area or service
contract.

Indoor Unit

1. Clean or change filters.

2. Lennox blower motors are prelubricated and

permanently sealed. No more lubrication is needed.

Содержание T?Class TSA*S4 Units

Страница 1: ...rting on page 9 to avoid damaging the service valve s internal seals INSTALLATION INSTRUCTIONS T Classt TSA S4 Units M and T Voltages AIR CONDITIONER 506663 01 11 10 Supersedes 506418 01 TABLE OF CONT...

Страница 2: ...036S4N41T 24 1 4 616 29 1 4 743 TSA048S4N41T and M 28 1 4 724 37 1 4 925 TSA060S4N41T and M 28 1 4 724 33 1 4 845 Typical Unit Parts Arrangement GROUND LUG CONTROL CUTOUT FOR HIGH VOLTAGE CONDUIT OR C...

Страница 3: ...ide and do not supersede local codes in any way Consult authorities who have jurisdiction before installation TORQUE REQUIREMENTS When servicing or repairing heating ventilating and air conditioning c...

Страница 4: ...liquid line valve sizes and 5 16 for vapor line valve sizes to back the stem out counterclockwise as far as it will go Operating Ball Type Service Valve 1 Remove stem cap with an appropriately sized...

Страница 5: ...the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction...

Страница 6: ...away from windows Two 90 elbows installed in line set will reduce line set vibration Figure 5 Placement and Slab Mounting New Outdoor Unit Placement See Unit Dimensions on page 2 for sizing mounting s...

Страница 7: ...to communicate the following points Model TSA S4 and size of unit e g 060 Line set diameters for the unit being installed as listed in table 2 and total length of installation Number of elbows and if...

Страница 8: ...ROOF RAFTER TAPE OR WIRE TIE To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties 8 FEET 2 43 METERS STRAP THE VAPOR LINE TO THE JOIST OR RAFTER...

Страница 9: ...stem may result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING When using a high pressure gas such as dry nitrogen to pressurize a refrige...

Страница 10: ...AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valv...

Страница 11: ...CE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction li...

Страница 12: ...ifice housing Take care not to twist or damage distributor tubes during this process G Remove and discard check expansion valve and the two Teflon rings H Use a field provided fitting to temporary rec...

Страница 13: ...DISTRIBUTOR ASSEMBLY A Remove the field provided fitting that temporary reconnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stub...

Страница 14: ...UNIT HIGH LOW NITROGEN A With both manifold valves closed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only...

Страница 15: ...and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F...

Страница 16: ...per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only with copper conductors Ground unit at disconnect switch or to an earth ground SIZE CIRCUIT AND I...

Страница 17: ...A Run 24VAC control wires through hole with grommet and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field...

Страница 18: ...Page 18 506663 01 11 10 Figure 14 Typical Field Wiring Diagram M Voltage 380 420v 3PH 50Hz...

Страница 19: ...Page 19 TSA S4 SERIES Figure 15 Typical Field Wiring Diagram T Voltage 220 240v 1PH 50Hz...

Страница 20: ...for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the refrigerant charge contained in outdoor unit into the system 4 Replace the ste...

Страница 21: ...ARGE IN LIQUID PHASE CONNECTIONS FOR TESTING AND CHARGING GAUGE SET A C D LOW HIGH B SUCTION LINE SERVICE PORT CONNECTION Figure 17 Gauge Set Setup and Connections WHEN TO CHARGE Warm weather best Can...

Страница 22: ...6 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18...

Страница 23: ...t to call for cooling 7 Allow temperatures and pressures to stabilize NOTE If necessary block outdoor coil to maintain325 375 psig 8 Record liquid line temperature LIQ ______ 9 Measure liquid line pre...

Страница 24: ...4 156 115 45 507 152 497 147 487 148 498 149 492 157 Temperature of the air entering the outside coil Table 6 HFC 410A Normal Operating Pressures Liquid 10 and Suction 5 Psig 3 Phase TSA S4 50Hz Inter...

Страница 25: ...rvice or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies WARNING Improper installation adjustment alteration service or maintenance can...

Страница 26: ...d by spraying unpressurized water from inside coil surface to the outside the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage 3 Then using plier...

Страница 27: ...t switches are ON Check for any blown fuses or tripped circuit breakers Verify unit access panels are in place Verify air filter is clean If service is needed locate and write down the unit model numb...

Страница 28: ......

Отзывы: