background image

The furnace cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an
electrical fault should occur. The unit must also be electrically grounded in accordance with local codes, or in the
absence of local codes, with the latest edition of the (U.S.)  National  Electrical  Code  ANSI/NFPA   No.  70 or  CSA
Standard  C22.1;  Part  1  Canadian  Electrical  Code, if an external electrical source is utilized. DO NOT use gas piping
as an electrical ground.

INTRODUCTION

This furnace is design certified by CSA International as a Category I furnace using air from inside the structure for

combustion.

It is shipped as a packaged unit, complete with burners and controls, and requires a line voltage (115V) connection to

the junction box, a thermostat hook-up as per the wiring diagram and a gas line connection. 

This furnace can be installed

in either upflow, downflow or horizontal

 

airflow positions.

 

The design of this furnace is

 

NOT  CSA  Certified for

installation in recreation vehicles, in manufactured (mobil) homes, outdoors or for temporary construction heating.

This furnace has been designed to interface with split system cooling equipment (approved by a nationally recognized

testing laboratory) so as to provide "year round air conditioning". The blower has been sized for both heating and cooling
and the furnace controls include a cooling fan relay.

The furnace installation must conform with local building codes or in the absence of local codes, with the latest edition

of the (U.S.) National  Fuel  Gas  Code  ANSI  Z223.1  (NFPA-54) or Canadian  Natural  Gas  and  Propane  Installation  Codes
CSA  B149.1.

For complete information on installation standards consult the (U.S.)  National  Fuel  Gas  Code, obtainable from the

National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269 or the American Gas Association, 1515
Wilson Boulevard Arlington, VA 22209 or the Canadian installation codes obtainable from Canadian Standards Association,
178 Rexdale Boulevard, Etobicoke, Ontario, Canada M9W 1R3.

This furnace is designed for minimum continuous return-air temperature of 60°F dB or intermittent operation down to

55°F dB such as when used with a night setback thermostat. Return-air must not exceed a maximum continuous
temperature of 85°F dB.

These instructions are written for individual residential installation only. For multi-unit installation or

commercial applications, please contact manufacturer for recommendations.

LOCATION / PLACEMENT

Site  Selection

:

This furnace may be located in an attic, closet, basement, crawl space, alcove or suspended from the
ceiling of a utility room or basement. Select a location that will meet all requirements for safety,
clearances, ventilation and combustion air, ductwork design, gas piping, electrical wiring and venting.

Clearances:

The following minimum clearances, or greater, must be provided between the furnace and adjacent
construction.

TABLE 1

MINIMUM INSTALLATION CLEARANCES

"UPFLOW"

 POSITION

"DOWNFLOW"

 POSITION

"HORIZONTAL"

 POSITION

Suitable for alcove or closet
installation† on combustible
flooring at minimum
clearance from adjacent
construction not less than
the following:

Suitable for alcove or closet installation† on non-
combustible flooring at minimum clearance from
adjacent construction not less than the following:
* Installation on combustible flooring only when
installed on special base (see model & rating label
for proper special base).

Suitable for attic, alcove or closet installation† on
combustible flooring at minimum clearance from
adjacent construction not less than the following:
* Line contact only permissible between lines
formed by intersection of the top and two sides of
the furnace jacket and building joist, studs, or
framing.

Top

Sides

Back

Front

Vent

2"

1"

1"

6"

6" with single wall vent

2"

1"

1"

3"

1" with B1 vent

 †

For closet installation see Air for Combustion and Ventilation.

20541501

 

Issue 0240

 

      Page 6 of 26

Содержание MPGA 050 B3

Страница 1: ...APPLICATION GUIDE GAS FURNACE Fit s All 80 English 02 2004...

Страница 2: ......

Страница 3: ...and liquids in the vicinity of this or any other appliance Installation and service must be performed by a qualified installer service agency or the gas supplier Installation by an unqualified person...

Страница 4: ...or the detection of leaks to check all connections as specified in The Gas Connection section on page 16 of these instructions 6 Always install furnace to operate within the furnace s intended tempera...

Страница 5: ......

Страница 6: ...s in place or A C evaporator in place When operating the furnace in the heating mode the static pressure and the temperature rise supply air temperature minus return air temperature must be within tho...

Страница 7: ...FURNACE WIRING SPECIFICATIONS 20541501 Issue 0240 Page 5 of 26...

Страница 8: ...lson Boulevard Arlington VA 22209 or the Canadian installation codes obtainable from Canadian Standards Association 178 Rexdale Boulevard Etobicoke Ontario Canada M9W 1R3 This furnace is designed for...

Страница 9: ...e furnace is to be installed in a crawl space consult local codes Use of a concrete pad 1 to 2 thick is recommended If the furnace is to be suspended from the ceiling it will be necessary to use steel...

Страница 10: ...on of gas proper venting and maintenance of ambient temperature at safe limits under normal conditions of use The furnace shall be located so as not to interfere with proper circulation of air In addi...

Страница 11: ...000 60 000 80 000 100 000 120 000 140 000 160 000 100 100 100 100 120 140 160 12 12 12 12 13 14 15 EXAMPLE 50 000 Btuh Furnace 10 000 Btuh Water Heater 60 000 Btuh Total Input 12 Dia Round Duct If ve...

Страница 12: ...n of rectangular air ducts must not be less than 3 inches Each opening must have a free area of not less than one square inch per 2 000 Btu per hour of total input of all appliances within the Confine...

Страница 13: ...re should be at least one 90 air turn between blower and return grille Further reduction in sound can be accomplished by installing acoustical air turning vanes and or lining the inside of the duct wi...

Страница 14: ...ace Under no circumstances should the air flow be such that cooled conditioned air can pass over the furnace heat exchanger This will cause condensation in the heat exchanger and possible failure of t...

Страница 15: ...use of one of the following auxiliary draft inducer kits Table 4 AUXILIARY DRAFT INDUCERS Vent Kit MFR Model Furnace Input Field Controls Co SWG 4G 50000 75000 100000 or 125000 Tjernlund Products Inc...

Страница 16: ...ssure switch tubing from the combustion blower 3 Remove the four 4 screws that secure the combustion blower adaptor plate to the flue collector box taking care to support the blower assembly so that i...

Страница 17: ...ny other gas fired burning appliance to their previous conditions of use ELECTRICAL CONNECTIONS When installed the furnace must be electrically grounded in accordance with local codes or in the absenc...

Страница 18: ...ifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life The furnace and its individual shutoff valve must be...

Страница 19: ...20541501 Issue 0240 Page 17 of 26 THEORY OF OPERATION...

Страница 20: ...g completed and the furnace has been properly vented the unit should be started and adjusted for proper operation Check off the following steps as they are completed 1 Be sure all electrical power is...

Страница 21: ...of gas flow by using the formula provided below or Table 5 Cubic Ft Hr Number of Dial Revolutions x Cubic Foot Revolution x 3600 Time in seconds Required for Number of Timed Revolutions TABLE 5 Gas R...

Страница 22: ...ifold pressure The appropriate manifold pressures based on the elevation and the heating value can be found in Table 7 TABLE 7 High Altitude Manifold Pressure Derate with standard 42 orifice Natural 5...

Страница 23: ...h The furnace should be allowed to cool off before attempting to reset the switch Failure to follow these instructions could result in injury due to burns The switch located behind the burner access p...

Страница 24: ...SEQUENCE OF OPERATION Direct ignition system control 20541501 Issue 0240 Page 22 of 26...

Страница 25: ...This will expose both the burner and flue openings of the primary heat exchangers 6 Vacuum the length of each heat exchanger tube using a straight attachment into the burner openings and the flue ope...

Страница 26: ...2 screws located in the blower compartment that secure the blower legs to the blower partition panel 7 Slide the blower forward about two 2 inches This will disengage the rear of the blower legs from...

Страница 27: ...TROUBLE SHOOTING With LED Indicator Assistance 20541501 Issue 0240 Page 25 of 26...

Страница 28: ...WIRING DIAGRAM 20541501 Issue 0240 Page 26 of 26...

Страница 29: ...he CSA International symbols on each nameplate is your assurance that your furnace design meets nationally recognized standards for safety and performance Do not store or use gasoline or other flammab...

Страница 30: ...dor of gas is present Use only your hand to adjust the gas control switch never use tools If the switch will not move by hand don t try to repair it call a qualified service technician Force or attemp...

Страница 31: ...tat dial or lever to select the temperature you would like the system to maintain Fan Operation You may wish to increase your comfort by setting your system for continuous air circulation of the indoo...

Страница 32: ...flashlight will be useful for these inspections Make one inspection prior to the beginning of the heating season and another during the middle Should you observe unusual amounts of any of the followi...

Страница 33: ...and place back in furnace To clean a permanent filter shake filter to remove excess dirt and or use a vacuum cleaner Wash filter in soap or detergent water and replace after filter is dry Permanent fi...

Страница 34: ...ner Blower Motor Blower Door Shield Top Bottom Blower Wheel Orifice Capacitor Ignitor Blower Support Leg Gas Control Sensor ELECTRICAL GROUP HEAT EXCHANGER GROUP INDUCER GROUP Access Door Primary Heat...

Страница 35: ...FURNACE MARKINGS IN FRENCH CONSULT WITH YOUR DEALER OR LOCAL DISTRIBUTOR HAVE AVAILABLE THE MODEL NO AND SERIAL NO LOCATED ON THE UNIT RATING PLATE TO INSURE THE CORRECT FRENCH INSTRUCTION PACKET POUR...

Страница 36: ......

Страница 37: ...510 88 111 Fax 420 2 579 10 393 e mail janka janka cz LENNOX DISTRIBUTION MOSCOW Tel 7 095 933 29 55 Fax 7 095 926 56 50 e mail lennox dist moscow co ru LENNOXSLOVENSKOs r o Tel 421 7 44 87 19 27 Fax...

Отзывы: