28
Troubleshooting
Table 7. Troubleshooting Codes
Code Description
E0
Indoor unit EEPROM error
E1
Communication error between indoor unit and outdoor unit
E3
Indoor fan speed error
E4
Indoor return air temperature sensor error
E5
Indoor coil temperature sensor error
EC
Low refrigerant
EE
High water level alarm
F0
Outdoor current overload sensed
F1
Outdoor ambient temperature sensor error
F2
Outdoor coil temperature sensor error
F3
Compressor discharge temperature sensor error
F4
Outdoor unit EEPROM error
F5
Outdoor unit fan speed error
P0
Inverter module IPM error
P1
High or low voltage protection
P3
Outdoor unit low temperature lockout
P4
Compressor drive error
--
Mode conflict
P6
Compressor high-pressure or low-pressure switch open
Test Run
Pre-Checks
Only perform test run after you have completed the
following steps:
•
Electrical Safety Checks – Confirm that the unit’s
electrical system is safe and operating properly
•
Refrigerant Leak Checks – Check all flare nut connec
-
tions and confirm that the system is not leaking
•
Confirm that gas and liquid valves are fully open
Procedure
You should perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to
turn it on.
3. Press the mode button to scroll through the following
functions, one at a time:
• COOL - Select lowest possible temperature
• HEAT - Select highest possible temperature
4. Let each function run for 5 minutes, and perform the
following checks:
Table 8. Test Run Checklist
Checks
Pass
Fail
No electrical leakage
Unit is properly grounded
All electrical terminals
properly covered
Indoor and outdoor units are
solidly installed
All pipe connection points do
not leak
Water drains properly from
drain hose
All piping is properly
insulated
Unit performs COOL function
properly
Unit performs HEAT function
properly
Indoor unit louvers rotate
properly
Indoor unit responds to
remote controller
Dry Mode Operation (Dehumidification)
Procedure
1. Using the provided wireless remote control, press the
MODE
button and select
DRY
mode.
2. Press the
UP/ DOWN
button to select the desired
temperature. The temperature setting range is from
62°F (17°C) to 86°F (30°C) in one degree increments.
NOTE:
The blower is preset at a low speed and cannot be
changed therefore it will get cold and most likely
will over shoot the temperature setting by 6-10
°
F
(3-5
°
C) depending on the room size or other
various factors. Also the
Follow Me
mode does
not operate in this mode.
NOTE:
In addition, the indoor units do not have a humidistat
installed therefore they are unable to determine
humidity levels. This product is not recommend as
a main source for dehumidification.
Sequence of Operation
When in dry mode operation the unit is actually in cooling
mode with a low speed blower operation. Set remote temp
to a lower room temp to begin the dry mode operation.
The compressor will stop when the room temperature is
4°F (2°C) lower than the temperature setting.
However there is a temperature compensation for cooling
mode that is two degrees Celsius. So the unit will stop
when the temperature is 8°F (4°C) lower than the room
temperature settings.