24
7.5.2. Multiple Units
Height of
Wall (C)
Unit
Height (A)
118
(2997
)
(Minimum
)
Unit to
Wall (B
)
24 (610)
(M
inimum
)
60 (1500
)
(Minimum
)
10 (254
)
(Minimu
m
)
10
(254)
(Minimum
)
AI
R
FLOW
AI
R
FLOW
CLEARANCE NOTES FOR MULTIPLE UNITS:
If the height of the wall (C) is less than or equal to the height of the smallest unit (A), the distance from the unit to the wall (B) must be a minimum of 10 inches
(254 mm).
If 1/2 the height of the unit (A) is less than the height of the wall (C), the distance from the unit to the wall (B) must be a minimum of 12 inches (305 mm).
If the height of the wall (C) is greater than the height of the unit (A), the distance from the unit to the wall (B) must be a minimum of 20 inches (508 mm).
NOTE: It is recommended that the single clearance
be followed in a multi-unit applications. If not then
these are the maximum and minimum clearances
you are allowed.
Figure 19. Multiple Outdoor Unit Clearances - Inches (mm)
Содержание MWHA009S4
Страница 14: ...14 Manual control button Figure 15 Manual Button Location...
Страница 51: ...51...
Страница 52: ...52...