Lennox HSXA15 SERIES Скачать руководство пользователя страница 11

Page 11

por line valve. Disconnect all power to the existing out-
door unit. Refer to gauges after shutdown to confirm
that the valves are not allowing refrigerant to flow back
into the low side of the system. Disconnect the liquid
and vapor lines from the existing outdoor unit.

 2 − Remove the existing outdoor unit. Set the new R410A

unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. 

DO NOT install provided R410A

check/expansion valve at this time. 

Make low voltage and line voltage connections to the
new outdoor unit. 

DO NOT turn on power to the unit

or open the outdoor unit service valves at this time.

 3 − Remove the existing refrigerant flow control orifice or

thermal expansion valve before continuing with flush-
ing procedures. The existing devices are not ap-
proved for use with R410A refrigerant and may pre-
vent proper flushing. Use a field−provided fitting to re-
connect the lines.

IMPORTANT

The line set and indoor coil must be flushed with at
least the same amount of clean refrigerant that pre-
viously charged the system. Check the charge in
the flushing cylinder before proceeding.

Flushing Connections

LOW

PRESSURE

HIGH

PRESSURE

VAPOR LINE

SERVICE VALVE

Existing

Indoor Coil

HSXA15 UNIT

GAUGE MANIFOLD

RECOVERY MACHINE

Inverted HCFC−22 Cylinder

(Contains clean HCFC−22 to be

used for flushing)

LIQUID LINE

SERVICE VALVE

INLET

DISCHARGE

TANK RETURN

CLOSED

OPENED

EXISTING VAPOR LINE

EXISTING LIQUID LINE

RECOVERY

CYLINDER

NOTE − The inverted HCFC−22
cylinder must contain at least
the same amount of refrigerant
as was recovered from the ex-
isting system.

Figure 10

Содержание HSXA15 SERIES

Страница 1: ...matched with an indoor coil as specified in Lennox Engineering Handbook Coils previously charged with HCFC 22 must be flushed INSTALLATION INSTRUCTIONS HSXA15 SERIES UNITS CONDENSING UNITS 504 668M 0...

Страница 2: ...SXA15 024 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 2 7 8 5 1 2 HSXA15 024 mm 708 657 759 311 570 367 562 73 140 HSXA15 030 HSXA15 036 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8...

Страница 3: ...t avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab plat forms or supports Refer to figure 2 for installation clear ances 36 914 mm 36 914 mm 36 914 mm 36 914...

Страница 4: ...CEC Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Страница 5: ...W Y G C Thermostat Indoor Unit Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is...

Страница 6: ...fty feet 15 m For applications longer than fifty feet consult the Lennox Refrig erant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Inst...

Страница 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Страница 10: ...ls used in this system absorb mois ture quickly Failure to install the filter drier will void the warranty Flushing Existing Line Set Indoor Coil IMPORTANT If this unit is being matched with an approv...

Страница 11: ...ice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap proved for use with R410A refrigerant and may pre vent proper flushing Use a field provided f...

Страница 12: ...or use with R410A refrigerant in the liquid line at the indoor coil Refrigerant Metering Devices Use HSXA15 units in TXV systems systems See the Len nox Engineering Handbook for approved TXV match ups...

Страница 13: ...ning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry ni...

Страница 14: ...he manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid deep vacuum operation Do not use com pressors to e...

Страница 15: ...he colder months The method of charging is deter mined by the unit s refrigerant metering device and the outdoor ambient temperature Measure the liquid line temperature and the outdoor ambi ent temper...

Страница 16: ...quid Line Temp Outdoor Ambient F C HSXA15 024 8 1 4 5 5 HSXA15 030 8 1 4 5 5 HSXA15 036 6 1 3 3 5 HSXA15 042 9 1 5 5 HSXA15 048 8 1 4 5 5 HSXA15 060 12 1 6 7 5 NOTE For best results the same electroni...

Страница 17: ...14 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0 57 161 0 88 266 0 119 412 2 1...

Страница 18: ...necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check condensate line and clean if necessary Indoor Unit 1 Clean or change filters 2 Adjust blower speed for cooling Measure t...

Отзывы: