Combustion Air Inducer

A combustion air inducer proving switch checks
combustion air inducer operation before allowing power
to the gas controller. The gas controller will not operate if
the inducer is obstructed.

Under normal operating conditions, the combustion air
inducer wheel should be checked and cleaned prior to the
heating season. However, it should be examined
periodically during the heating season to establish an
ideal cleaning schedule.

Clean the combustion air inducer as follows:

1− Turn off the electrical power and the gas supply to the

unit.

2− Disconnect the pressure switch air tubing from the

combustion air inducer port.

3− Remove and retain the screws securing the

combustion air inducer to the flue box. Remove and
retain the screw securing the combustion air inducer
to the vent connector. See figure 3.

4− Clean the inducer wheel blades with a small brush

and wipe off any dust from the housing. Clean
accumulated dust from the front of the collector box
cover.

5− Return the combustion air inducer motor to the

original location and secure with retained screws. It

is recommended that the combustion air inducer
gasket be replaced during reassembly.

6− Use a small brush to clean the combustion air inlet

louvers on the heat access panel.

Flue Passageway and Flue Box

1− Remove the combustion air inducer assembly as

described in the Combustion Air Inducer subsection.

2− Remove the flue box cover. Clean the flue box with a

wire brush as required.

3− Clean the tubes with a wire brush.

4− Reassemble the unit. The flue box cover gasket and

combustion air inducer gasket should also be
replaced during reassembly.

Service Reminder

Call a qualified service technician if the unit is inoperative.
Before calling, always check the following to be sure
service is required:

1− Be sure electrical disconnect switches are 

ON

.

2− Check room thermostat for proper setting.

3− Replace any blown fuses or reset circuit breakers.

4− Gas valve should be 

ON

.

5− Air filters should not be plugged, limiting air flow.

6− Make sure all access panels are in place.

Repair Parts Listing

When ordering repair parts, include the complete model number and serial number listed on the ETL rating plate − e.g.
SGA480H4BH1Y.

Gas Heat Section Parts

Heat Exchanger
Combustion Air Assembly
Combustion Air Proving Switch
Burner Assembly
Burner Manifold Assembly
Main Burner Orifices
Flame Roll−out Switches
Auxiliary Limit Controls
Ignition Electrode Assembly
Ignition Lead
Ignition Sensor Assembly
Sensor Lead
Combination Gas Valve
Limit Controls

Cooling Parts

Compressors
Condenser Fan Motors
Condenser Fan Blades
Condenser Fan Run Capacitors
Freezestats
Condenser Fan Mounting Bracket
Fan Grille
Indoor Blower Motors
Blower Wheel
Expansion Valve 
Distributor
Exhaust Fans (Opt.)

Electrical Control Parts

IMC Control Board
Compressor Contactors
Circuit Breakers (Opt.)
Transformer (Control)
Transformer (Contactor)
Blower Contactor
Limit, Blower Relay
Heat Relays
Condenser Fan Relays
Capacitor CAB
Relay CAB
Crankcase Heaters
Disconnect Switch (Opt.)

Содержание SGA420

Страница 1: ...on and service must be per formed by a qualified installer ser vice agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your bui...

Страница 2: ...COILS OPTIONAL BURNERS GAS VALVES 2 CONDENSER COILS 4 CONTROL BOX COMPRESSORS 4 CONDENSER FANS 6 BLOWERS FILTERS ELEVEN 16 x 25 x 2 406 x 635 x 51mm OR 16 X 25 X 4 406 X 635 X 102mm ECONOMIZER OPTION...

Страница 3: ...errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Danger of electrical shock explosion and fire Improper servicing could result in dangerous operation...

Страница 4: ...llow the gas supplier s instructions If you do not smell gas go to the next step 7 Turn the knob on the gas valve counterclockwise to ON Do not force 8 Close or replace the heat section access panel 9...

Страница 5: ...Service To maintain efficiency and longevity your equipment must be serviced yearly by a qualified service technician Failure to provide proof of service can void warranty CAUTION Label all wires prio...

Страница 6: ...t the position of the flame sensor Sensor should be centered in the path of the flame 3 Before each heating season examine the burners for any deposits or blockage which may have occurred Clean burner...

Страница 7: ...e box cover Clean the flue box with a wire brush as required 3 Clean the tubes with a wire brush 4 Reassemble the unit The flue box cover gasket and combustion air inducer gasket should also be replac...

Страница 8: ...8 The unit will operate at maximum heating input 3 Measure the manifold pressure at the gas valves Manifold pressures should be GV1 GV3 Natural 4 0 w c LP 10 8 w c GV4 GV5 Natural 3 7 w c LP 10 5 w c...

Отзывы: