background image

22

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

D. Install Firestop / Spacers at ceilings and walls 

When Secure Flex penetrates a wall or ceiling, 

a firestop / spacer is required: use the SF4.5 VF 

firestop / spacer for ceilings and the SF4.5 HF 

firestop / spacer for walls. See the appropriate 

sections and Figures shown throughout the vent-

ing section for their installation requirements. 

APPLY  ONLY  MIL-PAC  BLACK 

HIGH  TEMPERATURE  SEALANT 

(Cat. No. 0K8) to the outside 

surface  of  both  collars  of  the 

adapter (be especially careful to 

fill the grooves of the outer collar 

to be covered by the flexible pipe) 

and slide flexible pipe over inner 

and outer adapter collars.

 3/4 inch (44 mm) Flexible 

Pipe and Adapter Outer Collar 

Overlap

Adapter (SV4.5RF)

Attach Adapter to Appliance 

Collar, or Secure Vent Sections

Flex Vent

Gear Clamps

Securing Screw 

- 3 Places, 20° apart 

(equally spaced) Just 

Below Gear Clamp

 3/4  in. (44 mm) Flexible 

Pipe and Adapter Inner Collar 

Overlap

Securing  Screw  -  3  Places 

Equidistant (equally spaced) 

Just Below Gear Clamp)

VERTICAL OR HORIZONTAL VENTING USING 

SECURE FLEX

 KITS AND COMPONENTS

Secure  Flex

  venting  kits  and  components 

may  be  used  in  any  venting  application  in 

place of rigid 

Secure Vent

 (SV4.5) direct vent 

components.  All restrictions, clearances and 

allowances that pertain to the rigid piping apply 

to the flexible venting.  

Secure Flex kits may 

not be modified; also, under no circumstances 

may separate sections of flex pipe be joined 

together

Using  adapter  (SV4.5RF),

  Secure  Flex

  kits 

may be added to the end of a vent run made 

up of rigid 

Secure Vent

 (SV4.5) vent sections 

provided that doing so does not violate any of 

the venting length, height, routing, horizontal 

to  vertical  ratio  requirements  or  clearance 

considerations detailed in this manual.

Secure  Flex

  kits  come  with  an  adapter  that 

can  be  fitted  to  the  inclined  channel  end  of 

the last 

Secure Vent

 (SV4.5) vent section in a 

rigid system in the exact same fashion as any 

other 

Secure Vent 

section.  Align the dimpled 

end of the adapter over the previously installed 

section or appliance collar, adjusting the radial 

alignment until the four locking dimples of the 

adapter are aligned with the inlets of the four 

incline channels of the last vent section or collar.  

Push on the adapter until it fully engages, then 

twist the adapter clockwise running the dimples 

down and along the incline channels until they 

seat at the end of the channels.

Attach the flexible vent to the adapter as fol-

lows 

(see also 

Figure 33

)

:

A. Install the Inner Flex Pipe - 

.

 Install the small  gear clamp loosely around 

the inner flexible vent pipe, push it back out 

of the way.

2.

 Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 0K8

 

to the inner adapter collar, approximately 

1/2 inch from the end.

3.

 Pull and extend the inner flexible vent pipe. 

4.

  Slide the inner flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 1 

3/4 inches from the end, and that it is free  

from damage or tears. 

5

. Slide the gear clamp down and tighten it 

fully to secure the flexible vent to the adapter 

inner collar approximately 3/4 inch from the 

end of the flex.

6

.  Install 

three  screws  20  degrees  apart

 

through the flexible vent pipe and into the 

adapter collar just below the gear clamp to 

provide additional security to the connec-

tion.

B. Install the Outer Flex Pipe - 

.

 Install the large gear clamp loosely around 

the outer flexible vent pipe, push it back out 

of the way.

 

2.

 Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 0K8)

 

to the outer adapter collar; to the grooves 

of the collar which extend approximately 1 

inch from the end and to the flat surface, 

approximately 1-3/8 inches from the end. 

3.

 Pull and extend outer flexible vent pipe. 

4.

 Slide the outer flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 

1-3/8 inches from the end, and that it is free 

from damage or tears. 

5

. Slide  the  gear  clamp  down  and  tighten  it 

fully to secure the flexible vent to the adapter 

outer collar approximately 3/4 inch from the 

end of the flex.

6.

 Install 

three  screws  20  degrees  apart

 

through the flexible vent pipe and into the 

adapter collar just below the gear clamp to 

provide additional security to the connec-

tion.

C. Route Flex Vent -

Ensure that the flex vent is properly routed to 

provide the required clearance. 

Do not 

allow the 

flexible vent to bend in a radius tighter than 5" 

(127 mm). Refer to 

Figure 34

. Space out the 

internal flex vent spacers evenly - approximately 

every 6 inches - and avoid kinking of inner pipe. 

Support horizontal sections of flex with metal 

straps at 2 foot (0.61 m) intervals. 

E. Attach Flex Vent to Termination -

  

Secure  Flex

  components  can  be  purchased 

separately and attached to bulk lengths of 

Se-

cure Flex

 flexible tubing cut to size at the job 

site.  Secure the flexible vent to the 

Secure Flex

 

terminations in the same manner (see

 Figure 

33) 

as it was attached to the adapter.

Note: Secure Flex vent must be attached to Se-

cure Flex terminations only. DO NOT substitute 

Secure Vent terminations or the Secure Vent 

adapter for Secure Flex components. The col-

lars of Secure Flex terminations and adapters 

have a different diameter than that used with 

the Secure Vent pipe.  Additionally, Secure Flex 

components have an extended length center 

tube for use in attaching the flexible vent.

Figure 33

Flexible Vent 

Section

5” (27 mm)

Radius

Minimum

Figure 34

Note:  Outer Pipe Is Pulled Away To 

Show The Detail of The Inner Pipe

Содержание Merit MLDVT-45NE

Страница 1: ...FE DIRECT VENT MLDVT 30 35 40 45 SERIES Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not light any ap...

Страница 2: ...owing vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and Z FLEX Model GA Venting Systems listed...

Страница 3: ...pane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Do not use these appliances if any part has...

Страница 4: ...re Tap Manifold Burner Stage Terminal Ground TP PILOT OUT VENT LO TH TP TH TP HI IN IN Regulator Mounting Screw Cold Climate Insulation For cold climate installations seal all cracks around the applia...

Страница 5: ...bustible and combustible exterior sidewall This distance may be decreased to 2 5 mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Be aware that this is a heat produc...

Страница 6: ...e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 f o t h g i e h a n i h t i w m c 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 f o t h g...

Страница 7: ...sides as detailed inTable6 withthefollowingexception When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit...

Страница 8: ...box floor securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 46 on Page 30 TYPICAL INSTAL...

Страница 9: ...P VENT WITH ONE 90 ELBOW Framing should be constructed of 2x4 or larger lumber Inches mm D 30 D is the required framing depth dimension when the finish material drywall thickness is 2 in 3mm A 2 Frami...

Страница 10: ...rlocalcode requirements i e arebelowgradepenetrations of the gas line allowed etc IMPORTANT Ifpropaneisused beawarethat if tank size is too small i e under 100 lbs if this is the only gas appliance in...

Страница 11: ...ructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes theseinstructions thecurrentNational Fuel Gas Code ANSI Z223 1 in the USA or th...

Страница 12: ...5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Страница 13: ...are available in net lengths of 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm Refer to the Vent Section Length Charts on Page 12 for an aidinselectinglengthcombinations El...

Страница 14: ...supplied with the flashing over the vent flashing joint See Figure 21 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the ad justingscrew Applynon combus...

Страница 15: ...ERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 uWhenusingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF A Vent Restrictor as shown in Figure 14 Page 11...

Страница 16: ...2 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 60 ft 18 3 m Max Figure 25 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure...

Страница 17: ...ously connected vent sections See Figure 17 on Page 13 I Continue installation of horizontal inclined sections Continue with the installation of the straightventsectionsinhorizontal inclinedrun as des...

Страница 18: ...nations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not plac...

Страница 19: ...S THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 Use Table 10 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES Figur...

Страница 20: ...6 096 m Max Figure 31 Top Vent TWO 90 DEGREE ELBOWS See Table 10 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES...

Страница 21: ...Figure 29 V H H V vWall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF vWall Firestop...

Страница 22: ...mperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure th...

Страница 23: ...he electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 12 on Page 9 3 Removethe coverplate sknockoutandthen feedthepowersupplywirethroughtheknocko...

Страница 24: ...artment Accessthevalvecompartmentbyremovingthe lower control compartment panel see Figure 38 by lifting and pulling the panel forward The panel is mounted on supporting tabs at the extreme right and l...

Страница 25: ...e gas lines are tested and leak free be sure to rinse off the leak testing solution D Observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly acro...

Страница 26: ...ted Dis tribute these pieces over the surface of the burner as shown in Figures 44 and 45 Do not use more than is necessary Ensure that the main burner slots remain uncovered by the ember material Pos...

Страница 27: ...35 H7666 WARNING Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Left Rear Log Bracket Right Rear Log Bracket Rockwool Do Not Place...

Страница 28: ...ot Place Rockwool Over Burner Slots Log Rack Volcanic Stone Right Rear Log Bracket 1 Position on the left rear log bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log...

Страница 29: ...29 NOTES...

Страница 30: ...with the bottom of the door held away from the fireplace Figure 46 Hook the top flange of the door frame over the top of the firebox frame 6 Let the bottom of the door frame swing gentlyintowardsthefi...

Страница 31: ...ont glass panel are in place and sealed during adjustment 1 Locate adjustment rod and adjust air shutter to the standard set ting as shown in Figure 49 adjustment rod is located in the lower control c...

Страница 32: ...7 7 B F 5 4 V S e l b a t s u j d A 2 1 2 1 o t 2 1 7 g n i h s a l F 1 8 L 7 7 6 C S 5 4 V S 6 s r a l l o C m r o t S x o b s r a l l o c 6 4 2 2 H F H 5 4 V S k c a p 0 1 r e c a p S p o t s e r i...

Страница 33: ...o f n i m r e T l a c i t r e V x e l F h t i w 2 1 6 o t t a l f d i g i r f o n o i t c e s r e t p a d A r a l l o c t r o p p u s f o o r t n e v d n a g n i h s a l f f o o r y l b m e s s a r a...

Страница 34: ...on kit when performing any gas conversion Gas Conversion Kits Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructionsandallappli...

Страница 35: ...o pressure regula tor mounting screws Remove the pressure regulatoranddiaphragm Discardallremoved components Ensure the provided diaphragm is installed properly onto the replacement pressure regulator...

Страница 36: ...pe joint compounds on flare fittings PILOT OUT VENT LO TH TP TH TP HI IN IN Pilot Stage Terminal Pressure Tap Inlet Pilot Gas Outlet Supply Gas Inlet Pressure Tap Manifold Burner Stage Terminal Ground...

Отзывы: