9
Technical Information
Service Manual
2.4 Cooling and Heating Data Sheet in Rated Frequency
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 7.5 m.
Cooling:
Heating:
Rated cooling
condition(
℃
) (DB/WB)
Model
Pressure of gas pipe
connecting indoor
and outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed
of indoor
unit
Fan speed
of outdoor
unit
Compressor
revolution (rps)
Indoor
Outdoor
P (MPa)
T1 (
℃
)
T2 (
℃
)
27/19
35/24
LNINVE052/LNINVC052
0.9~1.1
in:8~9
out:10~12
in:75~85
out:37~43
Super High
High
68
27/19
35/24
LNINVE063/LNINVC063
0.9~1.1
in:7~9
out:10~12
in:75~85
out:37~43
Super High
High
73
27/19
35/24
LNINVE070/LNINVC070
0.9~1.1
in:8~9
out:10~12
in:75~85
out:37~43
Super High
High
52
27/19
35/24
LNINVE080/LNINVC080
0.9~1.1
in:7~9
out:10~12
in:75~85
out:37~43
Super High
High
58
Rated cooling
condition(
℃
) (DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed
of indoor
unit
Fan speed
of outdoor
unit
Compressor
revolution (rps)
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
20/15
7/6
LNINVE052/LNINVC052
2.2~2.4
in:75~85
out:37~43
in:1~3
out:2~5
Super High
High
72
20/15
7/6
LNINVE063/LNINVC063
2.2~2.4
in:75~85
out:37~43
in:1~3
out:2~5
Super High
High
77
20/15
7/6
LNINVE070/LNINVC070
2.2~2.4
in:75~85
out:37~43
in:1~3
out:2~5
Super High
High
56
20/15
7/6
LNINVE080/LNINVC080
2.2~2.4
in:75~85
out:37~43
in:1~3
out:2~5
Super High
High
89
Содержание LNINVC052
Страница 88: ...85 Installation and Maintenance Service Manual Models LNINVC070 LNINVC080...
Страница 117: ...JF00301922...