Page 4

Burner Flame

 

WARNING

Danger of explosion and fire. Can cause
injury or product or property damage.
Periodically inspect burner flame to en-
sure proper unit operation.

The primary air is permanently set for normal operation.
The flame will be basically blue with some clear yellow
streaking in the end of the flame. Inspect the burner flame
periodically during the heating season using the
inspection port provided on the burner access panel.

Flue Passage and Vent Inspection

Annually, before heating season, inspect the combustion
air louvers, vent cap, heat exchanger, burners and
combustion air inducer for corrosion, deterioration or
deposits of debris. Remove any obstructions or blockage.
See figure 3.

Service

To maintain efficiency and longevity, your equipment
must be serviced yearly by a qualified service technician.
Failure to provide proof of service can void warranty.

CAUTION

Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation
after servicing.

Servicing Filter

Units are equipped with eleven 16 X 25 X 2" (406 X 635 X
51mm) or 16 X 25 X 4" (406 X 635 X 102mm) filters. Filters
should be checked monthly and replaced when
necessary with filters of like kind and size. Take note of air
flow direction marking on filter frame when reinstalling
filters. See figure 4.

NOTE − Filters must be ULC approved or equivalent for
use in Canada.

HEAT EXCHANGER ASSEMBLY

HEAT

EXCHANGER

GAS VALVE

COMBUSTION

AIR INDUCER

PROVE

SWITCH

COLLECTOR

BOX

BURNER

ROLLOUT

SWITCH

FIGURE 3

VENT

CONNECTOR

Secures vent

to combustion

air inducer

Содержание SGA420

Страница 1: ...on and service must be per formed by a qualified installer ser vice agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your bui...

Страница 2: ...COILS OPTIONAL BURNERS GAS VALVES 2 CONDENSER COILS 4 CONTROL BOX COMPRESSORS 4 CONDENSER FANS 6 BLOWERS FILTERS ELEVEN 16 x 25 x 2 406 x 635 x 51mm OR 16 X 25 X 4 406 X 635 X 102mm ECONOMIZER OPTION...

Страница 3: ...errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Danger of electrical shock explosion and fire Improper servicing could result in dangerous operation...

Страница 4: ...llow the gas supplier s instructions If you do not smell gas go to the next step 7 Turn the knob on the gas valve counterclockwise to ON Do not force 8 Close or replace the heat section access panel 9...

Страница 5: ...Service To maintain efficiency and longevity your equipment must be serviced yearly by a qualified service technician Failure to provide proof of service can void warranty CAUTION Label all wires prio...

Страница 6: ...t the position of the flame sensor Sensor should be centered in the path of the flame 3 Before each heating season examine the burners for any deposits or blockage which may have occurred Clean burner...

Страница 7: ...e box cover Clean the flue box with a wire brush as required 3 Clean the tubes with a wire brush 4 Reassemble the unit The flue box cover gasket and combustion air inducer gasket should also be replac...

Страница 8: ...8 The unit will operate at maximum heating input 3 Measure the manifold pressure at the gas valves Manifold pressures should be GV1 GV3 Natural 4 0 w c LP 10 8 w c GV4 GV5 Natural 3 7 w c LP 10 5 w c...

Отзывы: