iComfort S30 Thermostat - Installer Zoning 

Control Settings

Zoning Control Parameters

After completing the installation of the iHarmony Zoning 

system. Power up the system. From the HD display, use the 

following procedure to customize the zoning configuration.

1. 

From the Home screen, press the Menu icon in the 

upper right-hand corner of the screen.

2. 

Press 

settings

.

3. 

Press 

iHarmony zoning 

to rename each zone. Either 

pre-defined or custom names can be used.

4. 

The first line is zoning. Options are ON and OFF. By 

default zoning is ON.

5. 

Select the specific zone to rename. Use the enter zone 

name field to rename the zone. Repeat to procedures 

to rename any other zones if desired. 

6. 

Once renaming zones is completed, press 

advanced

 

settings

.

7. 

Press view 

dealer control center

.

8. 

A  warning  message  will  appear  indicating  “intended 

for use by qualified Lennox equipment installers only“. 

Press proceed to continue.

9. 

 Press 

equipment

.

10. 

Press 

Zoning Control 

and  modified  any  of  the 

available parameters for zoning control.

Table 10. Zoning Control Parameters

Parameter

Description

About

This  provides  information  on  unit  code, 

language  supported,  equipment  type 

name,  control  software  revision,  control 

model number, control serial number, con

-

trol  hardware  revision,  protocol  revision 

number,  device  product  level,  24VAC  av

-

erage  power  consumption,  24VAC  peak 

power  consumption,  compatible  devices 

list,  application  code  memory  size,  mi

-

cro-controller part number, max number of 

zones,  supported  damper  types,  number 

of damper positions, zone temp sensor 1, 

zone temp sensor 2, zone temp sensor 3 

and zone temp sensor 4.

Equipment Name

A unique name can be assigned to this 

component. Name can be up to 29 charac

-

ters. Name can consist of letters, numbers, 

special characters and spaces.

Zones 1 through 

4 Temp Reading 

Calibration

Allows adjustment to temperature reading 

displayed on zone thermostat.

Reset Zoning 

Control

Any installer modifications under the zon

-

ing control tab will be reset back to the 

factory defaults if the reset zoning control 

option is used.

Zoning System Parameters
1. 

From the 

dealer control center

, press 

equipment

.

2. 

Press 

smart hub

.

3. 

Located  and  modified  any  setting  related  to  zoning.  

See below for list of parameters available for 

modification.

Table 11. Smart Hub Parameters

Parameter

Description

About

This screen provides information concerning lan-

guage  supported,  equipment  type  name,  control 

software  revision,  model,  control  mode  number, 

control  serial  number,  control  hardware  revision, 

protocol  revision  number,  device  product  level, 

24VAC average power consumption, 24VAC peak 

power consumption, compatible devices list, appli

-

cation code memory size and micro-controller part 

number.

Equipment 

Name

A unique name can be assigned to this compo-

nent. Name can be up to 29 characters. Name can 

consist of letters, numbers, special characters and 

spaces. Default name is subnet controller.

HP Heating 

Lockout 

Time

The HP could not get a zone to progress 0.5 de

-

grees towards the set point in 120 minutes (Alert 

Code 40 - Minor alert). System will switch to sec-

ondary heat source. (Electric heat or furnace in 

dual fuel applications). Transition back to Heat 

Pump normal operation when termination setting 

times out.
Range is 60 to 240 minutes. Default is 120 min-

utes. Adjustments are in increments of 30 min-

utes.

Zone 1 

through 4 

Continuous 

Blower 

CFM

Minimum and maximum CFM will be dependent 

on  system  component  configurations. These  pa

-

rameter values are automatically adjusted to the 

specific  hardware  configuration.  See  iHarmony 

zoning system installation instruction for minimum 

CFMs for specific indoor units.
Zones  requesting  the  fan  ON  are  only  allowed 

while no other zone demand is present. The ther-

mostat will sum all the zone continuous blower 

CFM requirements and send the command only 

after positioning the dampers and waiting for the 

damper close delay period to expire (30 seconds) 

Continuous blower demands are the lowest prior-

ity  demands,  all  other  conditioning  demands  will 

over-ride the continuous blower demand.

Range is 5 CFM to maximum of indoor unit. De

-

fault is dependent on tonnage of indoor unit. Ad-

justments are in increments of 5 CFM .

Zone 1 

through 

4 Cooling 

CFM

Minimum and maximum CFM will be dependent 

on  system  component  configurations. These  pa

-

rameter values are automatically adjusted to the 

specific  hardware  configuration.  See  iHarmony 

zoning system installation instruction for minimum 

CFMs for specific indoor units.
Target cooling CFM for a specific zone. Range is 5 

CFM to maximum of indoor unit. Default is depen-

dent on tonnage of indoor unit. Adjustments are in 

increments of 5 CFM.

Содержание iHarmony 10C16

Страница 1: ... zones maximum supported Lennox communicating variable speed indoor unit and communicating or non communicating conventional two stage outdoor unit four zones maximum supported Table of Contents Shipping and Packing List 1 General 1 Required Items Sold Separately 2 Recommended Items Sold Separately 2 Zoning Components 2 Transformer Phasing 2 Dampers 3 Discharge Air Temperature Sensor DATS 3 DATS T...

Страница 2: ...see recommendations in following table The damper control module and three in zone thermostats require a total of 6VA to operate Table 1 Zone Damper Transformer Selection Chart Catalog Number Size Description VA LOAD 10P17 40VA 120 208 240VAC 24VAC Damper VA x number of dampers 6VA damper control module 3 in zone thermostats damper transformer VA requirement 10P87 50VA 12P61 75VA 83P74 Electrical ...

Страница 3: ...charge Air Temperature Sensor DATS The included discharge air temperature sensor 88K38 monitors the supply air Figure 4 Discharge Air Temperature Sensor Installation Typical Up Flow Furnace shows the discharge air temperature sensor This electronic sensor s probe is inserted into the discharge air plenum see Figure 3 Discharge Air Temperature Sensor Installation DATS to gather air temperature data...

Страница 4: ...ing pressure switch valve tee adapter catalog number 87071 Other conditions Pressure switch status is used only for the heat pump heating and does not have any affect on non zone demands Heat pump will stop after the pressure switch status remains open for 60 seconds CAUTION High Pressure Switch must be installed on open side of tee first to prevent refrigerant loss Pressure switch 27W13 should be...

Страница 5: ... the suction manifold see Figure 6 Typical Freezestat Installation Indoor Coil of the indoor coil 2 The freezestat senses the line temperature and cycles the compressor off when the line temperature fails below its setpoint The freezestat will open and close as listed in Table 4 Available Freezestats 3 Connect freezestat wires to the freezestat terminals on the damper control module after removing...

Страница 6: ...nnect zone damper 24VAC transformer wires to terminals DMPR R and XFMR C see figure 8 Factory default is DMPR XFMR G SENSE Connect the IAQ device requiring blower operation to the indoor unit control G terminal as illustrated in the wiring diagrams located in the applicable iComfort Series Thermostat Installer Guide Place a wire jumper between the indoor unit G and damper control module G sense te...

Страница 7: ...amper Transformer R C JUMPER MUST BE SET TO 1 4 THE SETTING FOR 5 8 IS FOR FUTURE USE NC NO C DAMPER RSBUS COMM LED GREEN STATUS LED GREEN PS LED RED CNTRL LED RED ZONING OFF DMPR1 LED RED DMPR2 LED RED DMPR3 LED RED DMPR4 LED RED 3 3 AMP FUSE IN ZONE THERMOSTAT COMM LED GREEN NOTE 1 FREEZESTAT TERMINAL WILL HAVE FACTORY INSTALLED INSERTION BRIDGE DO NOT REMOVE UNLESS CONNECTING A FREEZESTAT 93G35...

Страница 8: ...ge the value 4 Press save F Change other red settings if present using a similar process After completing the settings press the back button to continue On the system devices screen continue by pressing the next button Table 7 Adjustable Parameters for Zoning System Parameter Name Default Min Max Incr Parameter Description Zone 2 through 4 Temp Reading Calibration 0ºF 5ºF 5ºF 1ºF Recalibrating the...

Страница 9: ...e delivered not the design CFM Table 8 Air Flow System Devices System Parameter Names Edit and Test Airflow Screen Parameter Names Zones 1 4 Continuous Blower CFM Blower Circulation Airflow Zones 1 4 Cooling CFM Cooling Airflow Zones 1 4 Heating CFM Heating Airflow 1 Select the desired radio button option Blower Circulation Airflow Cooling Airflow or Heating Airflow A 2 Adjust airflow for a specif...

Страница 10: ...of parameters available for modification Table 11 Smart Hub Parameters Parameter Description About This screen provides information concerning lan guage supported equipment type name control software revision model control mode number control serial number control hardware revision protocol revision number device product level 24VAC average power consumption 24VAC peak power consumption compatible...

Страница 11: ... F 4 44 15 56 C Default is 45 F 7 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for HP Heating In heat pump heating mode this setting sets the target discharge air temperature Range is 85 to 110 F 29 44 to 43 33 C Default is 90 F 32 22 C Adjustments are in increments of 1 F 0 56 C Zoning Target Supply Air Temp for Gas Electric Heating Default is 110 F Range is 100 ...

Страница 12: ...t When the Emergency Heat setting is OFF the heat pump is used to satisfy heating demands Humidity Control Refer to Lennox communicating thermostat installation and setup guide for more information on humidity control settings and operating modes Note there is no capability to control humidity humidification or dehumidification per individual zone Various humidity control modes would be applicable...

Страница 13: ... 380 SLP98xx090V60C 1HP motor 450 SLP98xx110V60C 1HP motor 450 SLP98UH135V60D 1HP motor 450 SL280xxV 3 ton 250 SL280xxV 4 5 ton 450 EL296xxV 2 3 ton 250 EL296xxV 4 ton 380 EL296xxV 5 ton 450 CBX32MV 018 024 250 CBX32MV 024 030 Rev 06 250 CBX32MV 036 Rev 06 250 CBX32MV 048 060 068 Rev 06 450 CBX40UHV 024 030 250 CBX40UHV 036 380 CBX40UHV 042 048 060 450 A 3 duty cycle corresponds to the minimum CFM...

Страница 14: ...ically clears when the system detects the issue no longer exists 115 Critical Low Secondary 24VAC Voltage 24VAC power to a system component control is lower than the required range of 18 to 30VAC Check and correct voltage Check for additional power robbing system components devices connected to system This alert code may require the installation of an additional or larger VA transformer Damper con...

Страница 15: ...fully NOTE If this issue occurred on an iHarmony zoning system the field will need to manually activate the zoning 310 Moderate Discharge Air Temp Sensor Problem There is a discharge air temperature sensor issue Compare discharge temperature sensor DATS resistance to temperature resistance charts in system component installation instruction Replace discharge air sensor if necessary NOTE Confirm th...