background image

15

Torr).

4. 

Break the vacuum by allowing nitrogen into the port 

connections (liquid and gas line pipes) until a positive 

pressure is achieved 

5. 

Evacuate  the  system  to  a  minimum  reading  of  500 

Microns (0.5 Torr).

6.  For a moisture-free system, ensure the vacuum is held 

without movement for a minimum of 4 hours.

7.  If vacuum fails to hold, carry out steps 2 through 6 until 

vacuum holds.

Wiring Connections

WARNING

Electric Shock Hazard. Can cause injury or death. Unit 

must be rounded in accordance with national and local 

codes.
Line voltage is present at all components when unit is 

not in operation. Disconnect all remote electric power 

supplies before opening access panel. Unit may have 

multiple power sources.

CAUTION

All terminal connections must be made as illustrated 

in the following diagrams. Improperly connected wiring 

could damage unit or cause communication errors 

between indoor and outdoor units.

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the 

current Canadian Electrical Code (CEC). 

Outdoor Unit 

•  Refer to unit nameplate for minimum circuit ampacity 

and maximum over-current protection size

•  Make all electrical power wiring connections at the out-

door unit

• 

Be sure to reattach all electrical box covers after con

-

nections are complete

Indoor Unit

•  All indoor units are powered by the outdoor unit.
• 

Communication Wiring (Indoor Units 30K and Below): 

Use one stranded 4-conductor wire to provide power 

and communication

•  Communication Wiring (Indoor Units 36K and Above): 

Use one stranded 3-conductor wire to provide power 

and one stranded 2-conductor wire to provide commu-

nication

•  Use minimum of 18 GA stranded wiring
•  When installing a condensate pump, wire in-line with 

the CN5 float switch

IMPORTANT

This unit must be properly grounded and protected by a 

circuit breaker. The ground wire for the unit must not be 

connected to a gas or water pipe, a lightning conductor 

or a telephone ground wire. 
Do not connect power wires to the outdoor unit until 

all other wiring and piping connections have been 

completed.
Do not install the unit near a lighting appliance that 

includes a ballast. The ballast may affect remote control 

operation.

IMPORTANT

Install unit so that unit disconnect is accessible.

Use  specified  wiring  and  cable  to  make  electrical 

connections. Clamp cables securely and make sure that 

connections are tight to avoid strain on wiring. Insecure 

wiring connections may result in equipment failure and 

risk of fire. 

Wiring must be installed so that all cover plates can be 

securely closed.

Содержание MCFA024S4-*P

Страница 1: ...g jurisdiction should be consulted before installation The MCFA and MCFB Ceiling Floor indoor units are matched with an outdoor heat pump unit to create a mini split system that uses HFC 410A refriger...

Страница 2: ...door unit will include the following items 1 Assembled Outdoor Unit and the following items Parts Figure Quantity Parts Figure Quantity Drain connector 1 Seal ring 1 Indoor Outdoor Unit Match Ups Outd...

Страница 3: ...1 phase 60hz Nominal Cooling Capacity 018 1 5 tons 024 2 tons 036 3 tons 048 4 tons Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M CF A 018 S 4 1 P Unit Type CF...

Страница 4: ...frigerant lines individually to prevent sweating UV rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable fiel...

Страница 5: ...es 40 1 4 25 53 3 4 15 3 8 16 mm 1023 635 1365 391 406 MPB018S4S P inches 36 21 1 4 27 5 8 14 1 4 13 3 4 mm 914 540 702 363 350 MPB024S4S P MPB036S4S P inches 40 1 2 26 1 2 31 7 8 16 1 8 15 7 8 mm 103...

Страница 6: ...P 50 5 8 1286 47 3 8 1203 MCFA048S4S P 65 1651 61 3 4 1568 MCFB018S4S P 42 1 8 1070 39 991 Figure 3 MCFA and MCFB Indoor Unit Dimensions Inches mm System Clearances Outdoor Unit 24 610 Air Outlet Air...

Страница 7: ...ervice valve stems are factory torqued from 9 ft lbs 12 N for small valves to 25 ft lbs 34 N for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at le...

Страница 8: ...on page 7 for minimum clearances Place the MCFA or MCFB on a wall which is both ca pable of supporting the unit s weight and which is con structed to enable the unit to fit flush on the wall An uneven...

Страница 9: ...own onto the brackets This will ensure that the unit remains level Indoor Unit Condensate Piping Connections IMPORTANT Make sure that drain piping is properly routed and insulated to prevent both leak...

Страница 10: ...intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation do not place anything...

Страница 11: ...amples are When prevailing winds are from the air inlet side then position the wind barrier a minimum of 12 inches 305 mm from the unit as illustrated in Figure 18 Wind Barrier When prevailing wind is...

Страница 12: ...rface to avoid ice build up around the unit Place the unit above a load bearing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof...

Страница 13: ...ch this system contains While it may have some miscibility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil 7 Align...

Страница 14: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cy...

Страница 15: ...size Make all electrical power wiring connections at the out door unit Be sure to reattach all electrical box covers after con nections are complete Indoor Unit All indoor units are powered by the out...

Страница 16: ...208 230V Indoor Unit Outdoor Unit Indoor Unit Figure 27 Single Zone Wiring 30K and Below From Power Supply Indoor Unit CommunicationTerminal Block L1 L2 Power Terminal Block 208 230V Outdoor Unit L1 L...

Страница 17: ...Output Remote Control Ceiling Floor Type CN21 M 5 5 VSWING INACTIVE CN24 M 5 SWING FAN FOR MODE CONFLICT SETTING DISPLAY BOARD 10 CN10A TO WIRED CONTROLLER 2 CN40 TO PRO GRA MMABL E WIR ED CON TRO LLE...

Страница 18: ...and regular wired controller use the same wiring connector Figure 31 MCFA036S4 P Unit Wiring Diagram CN5 Inductor CN8 CN18 CN7 T2B OUTER PIPE TEMP SENSOR T2 T1 CN6 4 BLACK WHITE RED RED VSWING INACTI...

Страница 19: ...OR TEMP SENSOR POW ER SUPPLY H PRO SV L PFC INDUCTOR COMPRESSOR DISCHARGE TEMP SENSOR RED BLACK V U CN19 CN51 CN55 W EXV BLACK DRIVER BOARD RED 7 7 YELLOW BLUE P 1 FM1 OUTDOOR DC FAN CN53 CN20 CN34 CN...

Страница 20: ...N17 CN39 CN18 HEAT_D HEAT_Y SV 4 WAY BLUE BLUE RED BLUE CN4 CN2 CN3 CN1 COMP U V W Y G DCFAN2 DCFAN1 5 5 CN6 CN5 CN8 CN15 CN9 CN14 7 5 CN6 CN3 L YELLOW YELLOW U V W BLUE BLACK RED Y G CN39 WHITE BLACK...

Страница 21: ...OARD C ODE PAR T NAME C OMP R E S S OR D HE AT1 C T1 AC CURRENT DETECTOR 4 WAY VALVE C OMP E XV E LE C TR IC E XPANS ION VALVE H P R O L P R O LOW P R E S S UR E S WIT CH HIG H P R E S S UR E S WIT CH...

Страница 22: ...RED BLACK V U CN19 CN51 CN55 W EEV BLACK DRIVER BOARD RED YELLOW BLUE P 1 FM1 OUTDOOR DC FAN FAN MOTOR CAPACITOR CN53 CN20 CN3 CN4 CN10 CN40 CN22 CN44 CN8 CN9 CN7 CN2 CN1 CN5 CN54 CN52 CN33 5 6 CN6 SV...

Страница 23: ...e Length feet meters Amount of Refrigerant to add 18 25 7 5 0 161 oz ft 15g m 24 25 7 5 0 322 oz ft 30g m 36 25 7 5 0 322 oz ft 30g m 48 25 7 5 0 322 oz ft 30g m Troubleshooting Table 7 Troubleshootin...

Страница 24: ...crements NOTE The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over shoot the temperature setting by 6 10 F 3 5 C depending on the room size or...

Отзывы: