NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Installations at Altitudes of 0 to 4500 feet - 
Units are tested and approved for elevations 
of 0 to 4500 feet (0 to 1370 meters). 

Installations at Altitudes above 4500 ft.- 
For elevations above 4500 feet (1370 
meters), install the unit according to the 
regulations of the local authorities having 
jurisdiction and, in the USA, the latest 
edition of the National Fuel Gas Code (ANSI 
Z223.1) or, in Canada, the  latest edition of 
the CAN-B149.1 and CAN-B149.2 codes.

Table 4

 shows the units' gas orifi ce size for 

the elevations indicated:

 

LOCATION

In selecting the location, the aesthetic and 
functional use of the appliance are primary 
concerns. However, vent system routing to 
the exterior and access to the fuel supply are 
also important. Consideration should be given 
to traffi c ways, furniture, draperies, etc., due 
to elevated surface temperatures. 

Considerations Should Include:
• Existing Chimneys
• Aesthetic Considerations
• Roof Design (Rafter Locations and Roof Pitch)
• Room Traffi c
• Proximity to Combustibles
• Proximity for Optimum Heat Transfer
• Electrical Wiring (if optional blower is installed)

The installation of this stove will require some 
research. Once your options are determined, 
consult with your local building department who 
will be able to give you the necessary installation 
requirements for your area (Is a building permit 
required?, Rooms where installation may not 
be allowed?, etc.). 

Tables 2 and 3

 show the units' gas pressure 

requirements:

Inlet Gas Supply Pressure

(all models)

Fuel #

Minimum

Maximum

Natural Gas

4.5" WC

(1.12 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.73 kPa)

13.0" WC

(3.23 kPa)

Table 2

Manifold Gas Supply Pressure

(millivolt models)

Fuel #

Low

High

Natural 

Gas

(Lo) 1.6" WC

(.40 kPa)

(Hi) 3.5" WC

(.87 kPa)

Propane

(Lo) 6.3" WC

(1.57 kPa)

(Hi) 10.0" WC

(2.49 kPa)

Table 3

Ne pas se servir de cet appareil s'il a été 
plongé dans l'eau, complètement ou en 
partie.  Appeler un technicien qualifi é pour 
inspecter l'appareil et remplacer toute partie 
du système de contrôle et toute commande 
qui ont été plongés dans l'eau.

This appliance may be installed in an 
aftermarket permanently located, manu-
factured  home (USA only) or mobile 
home, where not prohibited by local codes.

Cet appareil peut être installé dans un 
maison préfabriquée (É.-U. seulement) ou 
mobile  déjà  installée à demeure si les 
réglements locaux le permettent.

Test gauge connections are provided on 
the front of the millivolt gas control valve 
(identifi ed IN for the inlet and OUT for the 
manifold side).

These appliances and their individual shut-off 
valves must be disconnected from the gas 
supply piping system during any pressure 
testing of that system at pressures in excess 
of 1/2 psig (3.5 kPa)

.

These appliances must be isolated from the 
gas supply piping system (by closing their 
individual manual shut-off valve) during any 
pressure testing of the gas supply piping 
system at test pressures equal to or less than 
1/2 psig (3.5 kPa).

These appliances must not be connected to 
a chimney or fl ue serving a separate solid 
fuel burning appliance.

WARNING: This appliance must be properly 
connected to a venting system.  Operation 
of this gas appliance when not connected to 
a properly installed and maintained venting 
system can result in carbon monoxide (CO) 
poisoning and possible death.

Carbon Monoxide Poisoning: Early signs 
of carbon monoxide poisoning are similar 
to the fl u with headaches, dizziness and/or 
nausea. If you have these signs, obtain fresh 
air immediately. Turn off the gas supply 
to the appliance and have it serviced by 
a qualifi ed professional, as it may not be 
operating correctly.

The millivolt appliances are manually con-
trolled and feature a spark igniter (piezo) 
that allows the appliance's pilot gas to be 
lit without the use of matches or batteries.  
This system provides continued service in 
the event of a power outage.

Do not use these appliances if any part 
has been under water.  Immediately call a 
qualifi ed, professional service technician to 
inspect the appliance and to replace any parts 
of the control system and any gas controls 
which have been under water.

Burner Orifi ce Sizes

Model

No.

Nat.

Gas

Prop.

Gas

Elevation

Feet

(meters)

CI1500DVF

.104"

.061"

0-4500

(0-1372)

CI2500DVF

.121"

.068"

0-4500

(0-1372)

Table 4

       WARNING 

Failure to comply with the instal-
lation and operating instructions 
provided in this document will 
result in an improperly installed 
and operating appliance, void-
ing its warranty.  Any change 
to this appliance and/or its 
operating controls is dangerous.  
Improper installation or use of 
this appliance can cause serious 
injury or death from fi re, burns, 
explosion or carbon monoxide 
poisoning.

       WARNING 

Do not place clothing or other 
fl ammable materials on or near 
this appliance.

       WARNING 

Children and adults should be 
alerted to the hazards of high 
surface temperatures. Use 
caution around the appliance 
to avoid burns or clothing igni-
tion. Young children should be 
carefully supervised when they 
are in the same room as the 
appliance.

Note: An Optional Screen Panel 
for the glass is available (see 
Homeowners Manual for ordering 
information).

       

AVERTISSEMENT

Surveiller les enfants.  Garder les 
vêtements, les meubles, l'essence 
ou autres liquides à  vapeur infl am-
mables lin de l'appareil.

Содержание SEREFINA CI1500DVF series

Страница 1: ...E OU LA MORT POUR VOTRE SÉCURITÉ Ne pas entreposer ni utiliser d essencenid autrevapeursouliquidesinflammablesdans le voisinage de cet appareil ou de tout autre appareil POUR VOTRE SÉCURITÉ Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Ne touchez à aucun interrupteur Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez Evacuez la piéce ...

Страница 2: ...used Millivolt appliances are designed to oper ate on natural or propane gas A millivolt gas control valve with piezo ignition system provides safe efficient operation External electrical power is required to operate the optional blower if installed on these units Note Installation and repair should be per formed by a qualified service person The appliance should be inspected annually by a qualifi...

Страница 3: ...e appliances and their individual shut off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1 2 psig 3 5 kPa These appliances must be isolated from the gas supply piping system by closing their individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or l...

Страница 4: ...mm H 40 1016 mm 48 1 2 1232 mm Specifications CI1500DVF CI2500DVF Min Max BTU hr Input NG 17 500 28 000 25 500 38 500 Min Max BTU hr Input LP 20 500 27 000 26 500 34 500 DV Vent Size 4 inner 6 5 8 outer 4 inner 6 5 8 outer Room Fan CFM 150 150 Weight lb 206 290 Efficiencies CI1500DVF CI2500DVF EnerGuide P4 67 NG 65 LP 67 NG 64 LP Steady State Efficiency 85 NG 87 LP 83 NG 85 LP Note Due to Lennox o...

Страница 5: ... alcove that allows for the minimum clearances to combustible surfaces Your local building inspector should review your plans prior to installation When installing this appliance provide adequate clearances for the purposes of servicing and proper operation As determined through the safety certification of this unit a minimum clearance to combustible materials must be maintained around specific ar...

Страница 6: ...additionalvent location restrictions refer to Figure 5 VENT TERMINATION CLEARANCES Vertical Vent Termination Clearances These instructions should be used as a guidelineanddonotsupersedelocalcodesin anyway Installventaccordingtolocalcodes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Side Elevation View Q...

Страница 7: ... n i w t n e v e r p o t d e d n e m m o c e r m m 9 2 2 9 n o i t a s n e d n o c w o d n i w t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V D l a t n o z i r o h a n i h t i w l a n i m r e t e h t e v o b a d e t a c o l r e t n e c e h t m o r f m m 8 5 4 s e h c n i 8 1 f o e c n a t s i d l a n i m r e t e h t f o e n i l m m 8 5 4 8 1 m m 8 5 4 8 1 t i f f o s d e t a...

Страница 8: ...et aside Step5 Page8 Removepackagedmaterials from inside firebox and set aside log set bag of embers and NG to LP conversion kit Step 6 Page 9 Remove cardboard packag ing material from beneath relief door and discard Step 7 Page 9 Install LP Conversion kit if necessary Install any optional accessories excluding firescreens Step 8 Page 9 Install lower access door Step 9 Page 9 Venting System Instal...

Страница 9: ...control wiring system of the unit to a 120 volt power supply residential line voltage Thegasvalveissetinplaceandpre wiredatthe factory on both models see Figure 11 SIT Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced with Type AWM105 C 18 GA wire Thermopile TH TP TH TP ON OFF Switch Optional Thermostat Remote Control Receiver SWITCH Figure 10 Bl...

Страница 10: ...see Figures 13 and 14 SupportBrackets Installventsupportbrack ets as specified in the vent manufacturers instructions and the National Gas Fuel Code USA NFPA 54 ANSI Z223 1 7 6 5 Support ofGasVents Gasventsshallbesupportedand spaced in accordance with their listings and the vent manufacturer instructions General Information These instructions should be used as a guideline and do not supersedelocal...

Страница 11: ...ance for Natural Gas and 36 for Propane Gas before the first elbow The horizontal run may extend up to 20 feet 6 meters and include a vertical rise of up to 40 feet 12 meters see Figure 13 Horizontal termination must meet the criteria shown in Figures 4 and 5 Approved vent systems must terminate above and including the heavy line in Figure 13 Two 45 degree elbows may be substituted for each single...

Страница 12: ...nversion Kit for 6 I D 1 insulation SV4CCK2 Factory Built Chimney Conversion Kit for 7 I D 1 insulation 8 I D 1 insulation 6 I D 2 insulation SV4CCK3 Factory Built Chimney Conversion Kit for 10 I D 1 insulation 7 I D 2 insulation 8 I D 2 insulation Model Brand SIMPSON DURA VENT Description 934 Masonry Chimney Conversion Kit 931 Factory Built Chimney Conversion Kit A for 6 I D 932 Factory Built Chi...

Страница 13: ...Black 904B 24 Pipe Length Black SV4L36 36 Pipe Length Galvanized 903 36 Pipe Length Galvanized SV4LB36 36 Pipe Length Black 903B 36 Pipe Length Black SV4L48 48 Pipe Length Galvanized 902 48 Pipe Length Galvanized SV4LB48 48 Pipe Length Black 902B 48 Pipe Length Black SV4LA 6 Adj Pipe Length Galvanized 908 6 Adj Pipe Length Galvanized SV4LBA 6 Adj Pipe Length Black N A N A SV4LA12 12 Adj Pipe Lengt...

Страница 14: ...inlet port fitting Figure 20 Ember Strip Rear Log Figure 21 Left Front Log Figure 22 2 Place the largest log onto the rear log stoppers see Figure 20 Ensure that the grooves on the bottom of the log aligns onto the corresponding places on the rear log stoppers Push the log back so that it is against the back of the rear log stoppers see Figure 21 3 Place the left front log onto the corre sponding ...

Страница 15: ...ethefineembermaterial mineral wool into dime sized fluffy pieces b Distribute the pieces over the top of the front burner ports avoiding covering the slots see Figure 29 and filling the area in front of the forward logs Figure 26 Figure 27 Figure 29 VERIFY THAT THE GAS LINE HAS BEEN PURGED OF AIR SEE STEP 10 Figure 25 Left Top Twig Step 12 RE INSTALL FRONT GLASS ENCLOSURE PANEL Reverse instruction...

Страница 16: ...d run initial system checkout before closing up the front of the unit Follow the pilot lighting instruc tions provided in the Homeowner s Care and Operation Instructions or pull out the instruction label located in a holder on rear shield of stove For piezo igniter location see Figure 30 Fasten the two latches located beneath the firebox floor to the glass frame vee flange Close both the latches s...

Страница 17: ...15 9 mm CI2500DVF 1 2 12 7 mm 5 8 15 9 mm Initially always position the air shutter to the factorysettingasshowninFigure34 adjust mentrodislocatedinthelowercontrolarea This can be done by moving the adjustment rodupordownaccordingly Allowtheburner to operate for at least 15 minutes Observe the flame continuously If it appears weak or sooty as previously described adjust the air shutter to a more o...

Страница 18: ...MBRE DE SERIE XXXXX XXXXX IIIIIIIIIIIIIIIIIIII XXXXXXXXXXXXXXXX P N 9 1452A MODEL NO CI1500DVF SERIES MANUFACTURED AT SANTA TERESA NM FOR USE WITH NATURAL GAS EQUIPE POUR GAZ NATUREL ALTITUDE MIN GAS SUPPLY PRESS WC PRESS MIN D ALIMENTATION CE MANIFOLD PRESSURE WC PRESSION CE TUBULURE CE MANUFACTURER S RECOMMENDED ORIFICE SIZE DIMENSION DE L INJECTEUR RECOMMANDE PAR MANUFACTURIER DMS MAX INPUT BTU...

Страница 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE ...

Страница 20: ...ts P N 775 147M REV D 11 2006 1110 West Taft Avenue Orange CA 92865 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information ...

Отзывы: