background image

Page 6

Equipment In Confined Space

All Air From Inside

Chimney or

Oil Ven

t

Water

Heater

Openings

(To Adjacent Room)

Figure 4

NOTE-Each opening shall have a free area of at least 1 square inch
(6.4 square centimeters) per 1,000 Btu (293 W) per hour of the total
input rating of all equipment in the enclosure, but not less than 100
square inches

 

(614.5 square centimeters).

Oil

Furnace

Air from Outside

If air from outside is brought in for combustion and ventila­
tion, the confined space shall be provided with two perma­
nent openings. One opening shall be within 12” (305 mm)
of the top of the enclosure and one within 12” (305 mm) of
the bottom. These openings must communicate directly or
by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch (6.4 square centimeters) per 4,000
Btu (1172 W) per hour of total input rating of all equipment
in the enclosure. (See figure 5.) When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch (6.4 square
centimeters) per 2,000 Btu (586 W) per total input rating of
all equipment in the enclosure (See figure 6).

Ventilation

Louvers

(For unheated

crawl space)

Outlet

Ai

r

Equipment In Confined Space

All Air From Outside

(Inlet Air from Crawl Space and Outlet Air to

Ventilated Attic)

NOTE-The inlet and outlet air openings shall each have a free area of at
least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W)
per hour of the total input rating of all equipment in the enclosure.

Ventilation Louvers

(Each End Of Attic)

Water

Heater

Inlet

Air

Chimney or

Oil Vent

Figure 5

Oil

Furnace

When ducts are used, they shall be of the same cross-sec­
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3” (76 mm). In calculating free area,
the blocking effect of louvers, grilles, or screens must be
considered. If the design and free area of protective cover­
ing is not known for calculating the size opening required, it
may be assumed that wood louvers will have 20 to 25 per­
cent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment opera­
tion.

Equipment In Confined Space

All Air From Outside

Outlet Ai

r

Inlet A

ir

Water

Heate

r

Chimney

Or Oil

Vent

Figure 6

NOTE-Each air duct opening shall have a free area of at least one
square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour of
the total input rating of all equipment in the enclosure. If the equipment
room is located against an outside wall and the air openings communi­
cate directly with the outdoors, each opening shall have a free area of at
least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W)
per hour of the total input rating of all other equipment in the enclosure.

Oil

Furnace

CAUTION

Combustion air openings in the front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may re­
sult in a fire hazard or injury.

WARNING

The barometric draft control must be removed from
the vent pipe when using a combustion air adapter.
Deviation from this practice will cause improper
burner operation and may allow flue products into
the living space which may result in personal injury
or death.

Locate & Level the Unit

Set the unit in desired location keeping in mind the clear­
ances listed in table 2. Also keep in mind oil supply connec­
tions, electrical supply, flue connections and sufficient clear­
ance for installing and servicing unit.

Содержание SIGNATURE SLO185UFV Series

Страница 1: ...ng List 1 SLO185UFV Unit Dimensions 2 SLO185UFV Unit Parts Arrangement 3 SLO185UFV Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Locate Level the Unit 6 Adjustments 7 Vent...

Страница 2: ...her Side ELECTRICAL INLET Right Side Only OIL PIPING INLET Left Side Only OPT OUTDOOR COMBUSTION AIR INLET CENTERING HOLE Field Fabricate Right Side only RETURN AIR OPENING Either Side 3 4 19 A B C D...

Страница 3: ...SPEED BLOWER MOTOR OBSERVATION PORT HEAT EXCHANGER FLUE COLLAR LIMIT SWITCH INDOOR BLOWER CAPACITOR BLOWER CONTROL Figure 2 SLO185UFV NX Burner Parts Arrangement Blower Motor Blower Wheel With Air Gu...

Страница 4: ...gs required SLO185UFV 79 105 10 X 20 254 mm X 508 mm SLO185UFV 124 141 11 X 22 279 mm X 559 mm This unit is approved for use on combustible flooring and for clearances to combustible material as liste...

Страница 5: ...ed at the same time as the furnace much more air is required to ensure proper combustion and to prevent a down draft situation Insufficient amounts of air also cause incomplete combustion which can re...

Страница 6: ...tional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall be no less than 3 76 mm In calculating free area the blocking effect of louvers...

Страница 7: ...le assembly must be checked for proper depth and alignment You must remove the entire burner assembly not just the nozzle from the furnace to check the nozzle depth and alignment The smaller sized fir...

Страница 8: ...make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized ac cording to the requirements of the National Fire Protec...

Страница 9: ...nt connectors serving this appliance shall not be connected into any portion of mechanical draft sys tems operating under positive pressure 18 Keep the area around the vent terminal free of snow ice a...

Страница 10: ...aft control Alternate Side Flue Connections The vent pipe may exit the top or sides of the cabinet A hole is provided in the top cap for top exit For side exit lo cate the center hole punched in the s...

Страница 11: ...returning it to the tank To determine the run and lift for piping refer to table 5 Use continuous lengths of heavy wall copper tubing or steel pipe for oil supply pipe Install oil supply pipe under f...

Страница 12: ...he building between the tank shut off valve and the burn er Locate filter close to burner for easy maintenance Table 6 lists the filters for the SLO185UFV furnace Table 6 Oil Filters Cat No 10 micron...

Страница 13: ...this product may result in a fire causing property dam age severe injury or death Use copper wire only with this product CAUTION Failure to use properly sized wiring and circuit breaker may result in...

Страница 14: ...Page 14 Figure 17 Field Wiring Diagrams 1 Heat 1 Cool 1 Heat 2 Cool 1 Heat 1 Cool With Thermostat Dehumidification Mode 1 Heat 2 Cool With Thermostat Dehumidification Mode...

Страница 15: ...iagrams Continued Dual Fuel Single Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump With Dual Fuel Control Mode and T...

Страница 16: ...of each cooling demand to allow for greater humidity removal and to conserve energy If after 7 1 2 minutes the Y demand is not met 100 CFM is supplied until the demand is satisfied OFF CALL 100 82 Y...

Страница 17: ...flash 10 times At times the light may appear to flicker or glow This takes place when the control is communicating with the motor between cycles This is normal operation After the CFM for each applica...

Страница 18: ...External Static Pressure Range ADJUST Jumper Setting Jumper Speed Positions HEAT Speed COOL Speed 85 High Fire 75 Low Fire A C A B C D cfm cfm cfm cfm cfm cfm N A N A 2000 2000 1800 NORM 1850 1550 20...

Страница 19: ...of bubbles Then terminate the call for heat The burner control will resume normal operation Fuel Pump Pressure Adjustment Measure fuel pump pressure with unit off Attach pressure gauge to pump outlet...

Страница 20: ...er obtain and record the flue gas temperature at the service hole 11 Use the CO2 reading and the flue gas temperature reading to determine unit efficiency 12 When proper combustion and smoke readings...

Страница 21: ...tube CAUTION Do not attempt to clean the combustion chamber It can be easily damaged 5 Replace the three clean out caps and flue access el bow Make sure locking screws are secure 6 Brush out and vacu...

Страница 22: ...nal is de energized Response D After the thermostat is satisfied the thermostat circuit opens The oil delay valve and burner are de energized D Burner is de energized D Heat fan off ramp timing begins...

Страница 23: ...speed ramps down Circulating fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory co...

Страница 24: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Страница 25: ...must be removed from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle straine...

Страница 26: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 27: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 28: ...ed heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High sta...

Отзывы: