background image

INSTALLATION

INSTRUCTIONS

©

2017 Lennox Industries Inc. 

Dallas, Texas, USA

THIS MANUAL MUST BE LEFT WITH THE OWNER 

FOR FUTURE REFERENCE

WARNING

Improper installation, adjustment, alteration, ser vice or 

maintenance can cause property damage, personal 

injury or loss of life.
Installation and service must be performed by a li censed 

professional HVAC installer (or equivalent) or a service 

agency.

WARNING

The clean Air Act of 1990 bans the intentional venting of 

refrigerant (CFCs, HCFCs, and HFCs) as of July, 1992. 

Approved methods of recovery, recycling or reclaiming 

must be followed. Fines and/or incarceration may be 

levied for non-compliance.

WARNING

This product contains a chemical known to the State 

of California to cause cancer, birth defects, or other 

reproductive harm.

CAUTION

As with any mechanical equipment, contact with sharp 

sheet metal edges can result in personal injury. Take 

care while handling this equipment and wear gloves and 

protective clothing.

General

Refer to the Product Specifications bulletin (EHB) for more 

product information.
These instructions are intended as a general guide and 

do not supersede local or national codes in any way. 

Authorities having jurisdiction should be consulted before 

installation.

The  MCFA  and  MCFB  Ceiling/Floor  indoor  units  are 

matched with an outdoor heat pump unit to create a mini-

split system that uses HFC-410A refrigerant.

MLA/MPA/MPB and  

MCFA/MCFB Series

SINGLE-ZONE MINI-SPLIT SYSTEMS 

 

(208/230V) --  

Ceiling / Floor  Indoor Units 

507548-06 

4/2017 

Supersedes 10/2016

Table of Contents

General ...........................................................................1

Included Parts.................................................................2

Indoor / Outdoor Unit Match-Ups

....................................2

Model Number Identification

 ...........................................3

Typical Single-Zone System Components

......................4

System Dimensions  .......................................................5

Outdoor Units ..............................................................5

Indoor Units .................................................................6

System Clearances ........................................................6

Outdoor Unit ................................................................6

Indoor Unit ...................................................................7

Torque Requirements for Caps and Fasteners...............7

Indoor Unit Installation ....................................................7

Unit Placement Considerations ...................................7

Floor Installation ..........................................................8

Ceiling Installation .......................................................8

Indoor Unit Condensate Piping Connections ...............9

Outdoor Unit Installation

 ...............................................10

Placement Considerations .........................................10

Direct Sunlight, Rain, Snow and Ice Protection .........10

Prevailing Winds ........................................................11

Buried Refrigerant Pipe Protection ............................12

Outdoor Unit Condensate Piping ...............................12

Securing the Outdoor Unit .........................................12

Refrigerant Piping Connections ....................................13

Leak Test and Evacuation

 ............................................14

Leak Test ...................................................................14

Triple Evacuation Procedure......................................14

Wiring Connections ......................................................15

Outdoor Unit  .............................................................15

Indoor Unit .................................................................15

Unit Start-Up .................................................................23

Adding Refrigerant for Longer Line Set ........................23

Troubleshooting ............................................................23

Test Run .......................................................................23

Pre-Checks ................................................................23

Procedure ..................................................................23

Dry Mode Operation (Dehumidification)

 .......................24

Procedure ..................................................................24

Sequence of Operation ..............................................24

Содержание MCFA024S4-*P

Страница 1: ...g jurisdiction should be consulted before installation The MCFA and MCFB Ceiling Floor indoor units are matched with an outdoor heat pump unit to create a mini split system that uses HFC 410A refriger...

Страница 2: ...door unit will include the following items 1 Assembled Outdoor Unit and the following items Parts Figure Quantity Parts Figure Quantity Drain connector 1 Seal ring 1 Indoor Outdoor Unit Match Ups Outd...

Страница 3: ...1 phase 60hz Nominal Cooling Capacity 018 1 5 tons 024 2 tons 036 3 tons 048 4 tons Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M CF A 018 S 4 1 P Unit Type CF...

Страница 4: ...frigerant lines individually to prevent sweating UV rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable fiel...

Страница 5: ...es 40 1 4 25 53 3 4 15 3 8 16 mm 1023 635 1365 391 406 MPB018S4S P inches 36 21 1 4 27 5 8 14 1 4 13 3 4 mm 914 540 702 363 350 MPB024S4S P MPB036S4S P inches 40 1 2 26 1 2 31 7 8 16 1 8 15 7 8 mm 103...

Страница 6: ...P 50 5 8 1286 47 3 8 1203 MCFA048S4S P 65 1651 61 3 4 1568 MCFB018S4S P 42 1 8 1070 39 991 Figure 3 MCFA and MCFB Indoor Unit Dimensions Inches mm System Clearances Outdoor Unit 24 610 Air Outlet Air...

Страница 7: ...ervice valve stems are factory torqued from 9 ft lbs 12 N for small valves to 25 ft lbs 34 N for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at le...

Страница 8: ...on page 7 for minimum clearances Place the MCFA or MCFB on a wall which is both ca pable of supporting the unit s weight and which is con structed to enable the unit to fit flush on the wall An uneven...

Страница 9: ...own onto the brackets This will ensure that the unit remains level Indoor Unit Condensate Piping Connections IMPORTANT Make sure that drain piping is properly routed and insulated to prevent both leak...

Страница 10: ...intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation do not place anything...

Страница 11: ...amples are When prevailing winds are from the air inlet side then position the wind barrier a minimum of 12 inches 305 mm from the unit as illustrated in Figure 18 Wind Barrier When prevailing wind is...

Страница 12: ...rface to avoid ice build up around the unit Place the unit above a load bearing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof...

Страница 13: ...ch this system contains While it may have some miscibility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil 7 Align...

Страница 14: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cy...

Страница 15: ...size Make all electrical power wiring connections at the out door unit Be sure to reattach all electrical box covers after con nections are complete Indoor Unit All indoor units are powered by the out...

Страница 16: ...208 230V Indoor Unit Outdoor Unit Indoor Unit Figure 27 Single Zone Wiring 30K and Below From Power Supply Indoor Unit CommunicationTerminal Block L1 L2 Power Terminal Block 208 230V Outdoor Unit L1 L...

Страница 17: ...Output Remote Control Ceiling Floor Type CN21 M 5 5 VSWING INACTIVE CN24 M 5 SWING FAN FOR MODE CONFLICT SETTING DISPLAY BOARD 10 CN10A TO WIRED CONTROLLER 2 CN40 TO PRO GRA MMABL E WIR ED CON TRO LLE...

Страница 18: ...and regular wired controller use the same wiring connector Figure 31 MCFA036S4 P Unit Wiring Diagram CN5 Inductor CN8 CN18 CN7 T2B OUTER PIPE TEMP SENSOR T2 T1 CN6 4 BLACK WHITE RED RED VSWING INACTI...

Страница 19: ...OR TEMP SENSOR POW ER SUPPLY H PRO SV L PFC INDUCTOR COMPRESSOR DISCHARGE TEMP SENSOR RED BLACK V U CN19 CN51 CN55 W EXV BLACK DRIVER BOARD RED 7 7 YELLOW BLUE P 1 FM1 OUTDOOR DC FAN CN53 CN20 CN34 CN...

Страница 20: ...N17 CN39 CN18 HEAT_D HEAT_Y SV 4 WAY BLUE BLUE RED BLUE CN4 CN2 CN3 CN1 COMP U V W Y G DCFAN2 DCFAN1 5 5 CN6 CN5 CN8 CN15 CN9 CN14 7 5 CN6 CN3 L YELLOW YELLOW U V W BLUE BLACK RED Y G CN39 WHITE BLACK...

Страница 21: ...OARD C ODE PAR T NAME C OMP R E S S OR D HE AT1 C T1 AC CURRENT DETECTOR 4 WAY VALVE C OMP E XV E LE C TR IC E XPANS ION VALVE H P R O L P R O LOW P R E S S UR E S WIT CH HIG H P R E S S UR E S WIT CH...

Страница 22: ...RED BLACK V U CN19 CN51 CN55 W EEV BLACK DRIVER BOARD RED YELLOW BLUE P 1 FM1 OUTDOOR DC FAN FAN MOTOR CAPACITOR CN53 CN20 CN3 CN4 CN10 CN40 CN22 CN44 CN8 CN9 CN7 CN2 CN1 CN5 CN54 CN52 CN33 5 6 CN6 SV...

Страница 23: ...e Length feet meters Amount of Refrigerant to add 18 25 7 5 0 161 oz ft 15g m 24 25 7 5 0 322 oz ft 30g m 36 25 7 5 0 322 oz ft 30g m 48 25 7 5 0 322 oz ft 30g m Troubleshooting Table 7 Troubleshootin...

Страница 24: ...crements NOTE The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over shoot the temperature setting by 6 10 F 3 5 C depending on the room size or...

Отзывы: