NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

13

13

START

CHECK

• Turn Off Gas Supply.

• Ensure Valve Switch Is In ON Position.

• Disconnect Control Harness.

• Set Thermostat To Call For Heat.

• Check for proper volt-

age at control harness  
(see insert A).  Voltage 
should be 24V   between 
thermostat or pressure 
switch and 24V common 
and 24V hot.

NO

•  Line voltage power
•  Low voltage transformer
•  Limit controller
•  Thermostat
•  Wiring

                      YES

• Plug control harness into 

valve.  Wait for internal check 
delay.

 • Igniter warms up and glows 

red. 

NO

 • With pilot burner cable con-

nected, measure voltage at 
valve HSI element output.  24V 
nominal.  (See insert B)

NO

•  Replace valve.

                         YES

                      YES

•  Replace igniter/fl ame rod 
    assembly.

                         YES

• Turn on gas supply.   
• Pilot burner lights.

NO

•  Check that pilot gas is fl owing.  Wait 

to ensure pilot gas tubing is purged.  
Recycle call for heat if necessary.

NO

•  Replace valve.

                         YES

                      YES

•   Measure voltage between 24V hot and 

24V common leads to valve control.  
Must measure at least 19.5 VAC with 
igniter powered (see insert A).  To 
identify proper lead, this check must 
be done with the valve control con-
nected and igniter powered.

NO

•  Check transformer and    

line volt supply.

                         YES

•    Replace Pilot Assembly.

•  Main valve opens and main 

burner lights.

NO

•  Check that pilot fl ame makes good 

contact with pilot burner fl ame rod.

•    Check for good electrical connection 

through the pilot tubing.

•   If both of the above are good, replace 

igniter/fl ame rod assembly.

                      YES

                         YES

•  System Is okay.

•    Cycle thermostat off and back on.

   

Igniter will cycle off and 

back on once during the 90 
second ignition trial.  All 
voltage measurements must 
be taken while the igniter is 
powered.

 

      

When measuring voltage 

at connections, use care 
to ensure terminals are 
not damaged.

•    Main burner lights.

NO

 •  Replace valve.

Insert A

End View of Control Harness Connector

24 Volt

Common

24 Volt Hot

24 Volt 

Switched

Check For Damaged or Missing
Terminals in Connector

Insert B

Igniter Terminals

1

2

2

1

2

1

TROUBLESHOOTING PROCEDURE - ELECTRONIC IGNITION SYSTEM

Содержание Merit Plus MPB35ST-NE

Страница 1: ...ot store or use gasoline or other flammables or liquids in the vicinity of this or any other appliance FOR YOUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrica...

Страница 2: ...Electronic models have a fixed rate gas valve Input of electronic models is shown in the following table INTRODUCTION The millivolt appliances have a millivolt gas controlvalvewitha piezoignitionsyste...

Страница 3: ...ngappliance voiding its warranty Any change to this appliance and or its operating controlsisdangerous Improper installation or use of this appli ance can cause serious injury or deathfromfire burns e...

Страница 4: ...alve shown in Figure 3 Gas Control Compartment Access The gas controls can be found behind the control compartment access panel To open the control compartment access panel actuate the spring loaded m...

Страница 5: ...ng pilot flame Exercise cau tion when using products with combustible vapors VENT OPERATION TEST A vent operation test is required as part of the installationtoverifythatproperventingcondi tions exist...

Страница 6: ...d service technician should follow vent installation instructions for proper reassembly and proper sealing of the venting system components However more frequent periodic inspections and cleanings sho...

Страница 7: ...s properly installed Generally the glass enclosure panels should not be removed except to gain access to the components within the firebox and the appliance may only be operated without the front glas...

Страница 8: ...ulite Bag 2 liters F D Bottom View of Logs in packaging Top View of Logs C E A B Glowing Embers Bag of Glowing Embers rockwool Separate into Quarter Size separate Pieces Top View of Logs Installed E B...

Страница 9: ...tted Distribute these pieces over the surface of the burner as shown in Figure 8 Do not use more than is necessary Ensure that the main burner ports remain uncovered by the ember material Note This ap...

Страница 10: ...ar sooty Air Shutter Adjustment Guidelines Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flame will be orange Air shutter gap should be increased If air shu...

Страница 11: ...box Clean firebox walls and log grate Replace logs embers rockwool and vermiculite as detailed in this manual see Pagexs 8 10 Check Flame Patterns and Flame Height Homeowner Refer to Figurex 15 on Pag...

Страница 12: ...ual Reset Spill Switch has Tripped or is defective Follow Manual Reset procedure on Page 6 Once the redresetbuttonisfullydepressedandclicksin check continuity with a multimeter between switch terminal...

Страница 13: ...V common leads to valve control Mustmeasureatleast19 5VACwith igniter powered see insert A To identify proper lead this check must be done with the valve control con nected and igniter powered NO Chec...

Страница 14: ..._____ The Date On Which Your Fireplace Was Installed___________________________ The Type of Gas Your Fireplace Uses ____________________________________ Your Dealer s Name ____________________________...

Страница 15: ...on near the fireplace WhiteWallSwitchKit Cat No ModelNo Description 85L87 FWSK OFF ONWallSwitchKit ref Form 750 127M Touch Up Paint Kit Repair of minor scratches and discoloration of theappliancecharc...

Страница 16: ...58 AD35C 35 Arch Doors Charcoal H0859 AD35TI 35 Arch Doors Textured Iron H0860 AD35SP 35 Arch Doors Satin Pewter H0861 AD35AB 35 Arch Doors Antique Brass Arch Pane Design Kits H0930 APD35C 35 Arch Pan...

Страница 17: ...to previously installed Multi Open Series appliances The decorative arch kits can not be used in conjunction with the screen panel kit 35 Arch Door Kits Cat No Model No Description 26M43 ADK35CMPB Arc...

Страница 18: ...AT TO DO IF YOU SMELL GAS Extinguish any open flame Open windows Do not light any appliance Do not touch any electrical switches TO TURN OFF GAS TO APPLIANCE 1 Turn remote wall switch OFF The pilot wi...

Страница 19: ...s been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRU...

Страница 20: ...l 11 H3358 1 Grate Assembly All 12 69L2101 4 Latch Glass Enclosure Panel All 13 H3354 1 Firebox Sub floor All Item Part Cat Qty Description Where Used Misc Replacement Parts 14 H3210 1 Log Set All 15...

Отзывы: