Factory Unit Controller Settings
Use the Unit Controller to adjust parameters; menu paths
are shown in each table. Refer to the Unit Controller
manual provided with each unit.
Tables 29 through 40 show factory settings (in degrees, %
of fan CFM, etc.). Record adjusted settings on the label
located inside the compressor access panel.
When field installing optional kits and accessories, the
Unit Controller must be configured to identify the option
before it will function. Refer to figures 39 and 40 to
determine whether the Unit Controller configuration I.D.
must change. To configure the option, use MAIN MENU >
SETUP > INSTALL menu path. Press SAVE until
CONFIGURATION ID 1 or 2 appears depending on the
option installed. Change the appropriate character in the
configuration I.D. For example, when an economizer is
installed using a single enthalpy sensor, change
configuration I.D. 1, the second character, to “S”.
TABLE 29
580730
Units With BACnet Module Settings
Use menu SETUP > NETWORK INTEGRATION. Set “BACNET”
and network address.
BACNET MAC ADDRESS:
TABLE 30
580732
Units With Room Sensor, CPC/LSE Gateway Settings
Use menu SETUP > NETWORK INTEGRATION. Set “L CONNEC
TION” and network address.
LCONN ADDRESS:
TABLE 31
580735
Units with BACnet Module (Target) Settings
Use menu SETUP > NETWORK INTEGRATION. Set “BACNET”
and network address.
BACNET MAC ADDRESS:
Para
meter
Fact
ory
Setting
Setting
Description
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
91
120
Sets the compressor minimum run
time to 2 minutes.
106
99
Set reheat SP from connected sensor
to 99% to basically disable. Reheat
will be controlled over by BAS. Only
applies to units with the reheat option.
111
3
Thermostat with three cooling stages.
117
0
DCV max. open damper. 0=controlled
by network.
153
60
Time delay between heating and cool
ing mode.