background image

Page 18

Heating  Operation  and  Adjustments

A−Heating  Sequence  of  Operation

  1− When  the  thermostat  calls  for  heat,  the  combustion

air  blower  starts  immediately.

  2− The  combustion  air  switch  checks  for  proper  blower

operation  before  allowing  power  to  the  ignition

controller.  This  switch  is  factory  set  and  no

adjustment  is  necessary.

  3− After  a  pre−purge  of  45  seconds,  the  spark  ignitor  is

energized,  and  the  solenoid  valve  opens  in  the  gas

valve.

  4− The  spark  then  ignites  the  gas,  the  ignition  sensor

proves  the  flame  and  the  combustion  process

continues.

  5− In  the  event  that  the  flame  is  not  detected  after  the

first  trial  for  ignition,  the  controller  will  repeat  steps  3

and  4  up  to  two  more  times  (depending  upon

controller  model)  before  locking  out.

  6− For  troubleshooting  purposes,  an  ignition  attempt

after  lock  out  may  be  re−established  manually.  Move

thermostat  HOFF"  and  return  thermostat  switch  to

HHEAT"  position.

B−Limit  Control

Limit  controls  are  factory  set  and  not  adjustable.

Two  primary  limits  are  located  on  the  division  panel

between  the  return  and  supply  sections  on  high  heat

units.  One  primary  limit  is  located  on  the  division  panel  on

standard  heat  units.

A  secondary  limit  is  located  on  the  blower  transition  in

both  standard  and  high  heat  units.

C−Heating  Adjustment

  1− Main  burners  are  factory  adjusted  for  proper  flame.

Air  shutters  are  provided  for  localized  areas  if
necessary.

  2− Burner  flames  may  be  observed  through  the

inspection  port  in  the  access  panel.  Always  operate
the  unit  with  the  access  panel  in  place.

 

WARNING

Danger  of  explosion.  Can  cause  injury  or
death.  Do  not  overtighten  main  burner
mounting  screws.  Snug  tighten  only.

  3− The  gap  on  the  flame  sensing  electrode  should  be

between  3/32"  and  5/32"  (0.094  −  0.156  mm).
Remove  right  burner  by  removing  screw  and  sliding
the  burner  off  the  orifice.  The  carry  over  slot  on  all
burners  is  1/8"  (.125  mm)  and  it  must  be  maintained.
Clean  the  carry  over  slot  using  a  strip  of  16  gauge
steel.  Check  gap  with  1/8"  (.125mm)  twist  drill.
Replace  all  burners  using  mounting  screws.

  4− Gas  manifold  pressure  should  be  set  at  3.5"  w.c.  for

natural  gas  units  and  10.5"  w.c.  for  LP  gas  units.

Units  must  be  derated  when  installed  at  altitudes
above  4500  feet  (610  m)  above  sea  level.  At
altitudes  above  4500  feet  (610  m),  units  must  be
derated  to  match  the  gas  manifold  pressures
shown  in  table  16.

NOTE0This  is  the  only  permissible  derate  for  these  units.

TABLE  16

Altitude − ft (m)

Gas  Manifold  Pressure−in.  w.g.  (kPa)

Altitude  −  ft.  (m)

Natural

LP  (Propane)

4501−5500  (1372−1676)

3.4  (0.85)

10.2  (2.54)

5501−6500  (1676−1981)

3.3  (0.82)

9.8  (2.44)

6501−7500  (1981−2286)

3.2  (0.80)

9.5  (2.36)

Содержание Humiditrol L Series

Страница 1: ...5 TON 504 417M 8 2001 Supersedes 4 2001 L SERIES PACKAGED UNITS Table of Contents DIMENSIONS 1 PARTS ARRANGEMENTS 2 SHIPPING AND PACKING LIST 3 GENERAL 3 UNIT SUPPORT 3 DUCT CONNECTION 4 CONDENSATE D...

Страница 2: ...46 1 2 1181 EXHAUST AIR OUTDOOR AIR 15 381 END VIEW Economizer Outdoor Air Dampers CONDENSATE DRAIN EVAPORATOR COIL BLOWER 45 1143 5 1 8 130 24 3 4 629 FILTERS OPTIONAL OUTDOOR AIR HOOD Factory or Fi...

Страница 3: ...TRIC HEAT OPTIONAL CONDENSER FAN HEAT EXCHANGER COMPRESSOR EVAPORATOR COIL BLOWER TB1 COMBUSTION AIR INDUCER GAS VALVE BURNERS FILTERS DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFI OUTLET OPTIONAL...

Страница 4: ...rty damage Turn off gas and electrical power to unit before performing any maintenance or servicing operations on the unit Follow lighting instructions attached to unit when putting unit back into ope...

Страница 5: ...our sides of unit base Supports must be constructed of steel or suitably treated wood materials NOTE Securely fasten roof frame to roof per local codes Duct Connection All exterior ducts joints openin...

Страница 6: ...provided upstream of gas supply connection to the unit Install a ground joint union between the gas control manifold and the main manual shut off valve See figure 6 Compounds used on threaded joints o...

Страница 7: ...ve filters from unit and slide into filter channels If the filters have a metal frame remove the cardboard shipping pad protecting the evaporator coil B Intake Hood The intake hood top panel is secure...

Страница 8: ...rmostat where it might be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or units concealed pipes and chimneys B Control Wiring 1 Route t...

Страница 9: ...HERMOSTAT HAS NO NIGHT SETBACK TERMINALS 19 20 21 VOUT GND VIN A91 HUMIDITY SENSOR Connect shield drain to unit TB1 7 1 2 18 FIGURE 12 24 VOLT FIELD WIRING IN ZONE SENSOR MODE ECTO 6 01 OPTION 1 2 OR...

Страница 10: ...the static pressure and RPM readings to determine unit CFM 6 The CFM can be adjusted at the motor pulley see section C Blower Belt Adjustment C Blower Belt Adjustment Maximum life and wear can be obt...

Страница 11: ...85 1 20 0 90 1250 1 40 1 04 1800 850 630 0 50 0 37 730 0 55 0 41 820 0 65 0 48 905 0 75 0 56 985 0 85 0 63 1060 1 00 0 75 1130 1 10 0 82 1200 1 30 0 97 1265 1 45 1 08 1900 895 665 0 55 0 41 760 0 65 0...

Страница 12: ...1 01 1255 1 50 1 12 1900 899 565 0 35 0 26 665 0 45 0 34 755 0 55 0 41 840 0 65 0 48 920 0 80 0 60 995 0 90 0 67 1065 1 05 0 78 1135 1 25 0 93 1200 1 40 1 04 1265 1 60 1 19 2000 945 595 0 40 0 30 690...

Страница 13: ...21 0 12 31 0 12 30 0 04 10 1600 755 0 05 13 0 10 26 0 15 38 0 16 40 0 04 10 1800 850 0 06 16 0 12 31 0 18 46 0 21 52 0 05 12 2000 945 0 07 18 0 14 36 0 21 53 0 25 62 0 05 12 2200 1040 0 09 21 0 17 42...

Страница 14: ...ased on terminal velocities of 75 ft 22 9 m per minute TABLE 9 FD11 95 CEILING DIFFUSER AIR RESISTANCE Air Volume Effective Throw cfm L s ft m 2600 1225 19 24 6 7 2800 1320 20 28 6 9 3000 1415 21 29 6...

Страница 15: ...and blower rotation must match rotation marking If pressure differential is not observed or blower rotation is not correct 3 Disconnect all remote electrical power supplies 4 Reverse any two field in...

Страница 16: ...4_F 1 7 7_C 1 LGA LCA048H Humiditrol Units 16_F 1 9_C 1 LGA LCA060H Humiditrol Units 15_F 1 8 3_C 1 F Compressor Controls 1 High Pressure Switch S4 The compressor circuit is protected by a reset high...

Страница 17: ...off shut off the manual gas valve to the unit before shutting off electrical supply WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immedi...

Страница 18: ...gas valve counterclockwise to NON Do not force 36E Turn the knob 180 either way to HON 8 Close or replace the heat section access panel 9 Turn on all electrical power to appliance 10 Set thermostat to...

Страница 19: ...the blower transition in both standard and high heat units C Heating Adjustment 1 Main burners are factory adjusted for proper flame Air shutters are provided for localized areas if necessary 2 Burne...

Страница 20: ...orator coil is cooled and dehumidified the reheat coil adds heat to supply air See figure 19 for reheat refrigerant routing and figure 20 for standard cooling refrigerant routing REHEAT MODE REFRIGERA...

Страница 21: ...clean and free of obstructions and debris Read Relative Humidity At IMC Turn MODE DIP HTEMP switch 4 HON Display will alternately flash from readout to output A single push on the pushbutton will tog...

Страница 22: ...s initiated Compressor does not de energize L14 reheat valve is de energized for compressor cooling 3 Compressor reheat is in operation and outdoor air is suitable for free cooling then reheat demand...

Страница 23: ...el should be checked and cleaned prior to the heating season However it should be examined periodically during the heating season to establish an ideal cleaning schedule With power supply disconnected...

Страница 24: ...debris may become trapped between the slabs To clean between slabs carefully separate coil slabs and wash them thoroughly See figure 24 G Supply Air Blower Wheel Annually inspect supply air blower wh...

Отзывы: