background image

13

Refrigerant Piping Connections

Field piping consists of two copper lines connecting the 

outdoor unit to the indoor unit. “Table 2. Refrigerant Piping 

and Indoor Unit Connection Sizes” lists the connection 

sizes. The connections are made using the provided brass 

flare nuts at the end of the refrigerant piping connections. 

Both lines must be individually insulated.

1.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or water from getting into the 

refrigerant piping before it is connected.

2. 

CAREFULLY adjust refrigerant piping connections to 

suit the application.

3. 

Slowly  loosen  one  of  the  flare  nuts  to  release  the 

factory nitrogen charge from the indoor units only.

4. 

Remove  the  flare  nuts  from  the  connections  on  the 

unit and discard the seal from each of the piping 

connections.

5. 

Slide the flare nuts onto the ends of the field-provided 

refrigerant piping before using a suitable flaring tool to 

flare the end of the copper pipe.

6.  Apply recommended HFC-410A refrigerant lubricant 

to the outside of the flared refrigerant lines. 

IMPORTANT

The  compressor  in  this  unit  contains  PVE 

oil  (Polyvinylether).  PVE  oil  is  formulated  for 

 

hydro-fluorocarbon  (HFC)  refrigerants,  such  as  HFC-

410A, which this system contains. While it may have 

some miscibility properties with mineral-based oil and 

POE oil (Polyolester), it is not recommended to mix PVE 

oil with any other type of refrigerant oil.

7.  Align the threaded connections with the 

flared  refrigerant  lines.  Tighten  the  flare  nuts 

lightly  at  first  to  obtain  a  smooth  match  as 

illustrated in “Figure 25. Making Connections 

 

(Male to Female Connection)”.

8. 

Once  snug,  continue  another  half-turn  on  each  nut 

which should create a leak-free joint. A torque wrench 

may be used to tighten flare nuts using “Table 3. Flare 

Nut Torque Recommendations”. 

Do not over-tighten 

a  flared  joint.  Flared  connections  should  always 

be accessible and must be insulated to prevent 

condensation.

9.  After refrigerant piping has been installed and checked 

for leaks, apply insulation over all flared connections.

Table 2.  Refrigerant Piping and Indoor Unit 

Connection Sizes

Size 

(Btuh)

Liquid Line 

in.

Gas Line 

in.

18000

1/4

1/2

24000, 36000 & 

48000

3/8

5/8

A

B

CANT ON THE OUTSIDE OF

THE FLARE

MALE FLARE

CONNECTION

Figure 25. Making Connections  

(Male to Female Connection)

TORQUE WRENCH

TO INDOOR

UNIT

TO OUTDOOR UNIT

BACKUP

WRENCH

Figure 26. Tighten Flare Nut

Table 3.  Flare Nut Torque Recommendations

Outside 

Diameter

Recommended 

Torque

No torque wrench available 

Finger tighten and use an 

appropriately sized wrench to 

turn an additional:

Inches

1/4

15 ft.-lb. (20 N)

1/4 turn

3/8

26 ft.-lb. (35 N)

1/2 turn

1/2

41 ft.-lb. (56 N)

7/8 turn

5/8

48 ft.-lb. (65 N)

1 full turn

Содержание MCFA024S4-*P

Страница 1: ...g jurisdiction should be consulted before installation The MCFA and MCFB Ceiling Floor indoor units are matched with an outdoor heat pump unit to create a mini split system that uses HFC 410A refriger...

Страница 2: ...door unit will include the following items 1 Assembled Outdoor Unit and the following items Parts Figure Quantity Parts Figure Quantity Drain connector 1 Seal ring 1 Indoor Outdoor Unit Match Ups Outd...

Страница 3: ...1 phase 60hz Nominal Cooling Capacity 018 1 5 tons 024 2 tons 036 3 tons 048 4 tons Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M CF A 018 S 4 1 P Unit Type CF...

Страница 4: ...frigerant lines individually to prevent sweating UV rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable fiel...

Страница 5: ...es 40 1 4 25 53 3 4 15 3 8 16 mm 1023 635 1365 391 406 MPB018S4S P inches 36 21 1 4 27 5 8 14 1 4 13 3 4 mm 914 540 702 363 350 MPB024S4S P MPB036S4S P inches 40 1 2 26 1 2 31 7 8 16 1 8 15 7 8 mm 103...

Страница 6: ...P 50 5 8 1286 47 3 8 1203 MCFA048S4S P 65 1651 61 3 4 1568 MCFB018S4S P 42 1 8 1070 39 991 Figure 3 MCFA and MCFB Indoor Unit Dimensions Inches mm System Clearances Outdoor Unit 24 610 Air Outlet Air...

Страница 7: ...ervice valve stems are factory torqued from 9 ft lbs 12 N for small valves to 25 ft lbs 34 N for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at le...

Страница 8: ...on page 7 for minimum clearances Place the MCFA or MCFB on a wall which is both ca pable of supporting the unit s weight and which is con structed to enable the unit to fit flush on the wall An uneven...

Страница 9: ...own onto the brackets This will ensure that the unit remains level Indoor Unit Condensate Piping Connections IMPORTANT Make sure that drain piping is properly routed and insulated to prevent both leak...

Страница 10: ...intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation do not place anything...

Страница 11: ...amples are When prevailing winds are from the air inlet side then position the wind barrier a minimum of 12 inches 305 mm from the unit as illustrated in Figure 18 Wind Barrier When prevailing wind is...

Страница 12: ...rface to avoid ice build up around the unit Place the unit above a load bearing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof...

Страница 13: ...ch this system contains While it may have some miscibility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil 7 Align...

Страница 14: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cy...

Страница 15: ...size Make all electrical power wiring connections at the out door unit Be sure to reattach all electrical box covers after con nections are complete Indoor Unit All indoor units are powered by the out...

Страница 16: ...208 230V Indoor Unit Outdoor Unit Indoor Unit Figure 27 Single Zone Wiring 30K and Below From Power Supply Indoor Unit CommunicationTerminal Block L1 L2 Power Terminal Block 208 230V Outdoor Unit L1 L...

Страница 17: ...Output Remote Control Ceiling Floor Type CN21 M 5 5 VSWING INACTIVE CN24 M 5 SWING FAN FOR MODE CONFLICT SETTING DISPLAY BOARD 10 CN10A TO WIRED CONTROLLER 2 CN40 TO PRO GRA MMABL E WIR ED CON TRO LLE...

Страница 18: ...and regular wired controller use the same wiring connector Figure 31 MCFA036S4 P Unit Wiring Diagram CN5 Inductor CN8 CN18 CN7 T2B OUTER PIPE TEMP SENSOR T2 T1 CN6 4 BLACK WHITE RED RED VSWING INACTI...

Страница 19: ...OR TEMP SENSOR POW ER SUPPLY H PRO SV L PFC INDUCTOR COMPRESSOR DISCHARGE TEMP SENSOR RED BLACK V U CN19 CN51 CN55 W EXV BLACK DRIVER BOARD RED 7 7 YELLOW BLUE P 1 FM1 OUTDOOR DC FAN CN53 CN20 CN34 CN...

Страница 20: ...N17 CN39 CN18 HEAT_D HEAT_Y SV 4 WAY BLUE BLUE RED BLUE CN4 CN2 CN3 CN1 COMP U V W Y G DCFAN2 DCFAN1 5 5 CN6 CN5 CN8 CN15 CN9 CN14 7 5 CN6 CN3 L YELLOW YELLOW U V W BLUE BLACK RED Y G CN39 WHITE BLACK...

Страница 21: ...OARD C ODE PAR T NAME C OMP R E S S OR D HE AT1 C T1 AC CURRENT DETECTOR 4 WAY VALVE C OMP E XV E LE C TR IC E XPANS ION VALVE H P R O L P R O LOW P R E S S UR E S WIT CH HIG H P R E S S UR E S WIT CH...

Страница 22: ...RED BLACK V U CN19 CN51 CN55 W EEV BLACK DRIVER BOARD RED YELLOW BLUE P 1 FM1 OUTDOOR DC FAN FAN MOTOR CAPACITOR CN53 CN20 CN3 CN4 CN10 CN40 CN22 CN44 CN8 CN9 CN7 CN2 CN1 CN5 CN54 CN52 CN33 5 6 CN6 SV...

Страница 23: ...e Length feet meters Amount of Refrigerant to add 18 25 7 5 0 161 oz ft 15g m 24 25 7 5 0 322 oz ft 30g m 36 25 7 5 0 322 oz ft 30g m 48 25 7 5 0 322 oz ft 30g m Troubleshooting Table 7 Troubleshootin...

Страница 24: ...crements NOTE The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over shoot the temperature setting by 6 10 F 3 5 C depending on the room size or...

Отзывы: