Brazing Connections 

Use the procedures outlined in figures 8 and 9 for brazing 

line set connections to service valves. 

 WARNING

Danger  of  fire.  Bleeding  the  refrigerant 

charge from only the high side may result 

in pressurization of the low side shell and 

suction tubing. Application of a brazing torch 

to a pressurized system may result in ignition 

of the refrigerant and oil mixture. Check the 

high and low pressures before applying heat.

 CAUTION

Brazing  alloys  and  flux  contain  materials  which  are 

hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. 

Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to 

protect against burns.
Wash hands with soap and water after handling brazing 

alloys and flux.

 IMPORTANT

Allow braze joint to cool before removing the wet rag 

from the service valve. Temperatures above 250ºF can 

damage valve seals.

 IMPORTANT

Use silver alloy brazing rods with 5% minimum silver 

alloy for copper-to-copper brazing. Use 45% minimum 

alloy for copper-to-brass and copper-to-steel brazing.

 IMPORTANT

If this unit is being matched with an approved line set 

or indoor unit coil that was previously charged with 

mineral oil, or if it is being matched with a coil which 

was manufactured before January of 1999, the coil and 

line set must be flushed prior to installation. Take care to 

empty all existing traps. Polyol ester (POE) oils are used 

in Lennox units charged with HFC-410A refrigerant. 

Residual mineral oil can act as an insulator, preventing 

proper heat transfer. It can also clog the expansion 

device and reduce system performance and capacity.

Failure to properly flush the system, per this instruction 

and the detailed Installation and Service Procedures 

manual will void the warranty.

Содержание ML14XC1 Series

Страница 1: ...d Service Valves 6 Installation 8 Unit Placement 8 Removing and Installing Louvered Panels 10 New or Replacement Line Set 11 Brazing Connections 13 Flushing Line Set and Indoor Coil 16 Installing Indo...

Страница 2: ...Hz J voltage Product Tier ML Merit Series Unit Type C Air Conditioner Cooling Stages 1 Single Stage Compressor Ratings Revision Level Nominal Cooling Capacity 036 3 tons 042 3 5 tons 048 4 tons 060 5...

Страница 3: ...diameter in 5 16 5 16 5 16 5 16 No of rows 2 2 2 2 Fins per inch 22 22 22 22 Outdoor Fan Diameter in 22 22 22 26 No of Blades 3 3 4 4 Motor hp 1 6 1 6 1 4 1 4 Cfm 3160 3050 3600 4550 Rpm 825 825 825 8...

Страница 4: ...CONNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4...

Страница 5: ...CTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH S4 COMPRESSOR HARNESS TYPICAL PLUMBING COPELAND COMPRESSOR TYPICAL PLUMBING LG COMPRESSOR HIGH PRESSURE SWITCH S4 FIELD...

Страница 6: ...p before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2 NM Machine screws 10 28 ft lb 3 NM Compressor bolts 90 in lb 10 N...

Страница 7: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Страница 8: ...ions If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be con structed Size barrier at least the same height and width as outdoor unit Mount barrier 24 inches 610...

Страница 9: ...or 2 inches per 5 feet 50 mm per 1 5 m away from building structure DETAIL A DETAIL B INSTALL UNIT AWAY FROM WINDOWS TWO 90 ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION GROUND LEVEL MOU...

Страница 10: ...Remove panel A first then B C and finally D When reinstalling panels reverse that order starting with panel D C B and finally A REMOVAL Repeat steps 1 2 and 3 to remove panels B C and D STEP 1 Startin...

Страница 11: ...ING Fire Explosion and Personal Safety hazard Failure to follow this warning could result in damage personal injury or death Never use oxygen to pressurize or purge refrigeration lines Oxygen when exp...

Страница 12: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 13: ...T Allow braze joint to cool before removing the wet rag from the service valve Temperatures above 250 F can damage valve seals IMPORTANT Use silver alloy brazing rods with 5 minimum silver alloy for c...

Страница 14: ...EN HIGH LOW B A C PIPING PANEL REMOVAL AND LINE SET PREPARATION CAP AND CORE REMOVAL Remove piping panel for easier access to service valves Cut ends of the refrigerant lines square free from nicks or...

Страница 15: ...T TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service va...

Страница 16: ...STING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Страница 17: ...Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wre...

Страница 18: ...KP SURE CLOSE THE VALVE ON THE HFC 410A CYLINDER AND THE VALVE ON THE HIGH PRESSURE SIDE OF THE MANIFOLD GAUGE SET DISCONNECT THE HFC 410A CYLINDER C CONNECT A CYLINDER OF DRY NITROGEN WITH A PRESSURE...

Страница 19: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Страница 20: ...rams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage co...

Страница 21: ...CONTROL WIRING NOTE Wire tie provides low voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits NOTE For proper voltages select thermostat wire...

Страница 22: ...Page 22 FIGURE 15 Typical Factory Wiring G and Y Voltages...

Страница 23: ...Page 23 FIGURE 16 Typical Factory Wiring J Voltage...

Страница 24: ...he technician to check the following items These checks may only be con ducted by a licensed professional HVAC technician Outdoor Unit 1 Inspect component wiring for loose worn or damaged connections...

Страница 25: ...technician will check the refrigerant charge per the charging sticker information on the outdoor unit 3 Verify that system total static pressure and airflow set tings are within specific operating par...

Страница 26: ...high pressure switch is closed 3 K1 1 N O closes energizing compressor B1 and out door fan motor B4 4 Compressor B1 and outdoor fan motor B4 begin im mediate operation END OF COOLING DEMAND 5 Cooling...

Страница 27: ...the unit is running Power must be within range shown on the nameplate 8 Check system for sufficient refrigerant by using the procedures that follow System Refrigerant This section outlines procedures...

Страница 28: ...DRY BULB A AND WET BULB B DT IS THE INTERSECTING VALUE OF A AND B IN THE TABLE SEE TRIANGLE 2 FIND TEMPERATURE DROP ACROSS COIL MEASURE ING THE COIL A AND C TEMPERATURE DROP FORMULA TDROP A MINUS C F...

Страница 29: ...ve refrigerant based upon line length BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressure...

Страница 30: ...26 9 80 26 7 235 15 26 1 31 7 85 29 4 254 10 23 3 36 8 90 32 2 274 5 20 6 42 5 95 35 0 295 0 17 8 48 6 100 37 8 317 5 15 0 55 2 105 40 6 340 10 12 2 62 3 110 43 3 365 15 9 4 70 0 115 46 1 391 20 6 7...

Отзывы: