Lennox Merit 51M37 Скачать руководство пользователя страница 3

Page 3

51M37 SERIES 5/2

HEAT − Using the Heat Mode

Normal Heat Mode

In normal heat mode, both the heat pump and the backup
heat source are used to provide heat. If the thermostat de-
tects that the heat pump is not able to provide enough heat
(as may be the case in very cold weather), then the backup
heat source is activated.

Emergency Heat Mode

In emergency heat mode, only the backup heat source
provides heat the heat pump is disabled. The backup
heat source is activated only when there is a heat demand.

Enabling Normal Heat Mode

Use the HEAT button to select normal heat mode, emer-
gency heat mode, or to disable heat modes as desired. If
the thermostat is in OFF or COOL mode, pressing the Heat
button enables Heat mode. This is indicated by HEAT in
the SYSTEM box as shown in figure 4.

Heat

Prog

Fan

Settings

Cool

Day/Time

Hold

Enter

Normal Heat Mode Enabled

Figure 4

5:30

66

70

HOLD

AM

PM

SETPOINT

ROOM

FAN

AUTO

SYSTEM

HEAT

MO

°

°

Enabling Emergency Heat Mode

If the thermostat is in heat mode, pressing the Heat button
enables EMG. HEAT mode (see figure 5). If the thermostat
is in normal heat mode when the HEAT button is pressed,
then emergency heat mode is enabled.

SYSTEM

COOL
OFF

EMG.
HEAT

62

Emergency Heat Mode Enabled

Figure 5

ROOM

°

75

SETPOINT

°

Disabling Heat Mode

If the thermostat is in emergency heat mode when the
HEAT button is pressed, then heat modes are disabled.
This is indicated by OFF in the SYSTEM box as shown in
figure 6.

SYSTEM

COOL

OFF

HEAT

75

Heat Mode Disabled

Figure 6

ROOM

°

75

SETPOINT

°

Heating Demand

The thermostat must be in either normal or emergency
heat mode in order to properly control the heating equip-
ment. In either heat mode, when the actual temperature is
lower than the temperature setpoint (as shown in figure 7),
the thermostat detects a heating demand and activates the
heating equipment to satisfy the demand. Heating opera-
tion is indicated by a flame icon in the SYSTEM box.

SYSTEM

COOL
OFF

HEAT

72

Figure 7

ROOM

°

75

SETPOINT

Heating Demand

°

When the actual temperature rises above the temperature
setpoint, the flame icon will disappear. This indicates that
the heating demand has been satisfied and that the heat-
ing equipment has been turned off.

Heat pump operation is locked out for 5 minutes after a de-
mand has been satisfied. If another heat pump demand
occurs during this 5−minute interval, the flame icon will
flash; however, the heat pump will not run until the 5−min-
ute delay has elapsed.

NOTE − The heat pump is activated for at least 4 minutes if
no buttons are pressed during the demand interval. The
backup heat source is activated for at least 3 minutes if no
buttons are pressed during the demand interval.

If your system supports 3−stage heating (as does the
51M37 thermostat), you may notice various heating levels
being delivered during a demand.

If a small heat pump heating demand is present, "Lo" is dis-
played in the SYSTEM box; if a large heat pump heating
demand is present, "Hi" is displayed (see figure 8).

65

Large Heat Demand

Figure 8

ROOM

°

75

SETPOINT

SYSTEM

COOL
OFF

HEAT

°

Hi

Содержание Merit 51M37

Страница 1: ...eat Mode 3 COOL Cool Mode 4 HOLD Temperature Hold Mode 5 PROG Thermostat Programming 5 FAN Controlling Fan Operation 6 SETTINGS Filter and Maintenance Reminders 6 SETTINGS Balance Point 7 Service Indi...

Страница 2: ...ed When PROG or DAY TIME is pressed a field begins flash ing expecting another input Start making changes within 15 seconds or the HOME screen will return Heat Prog Fan Settings Cool Day Time Hold Ent...

Страница 3: ...ox as shown in figure 6 SYSTEM COOL OFF HEAT 75 Heat Mode Disabled Figure 6 ROOM 75 SETPOINT Heating Demand The thermostat must be in either normal or emergency heat mode in order to properly control...

Страница 4: ...B C D HOLD 75 Cooling Demand Figure 11 ROOM 70 SETPOINT FAN ON AUTO SYSTEM COOL OFF HEAT AM PM MO TU WE TH FR SA SU Hi Cooling operation is indicated by flashing snowflake icons in the SYSTEM box Whe...

Страница 5: ...ostat Programming The 51M37 thermostat can be programmed to perform a set of either heating or cooling events but not a combination of heat and cool for 5 consecutive days using a set of 4 unique even...

Страница 6: ...tings button shown below the Fan button in figure 17 once or twice for the desired reminder as shown in fig ure 18 and as described in table 1 Reminder Settings Display Figure 18 FILTER OFF MAINT For...

Страница 7: ...mperature is 45 F the outdoor temperature must drop to 37 F before equipment adjustment occurs Service Indicator When abnormal equipment operation is detected the SERVICE indicator will flash on the s...

Страница 8: ...AC is present on the terminals of the thermostat bracket If removing the thermostat from the wall use caution and avoid touching any of the connec tor terminals on the wall bracket Also when working w...

Страница 9: ...r ridden if a heating or cooling demand is initiated or terminated using the UP DOWN HEAT or COOL buttons Equipment Protection Override Both the minimum compressor OFF timer and the mini mum equipment...

Страница 10: ...than setpoint 1 5F OR 30 minute upstage timer HAS expired With a very large heat demand temperature is below setpoint 2 5F OR 15 minute 2nd upstage timer HAS expired Emergency heat demand only if eme...

Страница 11: ...ture Hold Mode 4 PROG Thermostat Programming 4 FAN Controlling Fan Operation 5 SETTINGS Filter Maintenance Reminder 5 Service Indicator 6 Thermostat RESET 6 Removing Installing Thermostat 6 Default Th...

Страница 12: ...ssed When PROG or DAY TIME is pressed a field begins flash ing expecting another input Start making changes within 15 seconds or the HOME screen will return Heat Prog Fan Settings Cool Day Time Hold E...

Страница 13: ...he COOL button to enable or disable cool mode as desired If the thermostat is in HEAT or OFF mode cool mode is enabled when the COOL button is pressed This is indicated by COOL in the SYSTEM box see f...

Страница 14: ...to perform a set of either heating or cooling events but not a combination of heat and cool for 5 consecutive days using a set of 4 unique events per day The remaining 2 days can then be set for a di...

Страница 15: ...nce or twice for the desired reminder as shown in fig ure 15 and as described in table 1 Reminder Settings Display Figure 15 FILTER OFF MAINT For FILTER press Settings button 1 time For MAINT press Se...

Страница 16: ...per clip or small pencil to press the RESET button ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section Removing and Installing Thermostat The thermo...

Страница 17: ...very via DIP switch 6 Smart Setback Recovery SSR affects the way the ther mostat responds to program events If SSR is disabled the thermostat will react to a program event at the time the event occurs...

Страница 18: ...the electrical disturbance has passed Thermostat Operating Conditions 35 F to 105 F 5 to 90 RH Thermostat Storage Conditions 40 F to 185 F 5 to 95 RH Thermostat Output Table Table 5 depicts the 51M35...

Страница 19: ...mperature Hold Mode 4 PROG Thermostat Programming 4 FAN Controlling Fan Operation 5 SETTINGS Filter Maintenance Reminder 5 Service Indicator 6 Thermostat RESET 6 Removing Installing Thermostat 6 Defau...

Страница 20: ...ed a field begins flash ing expecting another input Start making changes within 15 seconds or the HOME screen will return Heat Prog Fan Settings Cool Day Time Hold Enter Thermostat Buttons Figure 3 DO...

Страница 21: ...ons are pressed during the demand interval COOL Using the Cool Mode Enabling and Disabling Cool Mode Use the COOL button to enable or disable cool mode as desired If the thermostat is in HEAT or OFF m...

Страница 22: ...to perform a set of either heating or cooling events but not a combination of heat and cool for 5 consecutive days using a set of 4 unique events per day The remaining 2 days can then be set for a di...

Страница 23: ...gure 14 once or twice for the desired reminder as shown in fig ure 15 and as described in table 1 Reminder Settings Display Figure 15 FILTER OFF MAINT For FILTER press Settings button 1 time For MAINT...

Страница 24: ...a per clip or small pencil to press the RESET button ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section Removing Installing Thermostat The thermost...

Страница 25: ...ion 1 F 1 C Smart Setback Recovery via DIP switch 6 Smart Setback Recovery SSR affects the way the ther mostat responds to program events If SSR is disabled the thermostat will react to a program even...

Страница 26: ...hours of power loss programmed settings will be lost and replaced with default settings IMPORTANT Power must be applied for at least six consecutive hours prior to a power loss in order for memory to...

Страница 27: ...Mode 4 PROG Thermostat Programming 4 COPY Copy a Program 6 FAN Controlling Fan Operation 5 Displaying Outside Temperature 6 SETTINGS Filter Maintenance Reminder 6 Service Indicator 6 Thermostat RESET...

Страница 28: ...pressed a field be gins flashing expecting another input Start making changes within 15 seconds or the HOME screen will re turn Heat Prog Fan Settings Cool Day Time Hold Enter Thermostat Buttons Figur...

Страница 29: ...nd NOTE Heating equipment is activated for at least 3 min utes if no buttons are pressed during the demand interval COOL Using the Cool Mode Enabling and Disabling Cool Mode Use the COOL button to ena...

Страница 30: ...nt is displayed to the right of the actual room temperature Each button press adjusts the setpoint up or down by 1 degree After the desired setpoint is reached the HOME screen will reappear after abou...

Страница 31: ...e same program for other days A Press the PROG button then press the COPY button The display clears the screen except for Copy from MO with MO flashing Press the COPY button again to copy Monday s pro...

Страница 32: ...nds after the final arrow button press OR press the ENTER button at any time to store any changes and exit to the HOME screen After either programmed interval has elapsed the remind er will be display...

Страница 33: ...picts the 51M39 thermostat output states for var ious input conditions The following notes described terms used in the table Table 4 Thermostat Outputs Condition W1 W2 Y1 Y2 G Gas Heat Auto Fan Heat D...

Страница 34: ...F Field Offset via DIP switches to 3 F Sampling Method temperature measurements sampled every 15 seconds Displayed temperature is the average of the last four measurements Outdoor Temperature Measure...

Страница 35: ...with 24VAC for at least 5 minutes AND the L terminal is shorted to the R terminal OR S if the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes AND the L terminal is shorted...

Страница 36: ......

Страница 37: ...Mode 4 AUTO Using the Autochangeover Mode 4 HOLD Temperature Hold Mode 4 PROG Thermostat Programming 5 COPY Copy a Program 5 FAN Controlling Fan Operation 6 Displaying Outside Temperature 6 SETTINGS...

Страница 38: ...ssed a field be gins flashing expecting another input Start making changes within 15 seconds or the HOME screen will re turn Heat Prog Fan Settings Cool Day Time Hold Enter Thermostat Buttons Figure 3...

Страница 39: ...s shown in figure 6 75 Heat Mode Disabled Figure 6 ROOM 75 HEAT SETPOINT OFF Heating Demand The thermostat must be in either normal or emergency heat mode in order to properly control the heating equi...

Страница 40: ...ing de mand occurs during this 5 minute interval COOL and the snowflakes will flash however the cooling equipment will not operate until the 5 minute delay has elapsed AUTO Using the Autochangeover Mo...

Страница 41: ...desired hour press the PROG button when the desired hour is reached use the Up Down arrow buttons again to select desired minute The selected hour minute is when the program will start Press the PROG...

Страница 42: ...u activate them To do so press the SETTINGS button shown below the FAN button in fig ure 16 once or twice for the desired reminder as shown in figure 18 and as described in table 1 Reminder Settings D...

Страница 43: ...mperature is near the balance point For example if the balance point is 40 F and the actual outdoor temperature is 35 F the outdoor temperature must rise to 43 F before equipment adjustment occurs Con...

Страница 44: ...essed in the following definitions of SMALL LARGE VERY LARGE de mands are for guidance only actual temperatures may vary With a SMALL heat demand temperature is below setpoint 0 5F but above setpoint...

Страница 45: ...Scale Fahrenheit Measurement Range 35 F to 99 F Measurement Resolution 0 5 F Measurement Accuracy 1 F Field Offset via DIP switches to 3 F Sampling Method temperature measurements sampled every 15 sec...

Страница 46: ...HEAT or COOL button down for 4 seconds Over Temperature Protection Thermal mechanical switch opens W1 Y1 Y2 and E at 93 F 6 F Filter Reminder Settings of Off 1 3 6 or 12 months of fan run time are ava...

Страница 47: ...Hold Mode 4 PROG Thermostat Programming 4 COPY Copy a Program 5 FAN Controlling Fan Operation 5 Displaying Outside Temperature 5 SETTINGS Filter Maintenance Reminder 5 Service Indicator 6 Thermostat...

Страница 48: ...r input Start making changes within 15 seconds or the HOME screen will re turn Heat Prog Fan Settings Cool Day Time Hold Enter Thermostat Buttons Figure 3 DOOR OPEN Auto Copy Outside When an Arrow HOL...

Страница 49: ...de of the display see figure 7 Heat Prog Fan Settings Cool Day Time Hold Enter Turn Cool ON OFF Figure 7 DOOR OPEN Auto Copy Outside 66 i0 30 75 70 If the thermostat is in cool mode pressing the COOL...

Страница 50: ...the Up Down arrow buttons until the desired setpoint is displayed HOLD flashes see figure 9 This overrides the program for 2 hours from the last button press then returns to the program While in Temp...

Страница 51: ...em peratures for days not yet programmed FAN Controlling the Fan Operation Use the FAN button to select either continuous fan mode or auto fan mode To change from continuous to auto fan mode or vice v...

Страница 52: ...ed the SERVICE indicator will flash on the screen see figure 16 This indicates that the equipment requires service from a qualified service technician Thermostat RESET Under some abnormal conditions i...

Страница 53: ...nnec tor terminals on the wall bracket Also when working with the thermostat dip switches use a non conductive tool and take cau tion to avoid making any contact with the circuit board its imprinted c...

Страница 54: ...iated or terminated using the UP DOWN HEAT or COOL buttons Equipment Protection Override Both the minimum compressor OFF timer and the mini mum equipment cycle timer can be over ridden by press ing an...

Отзывы: