Lennox Merit 13ACX-018-230 Скачать руководство пользователя страница 10

Page 10

STEP 3 -- LEAK TEST AND EVACUATION (CONTINUED)

A

Open both manifold valves and start the vacuum pump.

B

Evacuate the line set and indoor unit to an 

absolute pressure

 of 23,000 microns (29.01 inches of mercury).

NOTE 

— During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure

indicates a relatively large leak. If this occurs, 

repeat the leak testing procedure

.

NOTE 

— The term 

absolute pressure

 means the total actual pressure above absolute zero within a given volume or system. Absolute

pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C

When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:

S

Close manifold gauge valves.

S

Close valve on vacuum pump.

S

Turn off vacuum pump.

S

Disconnect manifold gauge center port hose from vacuum pump.

S

Attach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.

S

Open manifold gauge valves to break the vacuum in the line set and
indoor unit.

S

Close manifold gauge valves.

D

Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the

nitrogen from the line set and indoor unit.

E

Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the

absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

F

When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a

cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in
the line set and indoor unit.

G

Perform the following:

A

Connect low side of manifold gauge set with
1/4 SAE in-line tee to 

vapor 

line service valve

B

Connect high side of manifold gauge set to

liquid 

line service valve

C

Connect available micron gauge connector
on the 1/4 SAE in-line tee.

D

Connect the vacuum pump (with vacuum
gauge) to the center port of the manifold
gauge set. The center port line will be used
later for both the HFC-410A and nitrogen
containers.

1

2

3

4

5

6

7

8

9

10

11 12

1/6 TURN

3

CONNECT GAUGE SET

4

EVACUATE THE SYSTEM

NOTE 

— Remove cores from service valves (if not already done).

Possible equipment damage.

Avoid deep vacuum operation. Do not use
compressors to evacuate a system.
Extremely low vacuum can cause internal
arcing and compressor failure. Damage
caused by deep vacuum operation will
void warranty.

WARNING !

EVACUATION

S

Close manifold gauge valves.

S

Shut off HFC-410A cylinder.

S

Reinstall service valve cores by removing manifold hose from service valve. Quickly
install cores with core tool while maintaining a positive system pressure.

S

Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6)
of a turn as illustrated.

OUTDOOR

UNIT

TO VAPOR

SERVICE VALVE

TO LIQUID LINE
SERVICE VALVE

MICRON

GAUGE

VACUUM PUMP

1/4 SAE TEE WITH SWIVEL
COUPLER

500

MANIFOLD

GAUGE SET

HFC-410A

RECOMMEND

MINIMUM 3/8” HOSE

HIGH

LOW

NITROGEN

A

B

C

D

FIGURE 12

Содержание Merit 13ACX-018-230

Страница 1: ... Units AIR CONDITIONER 506945 01 5 2013 Supersedes 7 2012 WARNING Improper installation adjustment alteration service or maintenance can cause personal injury loss of life or damage to property Installation and service must be performed by a licensed professional installer or equivalent or a service agency CAUTION Before attempting to perform any service or maintenance turn the electrical power to...

Страница 2: ...ICE Roof Damage This system contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to degrade Failure to follow this notice could result in damage to roof surface IMPORTANT This model is designed for use in check expansion valve systems only An indoor expansion valve ap proved for use with HFC 410A refrigerant must be or dered separately and installed prio...

Страница 3: ...THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WOOD BLOCK BETWEEN STUDS STRAP WOOD BLOCK STRAP SL...

Страница 4: ...t that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are ready to make connections IMPORTANT Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pres sure goes below 20 psig A hissing sound will be heard when the compressor is running unloaded Protector will reset when low press...

Страница 5: ... Teflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT V...

Страница 6: ...nts and debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service ports 1 2 ANGLE TYPE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVICE PORT CAP CUT AND DEBUR LINE SET SIZE MATCHES SERVICE VALVE CONNECTION COPPER TUBE STUB SERVICE VALVE CONNECTION REFRIGERANT LINE DO NOT CRIMP SER...

Страница 7: ...ed cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to ...

Страница 8: ...6 7 8 9 10 11 12 1 2 Turn SENSING BULB INSTALLATION EQUALIZER LINE INSTALLATION 1 2 3 4 5 6 7 8 9 10 11 12 1 8 Turn A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below B Remove the field provided fitting that temporarily reconnected the liquid line to the indoor unit s distributo...

Страница 9: ... indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After leak testing disconnect gauges from service ports After the line set has been connected to the indoor and outdoor units check the line set connections and indoor unit for leaks Use the following procedure to test for leaks A C...

Страница 10: ...utting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following A Connect low ...

Страница 11: ... damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the unit s electroniccontrols Precautionswill help to avoid control exposure to electrostatic dischargebyputtingthe unit the control and the technician at the same electrostatic potential To...

Страница 12: ...binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and suction line service valve stems to release the refrigerant charge contained in outdoor unit into the system 4 Replace the stem caps and tighten to the value listed in table 3 5 Check voltage supply at the disconnect switch The voltage must be within the range list...

Страница 13: ...nsion 3 16 for liquid line valve sizes and 5 16 for vapor line valve sizes to back the stem out counterclockwise as far as it will go Operating Ball Type Service Valve 1 Remove stem cap with an appropriately sized wrench 2 Use an appropriately sized wrenched to open To open valve rotate stem counterclockwise 90 To close rotate stem clockwise 90 1 2 3 4 5 6 7 8 9 10 11 12 1 12 TURN To Access Servic...

Страница 14: ...nged exposure of the unit to treated water i e sprinkler systems soak ers waste water etc will corrode the surface of steel and aluminum parts diminish performance and af fect longevity of the unit Routine Maintenance In order to ensure peak performance your system must be properly maintained Clogged filters and blocked airflow prevent your unit from operating at its most efficient level NOTE The ...

Страница 15: ...ure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temperatures Subcooling A B SUBCOOLING Saturated Condensing Temperature A minus Liquid Line Temperature B Approach A B APPROACH Liquid Line Temperature A minus Outdoor Air Temperature B Indoor C...

Отзывы: