
Page 7
51M39 SERIES 5/2
Removing and Installing Thermostat
The thermostat hinges on tabs on the top of the subbase;
no tool is needed to remove the thermostat from the sub-
base. Pivot the bottom of the thermostat outward (releas-
ing the snaps), then lift up to remove.
To install it, first position the top tilted toward the wall brack-
et and align it until you feel the tabs and slots engage; then,
while the top is in place, pivot the bottom toward the wall
until the thermostat snaps into place.
Default Thermostat Settings
Default thermostat settings are in table 2 and the default
program is shown in table 3.
Table 2
Default Thermostat Settings
Mode
Heat (Perm. Hold)
Heat Setpoint (Perm Hold)
70°F (or 21°C)
Cool Setpoint (Perm Hold)
78°F (or 26°C)
Fan
Auto
Filter Reminder
OFF
Maintenance Reminder
OFF
Equipment Protection Timers
Reset Back to Zero
Autochangeover
OFF
Table 3
Default Program Settings (Time & Temp.)
Programs
Time
Temp.− Heat
Temp.− Cool
All days − A
6:00am
70
_
F / 21
°
C
78
_
F / 26
°
C
All days − B
8:00am
62
_
F / 17
°
C
85
_
F / 29
°
C
All days − C
6:00pm
70
_
F / 21
°
C
78
_
F / 26
°
C
All days − D
10:00pm 62
_
F / 17
°
C
82
_
F / 28
°
C
Thermostat Output Table
Table 4 depicts the 51M39 thermostat output states for var-
ious input conditions. The following notes described terms
used in the table.
Table 4
Thermostat Outputs
Condition
W1
W2
Y1
Y2
G
Gas Heat, Auto Fan
Heat Demand, SMALL
X
Heat Demand, LARGE
X
X
Cool Demand, SMALL
X
X
Cool Demand, LARGE
X
X
X
No Demand
Gas Heat, Continuous Fan
Heat Demand, SMALL
X
X
Heat Demand, LARGE
X
X
X
Cool Demand, SMALL
X
X
Cool Demand, LARGE
X
X
X
No Demand
X
Electric Heat, Auto Fan
Heat Demand, SMALL
X
X
Heat Demand, LARGE
X
X
X
Cool Demand, SMALL
X
X
Cool Demand, LARGE
X
X
X
No Demand
Electric Heat, Continuous Fan
Heat Demand, SMALL
X
X
Heat Demand, LARGE
X
X
X
Cool Demand, SMALL
X
X
Cool Demand, LARGE
X
X
X
No Demand
X
NOTE − X = output is activated with 24VAC.
NOTE − The temperature ranges expressed in the follow-
ing definitions of SMALL/LARGE" demands are for guid-
ance only; actual temperatures may vary.
With a SMALL heat demand, temperature is:
below
setpoint –0.5F
but above
setpoint –1.5F
AND 30-minute upstage timer HAS NOT expired.
With a LARGE heat demand, temperature is:
less than
setpoint –1.5F
OR 30-minute upstage timer HAS expired.
With a SMALL cool demand, temperature is:
above
se0.5F
but below
se1.5F
AND 30-minute upstage timer HAS NOT expired.
With a LARGE cool demand, temperature is:
above
se1.5F
OR 30-minute upstage timer HAS expired.
Содержание Merit 51M37
Страница 36: ......