background image

Page 12

506663−01 11/10

Flushing Line Set and Indoor Coil 

Flushing is only required if existing indoor coil and line set are to be used.  Otherwise proceed to 

Installing Indoor Metering

Device 

on page 13.

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor as-
sembly.

C

Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro-
cess.

D

Remove and discard fixed orifice, valve stem assembly if present and
Teflon

®

 washer as illustrated above.

E

Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE
(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE
REMOVAL PROCEDURE (UNCASED COIL
SHOWN)

TWO PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

CHECK

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor
assembly.

C

Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.

D

Remove the vapor line sensing bulb.

E

Disconnect the liquid line from the check expansion valve at the liquid
line assembly.

F

Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.

G

Remove and discard check expansion valve and the two Teflon

®

 rings.

H

Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

INVERTED  CYLINDER
CONTAINS CLEAN  TO
BE USED FOR
FLUSHING.

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

V

APOR

LIQUID

1

A

Inverted  cylinder with clean refrigerant to the vapor service valve.

B

 gauge set (low side) to the liquid line valve.

C

 gauge set center port to inlet on the recovery machine with an empty
recovery tank to the gauge set.

D

Connect recovery tank to recovery machines per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

A

Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.

B

Invert the cylinder of clean  and open its valve to allow liquid
refrigerant to flow into the system through the vapor line valve.
Allow the refrigerant to pass from the cylinder and through the
line set and the indoor unit coil before it enters the recovery
machine.

C

After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the  vapor is
recovered. Allow the recovery machine to pull down to 0 the
system.

D

Close the valve on the inverted  drum and the gauge set valves.
Pump the remaining refrigerant out of the recovery machine and
turn the machine off.

The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.

1A

2

3

1B

Figure 10. Removing Metering Device and Flushing

Содержание T?Class TSA*S4 Units

Страница 1: ...rting on page 9 to avoid damaging the service valve s internal seals INSTALLATION INSTRUCTIONS T Classt TSA S4 Units M and T Voltages AIR CONDITIONER 506663 01 11 10 Supersedes 506418 01 TABLE OF CONT...

Страница 2: ...036S4N41T 24 1 4 616 29 1 4 743 TSA048S4N41T and M 28 1 4 724 37 1 4 925 TSA060S4N41T and M 28 1 4 724 33 1 4 845 Typical Unit Parts Arrangement GROUND LUG CONTROL CUTOUT FOR HIGH VOLTAGE CONDUIT OR C...

Страница 3: ...ide and do not supersede local codes in any way Consult authorities who have jurisdiction before installation TORQUE REQUIREMENTS When servicing or repairing heating ventilating and air conditioning c...

Страница 4: ...liquid line valve sizes and 5 16 for vapor line valve sizes to back the stem out counterclockwise as far as it will go Operating Ball Type Service Valve 1 Remove stem cap with an appropriately sized...

Страница 5: ...the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction...

Страница 6: ...away from windows Two 90 elbows installed in line set will reduce line set vibration Figure 5 Placement and Slab Mounting New Outdoor Unit Placement See Unit Dimensions on page 2 for sizing mounting s...

Страница 7: ...to communicate the following points Model TSA S4 and size of unit e g 060 Line set diameters for the unit being installed as listed in table 2 and total length of installation Number of elbows and if...

Страница 8: ...ROOF RAFTER TAPE OR WIRE TIE To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties 8 FEET 2 43 METERS STRAP THE VAPOR LINE TO THE JOIST OR RAFTER...

Страница 9: ...stem may result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING When using a high pressure gas such as dry nitrogen to pressurize a refrige...

Страница 10: ...AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valv...

Страница 11: ...CE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction li...

Страница 12: ...ifice housing Take care not to twist or damage distributor tubes during this process G Remove and discard check expansion valve and the two Teflon rings H Use a field provided fitting to temporary rec...

Страница 13: ...DISTRIBUTOR ASSEMBLY A Remove the field provided fitting that temporary reconnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stub...

Страница 14: ...UNIT HIGH LOW NITROGEN A With both manifold valves closed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only...

Страница 15: ...and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F...

Страница 16: ...per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only with copper conductors Ground unit at disconnect switch or to an earth ground SIZE CIRCUIT AND I...

Страница 17: ...A Run 24VAC control wires through hole with grommet and secure with provided wire tie B Make 24VAC thermostat wire connections Locate the two wires from the contactor and make connection using field...

Страница 18: ...Page 18 506663 01 11 10 Figure 14 Typical Field Wiring Diagram M Voltage 380 420v 3PH 50Hz...

Страница 19: ...Page 19 TSA S4 SERIES Figure 15 Typical Field Wiring Diagram T Voltage 220 240v 1PH 50Hz...

Страница 20: ...for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the refrigerant charge contained in outdoor unit into the system 4 Replace the ste...

Страница 21: ...ARGE IN LIQUID PHASE CONNECTIONS FOR TESTING AND CHARGING GAUGE SET A C D LOW HIGH B SUCTION LINE SERVICE PORT CONNECTION Figure 17 Gauge Set Setup and Connections WHEN TO CHARGE Warm weather best Can...

Страница 22: ...6 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18...

Страница 23: ...t to call for cooling 7 Allow temperatures and pressures to stabilize NOTE If necessary block outdoor coil to maintain325 375 psig 8 Record liquid line temperature LIQ ______ 9 Measure liquid line pre...

Страница 24: ...4 156 115 45 507 152 497 147 487 148 498 149 492 157 Temperature of the air entering the outside coil Table 6 HFC 410A Normal Operating Pressures Liquid 10 and Suction 5 Psig 3 Phase TSA S4 50Hz Inter...

Страница 25: ...rvice or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies WARNING Improper installation adjustment alteration service or maintenance can...

Страница 26: ...d by spraying unpressurized water from inside coil surface to the outside the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage 3 Then using plier...

Страница 27: ...t switches are ON Check for any blown fuses or tripped circuit breakers Verify unit access panels are in place Verify air filter is clean If service is needed locate and write down the unit model numb...

Страница 28: ......

Отзывы: