background image

12

PHILLIPS

SCREWDRIVER

d

CASSETTE BASE

HOOK

PANEL

HANGER

REFRIGERANT

PIPING CONNECTIONS

CONDENSATE

DRAIN

CONNECTION

COVER PANEL

SECURING

SCREW

COVER PANEL

LOUVER SWING

MOTORS

DETAIL A

DETAIL B

DETAIL C

Figure 10. Install Cover Panel

4.  Position the ceiling panel so that the arrow on the 

panel is aligned with the arrow sticker on the cassette 

base (both arrow stickers should be on the same side 

of the cassette base). 

NOTE: 

If the panel and the base are not properly aligned, 

the airflow will be blocked and the harness plugs 

from the panel to the cassette base will not be long 

enough to plug together.

5.  Place the cover panel hangers on the two corners with 

the louver swing motors. Place these two hangers 

on the corresponding hooks on the corners of the 

cassette base. See detail A in “Figure 10. Install Cover 

Panel”. Then, place the other hangers from the other 

two corners over their corresponding hooks on the 

cassette  base  as  shown  in  detail  B  in  “Figure  10. 

Install Cover Panel”.

6.  Connect the six-pin harness plugs from each of the 

two swing motors to the matching six-pin plugs from 

the control box in the cassette base.

7.  Connect the black harness from the display on the 

cover panel to the corresponding black plug from the 

control box in the cassette base.

8.  Connect the black two-pin plug from the temperature 

sensor to the corresponding black plug from the 

control box in the cassette base.

9.  Tighten the provided screws in the bracket in the cover 

panel immediately below each panel hanger. See 

detail C in “Figure 10. Install Cover Panel”.  Adjust the 

cover panel by turning slightly clockwise, if necessary, 

to make sure that the panel is properly aligned with the 

cassette base.

≥7/8 (22 mm)

5-3/4 (146)

⅜”

THREADED

ROD

CASSETTE

UNIT 

BASE

COVER

 

PANEL

CEILING

LEVELING

NUT

air ou

t

5/32-1/4 (4-6 mm)

CASSETTE BAS

E

CEILING

FOAM

INSULATION

COVER

 

PANEL

SUPPL

Y AI

R

LOUVER

FOAM

INSULATION

Side View Cutaway

1-7/8 (48 mm)

Figure 11. Cover Panel in Place

11. Continue to tighten the cover panel securing screws 

until the insulation between the cover panel and the 

cassette base has been compressed to approximately 

¼” (6 mm). The cover panel must form a seal with 

the ceiling and the cassette base around the entire 

perimeter of the unit. 

CORNER PANEL

LOOSEN UPPER NUT

TIGHTEN LOWER NUT

Figure 12. Adjust Unit Height through Corner Panel

12. If it is necessary to adjust the cassette height after the 

cover panel has been installed, access the leveling nut 

through the removable access cover on each corner.

13. The return air grille must be reinstalled on the cover 

panel. Align the four tabs on the grille with the four 

slots in the cover panel. Tilt the panel back into place. 

Press the opposite side of the cover gently until the 

latches engage.

Содержание M22A009S4-1P

Страница 1: ...supersede local or national codes in any way Authorities having jurisdiction should be consulted before installation The M22A M33A and M33B ceiling cassette indoor units are matched with an outdoor h...

Страница 2: ...Parts Figure Quantity Parts Figure Quantity M0STAT60Q 1 Wireless controller 1 Installation and owner s manual 1 ea Wireless control holder with 2 mounting screws 1 Paper template for installation 1 B...

Страница 3: ...024 2 tons 036 3 tons 048 4 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision 2 2nd Revision M P A 009 S 4 S 1 P Series Type M Mini Split OUTDOOR HEAT PUMP UNITS Cooling Efficienc...

Страница 4: ...0V MPA036S4S P M33A036S4 P 208 230V MPA048S4S P M33A048S4 P 208 230V MPB009S4S P M22A009S4 P 208 230V MPB012S4S P M22A012S4 P 208 230V MPB018S4S P M22A018S4 P 208 230V MPB024S4S P M33A024S4 P 208 230V...

Страница 5: ...RTANT The refrigerant metering device for this system is located in the outdoor unit This makes it necessary to insulate the refrigerant lines individually to prevent sweating 1 2 3 L1 L2 UV rated tap...

Страница 6: ...3 635 1365 391 406 MPB009S4S P inches 33 1 8 19 1 8 21 7 8 11 7 8 11 3 4 mm 842 486 556 302 298 MPB012S4S P inches 34 1 4 20 1 4 21 7 8 13 1 8 13 3 8 mm 870 514 556 333 340 MPB018S4S P inches 36 21 1...

Страница 7: ...2 572 21 1 2 546 20 5 8 524 22 1 2 572 10 3 8 264 23 5 8 600 Ceiling Opening INSTALLATION HANGERS LEVELING ADJUSTMENT NUT 4 CEILING DIFFUSER PANEL AIR OUTLET AIR OUTLET AIR INLET SIDE VIEW BOTTOM VIEW...

Страница 8: ...781 A 33 1 8 841 33 1 8 841 SIDE VIEW 37 3 8 949 37 3 8 949 BOTTOM VIEW Panel DIFFUSER PANEL AIR OUTLET AIR OUTLET AIR INLET LEFT SIDE VIEW Fresh Air Intake NOTE Not Used Size A in mm 024 8 1 8 206 03...

Страница 9: ...r Unit Clearances inches mm Indoor Unit 23 5 8 600 Ceiling Opening INSTALLATION HANGERS LEVELING ADJUSTMENT NUT 4 CEILING DIFFUSER PANEL AIR OUTLET AIR OUTLET AIR INLET 36 914 mm 36 914 mm 36 914 mm 3...

Страница 10: ...curity system or intercom Electrical interference and radio frequencies from any of these sources may affect op eration Be sure to instruct customers how to properly operate the unit especially mainte...

Страница 11: ...sher from failing off Position the nuts slightly above the final resting place of the four suspension brackets ANGLE IRON BOLTED IN PLACE ACROSS WOODEN JOISTS WOODEN JOIST THREADED ROD ANGLE IRON ACRO...

Страница 12: ...e 8 Connect the black two pin plug from the temperature sensor to the corresponding black plug from the control box in the cassette base 9 Tighten the provided screws in the bracket in the cover panel...

Страница 13: ...uld be approved corrosion resistant pipe You must confirm operation of every drain and pump in the system as part of the commissioning procedure Drain Plug Drain Pan Cassette Base Pour water here for...

Страница 14: ...F 50 C to protect the electronics If the outdoor unit is placed in direct sunlight it is possible that the limit may activate and shut down the unit Place unit away from overhanging roof lines which...

Страница 15: ...ed in Alcove 12 305mm Min Distance Wind Barrier Inlet Air Prevailing Winter Winds from Air Inlet Side Discharge Air Wind Barrier Prevailing Winter Winds From Air Discharge Side 79 2007mm Min Distance...

Страница 16: ...face to avoid exposure to refrigerant and oil during service and installation Failure to follow this notice could result in damage to roof surface Securing Outdoor Unit to Slab Frame or Rails If the o...

Страница 17: ...POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil 7 Align the threaded connections with the flared refrigerant lines Tighten the flare nuts lightly at fi...

Страница 18: ...rrent rises Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and out...

Страница 19: ...ause communication errors between indoor and outdoor units In the U S A wiring must conform with current local codes and the current National Electric Code NEC In Canada wiring must conform with curre...

Страница 20: ...0 A M PU MP 2 INDOOR UNIT MAINBOARD TO WIRED CONTROLLER 5 CN23 ON OFF Remote Control CN3 3 ALA RM Alarm Output CN1 5 M Motor 5 R E D B R O W N CN1 B L U E B L A C K CN5 WATER LEVEL SWITCH E Y X To LVM...

Страница 21: ...jumper for remote on off control TO PROGRAMMABLE WIRED CONTROLLER 2 CN40 4 Note The programmable wired controller and regular wired controller use the same wiring connector 2 COMPONENT IN DASH LINE I...

Страница 22: ...UTDOOR MAIN PCB BLUE BLACK RED CN13 CN12 L OUT CN18 4 WAY VALVE CN414 BLUE BLUE U V W Y G CN6 1 Y G RED BLUE 3 CN14 CN15 CRANKCASE HEATER Figure 34 208 230V MPA018S4S P Outdoor Unit Wiring Diagram COM...

Страница 23: ...P Outdoor Unit Wiring Diagram CODE PART NAME COMPRESSOR D CT1 AC CURRENT DETECTOR 4 WAY VALVE COMP DCFAN1 DCFAN2 H PRO L PRO LOW PRESSURE SWITCH HIGH PRESSURE SWITCH T3 T4 OUTDOOR COIL TEMP SENSOR OU...

Страница 24: ...COMPRESSOR Y G CN 50 3 U V W BLUE RED BLACK EXV OUTDOOR MAIN PCB OUTDOOR TE MP S E NS OR COMPR E S S OR DIS CHAR GE TE MP S E NS OR OUTDOOR C OIL TEMP SENSOR RED BLACK WHTIE T5 T4 T3 Figure 38 208 23...

Страница 25: ...SCHARGE TEMP ERA TURE SENS OR RED BLA CK V U C N 19 CN51 C N 55 W EXV BLACK DRIVER BOARD RED 7 7 YELLOW BLUE P 1 FM1 OUTDOOR DC FAN CN53 CN20 CN34 CN3 CN4 CN10 CN40 CN22 CN44 C N 8 C N 9 C N 7 C N 2 C...

Страница 26: ...CN20 CN24 CN25 CN17 FAN1 CN18 HEAT1 HEAT2 SV 4 WAY VALVE BLUE RED BLUE CN4 CN2 CN3 CN1 CO MP U V W Y G CN6 CN9 10 3 CN1 CN2 L YELLOW YELLOW U V W BLUE BLACK RED RED WIHTE BLACK RED BLACK CH1 CT1 FM2...

Страница 27: ...alves and while system is still under a vacuum 4 Open the liquid and gas line service valves to release the refrigerant charge contained in outdoor unit into the system 5 Replace the stem caps and tig...

Страница 28: ...checks Table 8 Test Run Checklist Checks Pass Fail No electrical leakage Unit is properly grounded All electrical terminals properly covered Indoor and outdoor units are solidly installed All pipe con...

Отзывы: