Application Guide / NEOSYS-AGU-1801-E 

TECHNICAL DESCRIPTION

GENERAL CHARACTERISTICS OF THE UNIT 

The NEOSYS unit is designed to be integrated into urban or 
residential environments. 
As main characteristics the NEOSYS unit offers 

state of the 

art design

 to match architectural constraints and 

adjustable 

sound level performances

 during day and night to satisfy local 

environmental constraints.

CASING/CHASSIS

- Casing made of galvanised steel sheet metal painted with a white 

powdered polyester paint and a red stripe. 

- Fully grey colour painted chassis protecting against corrosion. 

State of the art design

 with hidden compressors, fans and pump 

for perfect architectural integration. 

- Flat top, aesthetic grilles, 

very low unit height (2 meters)

 for 

discrete installation on a roof reducing the requirement of costly 
cladding solutions around the unit

Aesthetic side anti-intrusion grilles

 as standard to protect the 

unit during transportation and against human aggressions.

COMPRESSOR 

- Exclusive Compliant Scroll® design with both axial and radial 

compliance to increase compressor operation tolerance to liquid 
refrigerant, substantially improving durability and reliability. 

3-year 

warranty*.

- Motor cooled by suction gas. 
- Electronic control of the compressor discharge temperature. 
- Motor protection device against high temperature or over current 

situations. 

- Discharge non-return valve. 
-  Low noise scroll compressors mounted in a sound-proofed technical 

cabinet to reduce noise emissions. 

- Compressors assembly installed on an independent chassis 

supported by anti-vibration mountings.

WATER HEAT EXCHANGER

- True dual circuit plate heat exchanger
- Copper brazed Stainless steel plate heat exchanger.
- 13 mm thermal insulation foam.
- Water heat exchanger located in a technical cabinet protecting 

the insulation against climatic conditions (UV light, rain).

 

3-year warranty*

 

AIR HEAT EXCHANGER

- High ef

fi

 ciency aluminium Micro Channel heat exchangers (MCHX) 

with improved corrosion resistance in moderate marine or urban 
environment (cooling only version). 

3-year warranty*

.

-  Standard copper tubes/aluminium 

fi

 ns heat exchanger (heat pump 

version). 

- V-coil design to protect the unit against climatic conditions (e.g. 

hail).

FANS 

- Inverter fans (0 to 900 rpm operating range). 

Active Acoustic Attenuation System™

 to meet changing building 

load requirements while automatically adjusting the air 

fl

 ow  to 

respect night and day sound level constraints (adjustable setting 
over time schedule with 4 time zones per day). 

- Elimination of intrusive start/stop noise that is irritating to the 

human ear. 

- Fan-motor assembly using external rotor technology associated 

with owlet high performance aluminium fan blades of the latest 
generation.

- IP 54 electrical motor, class F protected against high temperature 

with an internal sensor. 

- Exclusive fan design with hybrid Ceramic bearings to extend the 

service life of motors and to reduce noise level. With these sealed 
hybrid ceramic bearings, our customer can expect little or no 
maintenance of the motor throughout its life. 

3-year warranty*.

-  Extremely rigid fan assembly via the integration of the fans mounted 

within a pre-formed bell mouth roof panel, thus improving rigidity 
while reducing vibrations.

- Rounded top acoterion panels to hide the fans and reduce noise 

emissions for quieter operation. 

REFRIGERANT CIRCUIT 

NEOSYS uses R410A refrigerant in 2 independent circuits 
(minimum). Each circuit includes: 

A refrigerant charge reduced by 30%

 due to the use of R410A 

combined with micro channel heat exchanger (NAC/Cooling only 
version). 

- Suction piping with thermal insulation. 
- Filter drier with removable cartridge 

fi

 lter. 

-  Thermostatic or electronic expansion valve (Electronic device only 

when "winter operation" option selected). 

- Temperature sensors and pressure transducers.
- Four-way valve and liquid receiver (heat pump units only).
-  Leak-tight refrigerant circuit with brazing carried out under nitrogen 

by certi

fi

 ed engineers. 

-  Each refrigerant circuit is pressure and leak tested with a Hydrogen/

Nitrogen mixture, and vacuumed before being charged with 
refrigerant. All units are then subjected to a complete functional 
and operational run test to guarantee  perfect sealing before 
leaving the factory. 

* Warranty under conditions - See page 3

Содержание NEOSYS NAC 1080

Страница 1: ...I V E 2 0 0 9 1 2 5 E C ECODESIGN LABELLING Er P AIR COOLED CHILLER HEAT PUMP 200 1000 kW APPLICATION GUIDE NEOSYS AGU 1801 E LENNOX participates in the ECP programme for LCP HP Check ongoing validity...

Страница 2: ......

Страница 3: ...covery Free cooling Acoustic data Operating limits ELECTRICAL DATA Electrical tables PERFORMANCES DIMENSIONAL DATA Dimensional data Weight data All the technical and technological information containe...

Страница 4: ...5 M Application Guide NEOSYS AGU 1801 E MODEL NUMBER DESCRIPTION EXAMPLE Air cooled C Cooling mode H Heat pump mode Cooling capacity in kW Number of circuits S 1 circuit D 2 circuits T 3 circuits F 4...

Страница 5: ...noise that is irritating to the human ear Active Acoustic Attenuation System to meet changing building load requirements while automatically adjusting the air flow to meet night and day sound level co...

Страница 6: ...fficiency version a low noise or an ultra low noise version NEOSYS can adapt all situations with only one version NEOSYS is fitted in standard with the Active Acoustic Attenuation System that is using...

Страница 7: ...xchanger With the use of fully aluminium coils already used in the automotive industry NEOSYS offers many customer benefits Upto40 lessrefrigerant chargethatcontributesto reduce the total amount of re...

Страница 8: ...nvironment cooling only version 3 year warranty Standardcoppertubes aluminiumfinsheatexchanger heatpump version V coil design to protect the unit against climatic conditions e g hail FANS Inverter fan...

Страница 9: ...ambient Waterpumpcontrolwithoperatingtimeequalizationandautomatic change over in case of a pump fault Twin pump only Master slaveorcascadecontroloftwochillersoperatinginparallel with operating time e...

Страница 10: ...mounted in parallel to the air condensers allow 100 heat recovery in all outdoor air conditions Production of free hot water at the same time of the production of chilled water Free cooling Additional...

Страница 11: ...sing dry contacts 24 Vac or 4 20 mA signals Modbus communication interface Communication card using ModBus JBus protocol with RS485 or TCP IP connection Communication interface with a building managem...

Страница 12: ...valve Thermostatic expansion valve Compressors Scroll Hermetic Number of compressors Capacity steps Oil type MOBIL EAL Arctic 22CC or ICI EMKARATE RL32CF Oil load per compressor l Condenser Microchan...

Страница 13: ...rs Scroll Hermetic Number of compressors Capacity steps Oil type MOBIL EAL Arctic 22CC or ICI EMKARATE RL32CF Oil load per compressor Condenser Microchannel aluminium tube and fins Air cooled Number o...

Страница 14: ...xpansion valve Electronic expan sion valve Compressors Number of compressors Type of compressor Scroll Hermetic Capacity steps Oil type MOBIL EAL Arctic 22CC or ICI EMKARATE RL32CF Oil load per compre...

Страница 15: ...tenuation System Global sound power level 1 dB A Sound pressure level 10 meters from the unit Minimum global sound power level with A3 system 3 Minimum sound pressure level with A3 system 3 10 meters...

Страница 16: ...on valve Thermostatic expansion valve Condenser Copper tube Aluminium fin Air cooled Number of condenser Fan Motor Variable speed fans Number of fans Diameter Maximum speed Variable speed 900 rpm maxi...

Страница 17: ...ircuit R410A Type of expansion valve Thermostatic expansion valve Condenser Copper tube Aluminium fin Air cooled Number of condenser Fan Motor Variable speed fans Number of fans Diameter Maximum speed...

Страница 18: ...ustic Attenuation System Global sound power level 1 dB A Sound pressure level 10 meters from the unit Minimum global sound power level with A3 system 3 Minimum sound pressure level with A3 system 3 10...

Страница 19: ...0124 1 8669 600 0 009 1 892 640 0 0082 1 8953 540 600 640 0 0072 1 9104 NEOSYS P a Xb a b 680 0 0056 1 8666 760 0 0056 1 8666 840 0 0056 1 8666 960 0 0042 1 886 1080 0 0042 1 886 Application Guide NEO...

Страница 20: ...00332 1 7409 340 380 420 480 0 0000011 3 1026 540 600 640 8 00E 09 4 023 680 760 840 960 1080 0 0000000005 4 2717 Application Guide NEOSYS AGU 1801 E Pressure drops are given for information only A to...

Страница 21: ...120 0 150 0 180 0 210 0 240 0 270 0 300 0 330 0 A B C D E F A NAC NAH 200 D NAC NAH 300 340 B NAC NAH 230 E NAC NAH 380 420 480 C NAC NAH 270 F NAC 540 600 640 A NAC NAH 200 D NAC NAH 300 340 380 B N...

Страница 22: ...s x Dt Where Minimum water content of the installation Cooling capacityof the chiller Nstage Number of control steps available in the unit Maximum acceptable temperature rise Dt 6 c for an air conditi...

Страница 23: ...ini water volume l MAXIMUM WATER CONTENT OF AN INSTALLATION The maximum water content of the installation is determined by the capacity of the expansion vessel On units fitted with a standard Hydrauli...

Страница 24: ...alanced to ensure a right water flow distribution through the chiller evaporator and the terminal units This is especially important when the system is designed with fan coils equipped with two way va...

Страница 25: ...al units equipped with two way control valves instead of three way valves elimination of water flow set valve Flexibility and accuracy in the pump operation control smooth start and stop gradual chang...

Страница 26: ...variable primary flow design uses fewer components than primary secondary systems as the pumps of the secondary distribution loop and the mixing tank are eliminated Whencomparedwithconstantprimaryflo...

Страница 27: ...ws the pump speed to maintain the target delta P In this mode the pump does not detect terminal capacity reduction fan speed staging Constant Delta T the eDrive regulation is managing the pump to main...

Страница 28: ...trolled by our Climatic control The bypass should be positioned at the beginning of the installation near the unit and allows significant energy savings and cost as opposed to a location at the end of...

Страница 29: ...llowing recovery of 15 of the rejected heat This heat exchanger is large enough to recover heat for the production of free hot watersimultaneouslywithchilledwaterproduction Theheatingcapacityoftheheat...

Страница 30: ...otal energy efficiency of the units when there is a production of chilled water and hot water simultaneously Cold water and hot water are valuated to the total power consumption of the unit TER coolin...

Страница 31: ...3 11 3 15 3 17 5 31 5 29 5 31 5 25 5 39 5 36 5 34 5 34 5 39 5 47 5 50 21 2 23 9 23 9 31 8 34 7 42 5 45 1 50 9 57 6 64 8 65 1 13 12 17 11 14 14 15 14 18 22 22 15 8 23 9 23 9 34 7 34 7 42 8 42 8 56 2 60...

Страница 32: ...re return Temperature 3 C motorised valves open to by pass return water flow through the Free Cooling coils The Free Cooling fans are driven by the CLIMATIC 60 via a specific PID algorithm The Free co...

Страница 33: ...NAC 200 to 540 2V for NAC 200 to 540 Air flow m3 h Water flow m3 h Ambient temperature C Outlet temperature C Free cooling capacity kW Free cooling absorbed power kW EER Free cooling pressure drop to...

Страница 34: ...76 68 89 58 270 70 82 85 87 84 78 70 91 60 300 70 82 85 87 84 78 70 91 60 340 70 82 85 87 84 78 70 91 60 380 71 83 87 88 85 79 71 92 61 420 71 83 87 88 85 79 71 92 61 480 71 83 87 88 86 79 71 92 61 N...

Страница 35: ...perature Full capacity operation Cooling mode Min outlet water temperature Max inlet water temperature Min difference water inlet outlet Max difference water inlet outlet Min outside air temperature M...

Страница 36: ...8 439 9 462 7 506 8 579 3 336 3 371 3 393 4 428 4 489 4 2 x 300 Application Guide NEOSYS AGU 1801 E ELECTRICAL DATA Minimum and maximum voltage V Maximum power kW Maximum current A Maximum current wit...

Страница 37: ...on as an option Evaporator anti freeze heater power kW Evaporator anti freeze heater Maximum current A Hydraulic anti freeze heater power kW Hydraulic anti freeze heater Maximum current A OPTIONS dual...

Страница 38: ...2 0 32 0 32 0 32 0 81 0 81 0 32 0 81 0 81 0 81 0 81 0 81 0 23 0 23 0 23 0 23 0 24 0 24 0 24 0 24 0 56 0 56 0 56 0 56 0 60 0 60 0 60 0 60 Application Guide NEOSYS AGU 1801 E ELECTRICAL DATA Minimum and...

Страница 39: ...3 540 555 9 177 9 95 6 61 8 545 4 183 4 93 8 59 6 534 4 189 6 91 9 57 4 516 8 200 2 88 9 53 9 504 4 208 1 86 8 51 5 600 631 5 194 6 108 7 64 0 620 2 200 1 106 7 61 9 608 2 206 5 104 6 59 6 589 0 217 5...

Страница 40: ...7 73 8 38 1 540 491 4 216 7 84 5 49 1 484 8 221 3 83 4 47 9 477 9 226 0 82 2 46 6 471 0 230 9 81 0 45 4 463 9 236 0 79 8 44 1 600 561 2 235 1 96 5 51 2 553 8 240 0 95 3 49 9 546 3 245 2 94 0 48 7 538...

Страница 41: ...44 8 514 7 267 6 88 6 43 5 506 4 273 8 87 1 42 2 640 541 3 270 2 93 1 44 2 532 8 276 3 91 7 42 9 524 2 282 7 90 2 41 6 680 597 6 294 0 102 8 31 9 587 6 299 6 101 1 30 9 577 4 305 4 99 3 29 9 760 657...

Страница 42: ...9 51 7 540 601 8 182 1 103 5 71 7 590 3 187 9 101 6 69 2 578 3 194 4 99 5 66 5 559 1 205 4 96 2 62 5 545 7 213 6 93 9 59 7 600 682 8 198 0 117 5 74 2 670 5 203 9 115 3 71 7 657 5 210 7 113 1 69 1 636...

Страница 43: ...7 237 1 87 7 52 6 502 1 242 3 86 4 51 1 600 607 3 240 7 104 5 59 5 599 4 245 8 103 1 58 0 591 5 251 1 101 8 56 6 583 3 256 6 100 4 55 1 575 0 262 3 98 9 53 6 640 629 1 248 5 108 2 58 8 621 0 253 8 10...

Страница 44: ...558 0 274 4 96 0 50 7 549 2 280 7 94 5 49 2 640 586 8 277 0 101 0 51 5 577 8 283 3 99 4 50 1 568 7 289 9 97 8 48 6 680 651 9 300 1 112 2 37 5 641 0 305 8 110 3 36 4 630 0 311 5 108 4 35 2 760 605 4 27...

Страница 45: ...7 59 5 540 647 5 186 5 111 4 82 2 635 0 192 6 109 2 79 2 621 9 199 4 107 0 76 2 601 2 210 8 103 4 71 5 586 7 219 3 100 9 68 4 600 733 5 201 6 126 2 85 0 720 3 207 9 123 9 82 1 706 4 215 0 121 5 79 2...

Страница 46: ...548 2 243 5 94 3 60 2 465 3 195 0 80 0 N A 600 652 9 246 4 112 3 68 2 644 6 251 7 110 9 66 6 636 1 257 2 109 4 64 9 627 5 262 9 108 0 63 3 618 8 268 8 106 5 61 6 640 676 5 254 4 116 4 67 5 667 9 259...

Страница 47: ...600 8 281 2 103 4 58 3 591 6 287 7 101 8 56 6 640 631 7 283 9 108 7 59 3 622 3 290 4 107 1 57 6 612 7 297 2 105 4 55 9 680 708 5 306 7 121 9 43 8 696 8 312 4 119 9 42 5 684 9 318 2 117 8 41 2 760 658...

Страница 48: ...06 6 1227 446 5 211 2 101 8 15 C 200 281 9 68 4 48 5 75 3 275 8 70 5 47 5 72 4 269 6 72 7 46 4 69 4 260 0 76 3 44 7 64 9 253 4 78 8 43 6 61 9 230 318 5 82 2 54 8 94 5 311 4 84 7 53 6 90 6 304 1 87 4 5...

Страница 49: ...7 84 3 41 2 55 8 236 2 85 7 40 6 54 3 232 6 87 2 40 0 52 8 230 277 3 98 2 47 7 73 1 273 3 99 9 47 0 71 2 269 3 101 7 46 3 69 2 265 2 103 5 45 6 67 3 261 0 105 4 44 9 65 4 270 318 1 123 1 54 7 74 4 31...

Страница 50: ...107 3 44 2 63 4 252 6 109 3 43 5 61 5 184 9 72 4 31 8 N A 270 193 3 70 0 33 3 N A 190 2 71 3 32 7 N A 187 0 72 7 32 2 N A 300 339 8 133 1 58 5 57 8 334 5 135 6 57 6 56 1 329 2 138 1 56 6 54 5 340 383...

Страница 51: ...9 2 33 4 335 5 116 5 57 7 31 9 327 1 120 8 56 3 30 4 314 3 127 4 54 1 28 2 380 381 6 116 7 65 7 40 4 372 9 120 9 64 1 38 7 363 9 125 3 62 6 37 0 350 3 132 2 60 3 34 5 420 421 1 135 5 72 5 48 5 411 1 1...

Страница 52: ...50 6 223 5 63 9 38 4 49 0 219 0 70 4 37 68 47 2 230 262 9 61 3 45 2 66 2 259 8 68 0 44 7 64 8 256 2 75 3 44 1 63 1 252 0 83 2 43 35 61 2 270 331 5 78 4 57 0 80 4 324 9 86 0 55 9 77 4 318 7 94 6 54 8 7...

Страница 53: ...35 2 270 233 5 75 6 40 2 41 8 232 4 83 1 40 0 41 4 231 7 91 8 39 9 41 2 300 256 2 82 6 44 1 34 4 256 1 91 6 44 1 34 4 256 5 101 5 44 1 34 5 340 273 4 88 0 47 0 21 8 272 9 96 9 47 0 21 7 272 8 107 1 46...

Страница 54: ...70 In 1 In 2 Out Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LOAD DITRIBUTION Kg Lennox recommend load distribution as detailed below More detailed load distributions available on page xxx LE...

Страница 55: ...50 1380 50 860 50 In2 In1 Out 8x 20 D2 G2 D1 G1 D3 G3 D4 G4 D1 D4 G1 G4 Application Guide NEOSYS AGU 1801 E LOAD DITRIBUTION Kg Lennox recommend load distribution as detailed below More detailed load...

Страница 56: ...00 350 436 319 223 397 495 374 253 NAH 300 442 551 416 282 489 609 460 312 Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LEGEND Gravity center Chilled water inlet Unit without hydraulic module...

Страница 57: ...614 472 317 Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LEGEND Gravity center Chilled water inlet Unit without hydraulic module 5 Victaulic Chilled water inlet Unit with all hydraulic module...

Страница 58: ...pplication Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LEGEND Gravity center Chilled water inlet Unit without hydraulic module 5 Victaulic Chilled water inlet Unit with all hydraulic module Chilled water...

Страница 59: ...309 548 693 523 353 Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LEGEND Gravity center Chilled water inlet Unit without hydraulic module 6 Victaulic Chilled water inlet Unit with all hydrauli...

Страница 60: ...478 371 316 479 558 538 418 356 Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LEGEND Gravity center Chilled water inlet Unit without hydraulic module 6 Victaulic Chilled water inlet Unit with...

Страница 61: ...5 265 245 289 In Out Out In VOIR DETAIL K o 250 x 125 o 250 x 125 25 60 G1 G8 D1 D8 D7 G7 D6 G6 D5 G5 D4 G4 D3 G3 D2 G2 D1 G1 IN OUT Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA LOAD DITRIBUTI...

Страница 62: ...0 500 500 500 500 500 500 500 NAC 960 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 NAC 1080 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 IN OUT Application Guide...

Страница 63: ...1 5 m 1 5 m 2 m Application Guide NEOSYS AGU 1801 E DIMENSIONAL DATA ANTI VIBRATION MOUNTS OPTION CLEARANCES Whatever the NEOSYS size clearances around the unit are the same as indicated below Overhe...

Страница 64: ...7806 7884 4048 4488 4511 NA 3974 4405 4423 4155 4595 4618 NA 4081 4512 4530 4086 4526 4549 NA 4012 4443 4461 4233 4674 4696 NA 4159 4591 4608 Application Guide NEOSYS AGU 1801 E WEIGHT DATA Without h...

Страница 65: ...high pressure double pump With high pressure double pump Without hydraulic module With low pressure single pump With low pressure double pump With high pressure double pump With high pressure double...

Страница 66: ...dule With low pressure single pump With low pressure double pump With high pressure double pump With high pressure double pump Without hydraulic module With low pressure single pump With low pressure...

Страница 67: ......

Страница 68: ...72 23 20 20 lennoxemea com NEOSYS AGU 1801 E Due to LENNOX EMEA ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liabi...

Отзывы: