background image

Page 15

STEP 2 Confirm DC voltage output on compressor
solenoid plug

A

 − Compressor solenoid plug 

WITH 

built in full wave−

rectifier (LSOM I) that converts 24 volt AC into 24 volt DC
power. See Table 1 for units equipped with the LSOM I.

1. Shut power off to outdoor unit.

2. Supply 24 volts AC control voltage to the wire ends of

the full wave rectifier plug. Listen for a click" as the so-
lenoid is energized. See figure 14.

compressor

solenoid fusite

terminals

compressor

fusite

terminals

meter

rectifier plug leads

apply 24vac

FIGURE 14

3. Unplug the full wave rectifier plug from the fusite con-

nection on the compressor.

4. Turn the low voltage power back onto the unit. Supply

24VAC to the wires of the full wave rectifier plug. Set
volt meter to DC volts and measure the DC voltage at
the female connector end of the full wave rectifier plug.
The DC voltage reading should be 1.5 to 3 volts lower
than the input voltage to the plug wire leads. (EX: Input
voltage is 24VAC output voltage is 22VDC).
See figure 15.

meter

rectifier plug leads

compressor

fusite

terminals

solenoid

fusite

terminals

compressor

apply 24vac

FIGURE 15

If the above checks verify that the solenoid plug is pro-
viding power to cycle into high capacity operation, contin-
ue to step 3 to determine if problem is with solenoid coil
in compressor

STEP 3 Confirm internal unloader solenoid has prop-
er resistance

1. Shut all power off to unit (main and low voltage)

2. Unplug the molded plug from the compressor solenoid

2−pin fusite.

3. Using a volt meter set on the 200 ohm scale

Replace the Compressor under these conditions:

Bad Solenoid

a. Measure the resistance at the 2−pin fusite. The resist-
ance should be 32 to 60 ohms depending on compressor
temperature. If no resist ancereplace compressor.

b. Measure the resistance from each fusite pin to ground.
There should 

not be

 continuity to ground. If solenoid coil

is grounded, replace compressor.

Good Solenoid

a. Seals not shifting, replace compressor
b. Slider ring not shifting, replace compressor.

C − Outdoor Fan Motor

All units use single−phase PSC fan motors which require a run
capacitor. In all units, the condenser fan is controlled by
the compressor contactor.

ELECTRICAL DATA tables in this manual show specifi-
cations for condenser fans used in SPB*H4’s.

Access to the condenser fan motor on all units is gained
by removing the four screws securing the fan assembly.
See figure 16. The grill fan assembly can be removed
from the cabinet as one piece. See figure 17. The con-
denser fan motor is removed from the fan guard by re-
moving the four nuts found on top of the grill. See figure
17 if condenser fan motor replacement is necessary.

Make sure all power is disconnected before
beginning electrical service procedures.

DANGER

FIGURE 16

Remove

screws

Remove

screws

ALIGN FAN HUB FLUSH WITH END OF SHAFT

FIGURE 17

NUTS (4)

Содержание SPBH4 Series

Страница 1: ...ng excessive force or rapid motion can result in personal injury Be aware of and use caution when working near these areas during installation or while servicing this equipment Information contained i...

Страница 2: ...meter in 5 16 5 16 5 16 No of rows 2 2 2 Fins per inch 22 22 22 Outdoor Fan Diameter in 22 22 26 No of blades 4 4 3 Motor hp 1 6 1 4 1 3 Cfm 3150 3980 4380 Rpm 844 836 850 Watts 215 305 280 Shipping D...

Страница 3: ...meter in 5 16 5 16 5 16 No of rows 2 2 2 Fins per inch 22 22 22 Outdoor Fan Diameter in 22 22 26 No of blades 4 4 3 Motor hp 1 6 1 4 1 3 Cfm 3150 3980 4380 Rpm 844 836 850 Watts 215 305 280 Shipping D...

Страница 4: ...ed equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and operation in a corrosive atmosphere chlorine f...

Страница 5: ...s clear the slots see figure 1 De tail B 3 Move panel down until lip of upper tab clears the top slot in corner post see figure 1 Detail A Position and Install Panel Position the panel almost parallel...

Страница 6: ...Unit may have multiple power supplies 2 Dual Capacitor C12 The compressor and fan in SPB H4 series units use perma nent split capacitor motors The capacitor is located inside the unit control box see...

Страница 7: ...ill enter a lockout condition The 5 strike pressure switch lockout condition can be reset by cycling OFF the 24 volt power to the control board or by shorting the TEST pins between 1 and 2 seconds All...

Страница 8: ...ge line tempera ture shown in figure 7 exceeds a temperature of 300 F 148 C during compressor operation the board will de en ergize the compressor contactor output and the defrost output if active The...

Страница 9: ...he actual difference between the clear coil and frosted coil temperatures exceeds the maxi mum difference allowed by the control a defrost cycle will be initiated IMPORTANT The demand defrost control...

Страница 10: ...e Demand Defrost Control Y1 Active Place a jumper on TEST pins for longer than one second but less than two seconds Clears any short cycle lockout and five strike fault lockout function if applicable...

Страница 11: ...refrigerant charge in system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to sys tem 1 Remove any blockages or r...

Страница 12: ...he liquid is worked toward the center of the scroll and is discharged Due to its efficiency the scroll compressor is capable of drawing a much deeper vacuum than reciprocating com pressors Deep vacuum...

Страница 13: ...ing mecha nism to open two by pass ports in the first compression pocket of the scrolls in the compressor The internal sole noid is activated by a 24 volt direct current solenoid coil The coil power r...

Страница 14: ...TE Block outdoor coil to maintain a minimum of 375 psig during testing 7 Record all of the readings for the Y1 demand on table 3 8 Close switch to energize Y2 demand 9 Allow pressures and temperatures...

Страница 15: ...Confirm internal unloader solenoid has prop er resistance 1 Shut all power off to unit main and low voltage 2 Unplug the molded plug from the compressor solenoid 2 pin fusite 3 Using a volt meter set...

Страница 16: ...d when the pressure drop across the filter drier is greater than 4 psig To safeguard against moisture entering the system follow the steps in section IV sub section B Evacuating the System when replac...

Страница 17: ...OR COIL COIL SENSOR FIGURE 19 SPB H4 HEATING CYCLE SHOWING MANIFOLD GAUGE CONNECTIONS OUTDOOR COIL EXPANSION CHECK VALVE BI FLOW FILTER DRIER TO HFC 410A DRUM LOW PRESSURE HIGH PRESSURE COMPRESSOR REV...

Страница 18: ...p with an adjustable wrench 2 Use a service wrench with a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16...

Страница 19: ...410A into the line set and indoor unit Weigh in a trace amount of HFC 410A A trace amount is a maxi mum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the R 410A cylinder and the valv...

Страница 20: ...pump and disconnect the manifold gauge center port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hos...

Страница 21: ...ose in table 2 If subcooling value is greater than shown recover some refrigerant if less add some refrigerant TABLE 2 SPB036H4 Subcooling Values for Charging Second Stage High Capacity SSB H4S41Y thr...

Страница 22: ...309 75 334 72 323 70 40 4 4 322 92 354 89 318 69 50 10 336 113 381 108 329 82 1 These are most popular match up pressures Indoor match up indoor air quality and indoor load cause pressures to vary 2...

Страница 23: ...airflow as illustrated in figure 23 to be sure the indoor airflow is as required Make any air flow adjustments before continuing with the following procedure 2 Measure outdoor ambient temperature dete...

Страница 24: ...17 7 0 0 CBX32MV 068 16 10 0 3 CH33 60D 2F 18 4 0 2 CH33 62D 2F 15 10 0 4 CR33 60 40 4 0 2 CX34 60D 6F 18 4 0 2 CX34 62D 6F 16 8 0 2 Table 8 SSB060H4S44Y INDOOR HEAT MATCHUP PUMP Target Subcooling Hea...

Страница 25: ...036 230 22 7 0 9 CBX27UH 042 230 24 11 3 0 CBX32M 036 22 7 0 9 CBX32MV 036 22 7 0 9 CBX32MV 048 24 11 3 0 CBX40UHV 030 22 7 0 9 CBX40UHV 036 22 7 0 9 CBX40UHV 042 24 11 3 0 CBX40UHV 048 24 11 3 0 CH33...

Страница 26: ...469 5 37 111 4 68 194 1 99 312 7 130 475 6 38 113 6 69 197 3 100 317 2 131 481 6 39 115 8 70 200 6 101 321 8 132 487 8 40 118 0 71 203 9 102 326 4 133 494 0 41 120 3 72 207 2 103 331 0 134 500 2 42 1...

Страница 27: ...ils for evidence of oil leaks B Indoor Coil 1 Clean coil if necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check the condensate line and clean it if necessary C Indoor Unit 1...

Страница 28: ...Page 28 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION...

Страница 29: ...Page 29 Figure 26 Unit Wiring Diagram 036 and 048 Sizes SPB H4S45Y...

Страница 30: ...Page 30 Figure 27 Unit Wiring Diagram 060 Size Only SPB H4S45Y...

Страница 31: ...he defrost board sends 24 volts through Y2 OUT to the L34 compressor solenoid plug The 2 wire com pressor solenoid plug converts the 24volt AC outputs to a 24volt DC signal input to the L34 internal h...

Отзывы: