Page 46
Cleaning the Burner Assembly
1 - Turn off gas and electrical power to the furnace. Re
move heating compartment access panel.
2 - Disconnect the gas supply line from the gas valve.
3 - Disconnect and label wires from gas valve.
4 - Disconnect ignitor wiring at 2 circuit plug.
5 - Disconnect and label wires from rollout switch.
6 - Disconnect and label flame sensor wire.
7 - Disconnect and label ground wire from burner/man
ifold assembly.
8 - Remove four screws that secures burner/manifold as
sembly to vestibule. Remove the assembly and make
note not to allow ignitor plate to dislodge from the as
sembly.
9 - Gently clean the face of the burners using the soft
brush attachment on a vacuum cleaner. Visually in
spect the inside of the burners and crossovers for any
blockage caused by foreign matter. Remove any
blockage
10 - Reinstall the burner/manifold assembly using the ex
isting four screws.
Burners are self aligning to cen
ter of clam shells.
11 - Reconnect ground wire.
12 - Reconnect flame sensor wire.
13 - Reconnect rollout switch wires.
14 - Reconnect ignitor wires.
15 - Reconnect gas valve wires.
16 - Reconnect gas supply line to gas valve.
17 - Refer to instructions on verifying gas and electrical
connections when re-establishing supplies.
18 - Follow instructions to place furnace in operation. Run
furnace 5 minutes to ensure burners are clean and op
erating correctly.
19 - Replace heating compartment access panel.