background image

Page 18

Filter Drier

A filter drier is shipped with each HSXA15 unit. The filter dri-
er must be field installed in the liquid line between the liquid
line service valve and the expansion valve. 

This filter drier

must be installed to ensure a clean, moisture−free sys-
tem.

 A replacement filter drier is available as Lennox part

no. 37L5201.

Maintenance

 

WARNING

Electric shock hazard. Can cause inju-
ry or death. Before attempting to per-
form any service or maintenance, turn
the electrical power to unit OFF at dis-
connect switch(es). Unit may have
multiple power supplies.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:

 1 − Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

 2 − Condenser fan motor is prelubricated and sealed. No

further lubrication is needed.

 3 − Visually inspect connecting lines and coils for evidence

of oil leaks.

 4 − Check wiring for loose connections.

 5 − Check for correct voltage at unit (unit operating).

 6 − Check amp−draw condenser fan motor.

Unit nameplate _________ Actual ____________ .

NOTE − If owner complains of insufficient cooling, the
unit should be gauged and refrigerant charge
checked. Refer to section on refrigerant charging in
this instruction.

Indoor Coil

 1 − Clean coil, if necessary.

 2 − Check connecting lines and coils for evidence of oil

leaks.

 3 − Check condensate line and clean, if necessary.

Indoor Unit

 1 − Clean or change filters.

 2 − Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

 3 −

Belt Drive Blowers − 

Check belt for wear and proper

tension.

 4 − Check all wiring for loose connections

 5 − Check for correct voltage at unit (blower operating).

 6 − Check amp−draw on blower motor

Unit nameplate_________ Actual ____________.

Optional Accessories

Refer to the Engineering Handbook for optional accesso-
ries that may apply to this unit. The following may or may
not apply:

 

 

Loss of Charge Kit

 

 

High Pressure Switch Kit

 

 

Compressor Monitor

 

 

Compressor Crankcase Heater

 

 

Hail Guards

 

 

Mounting Bases

 

 

Timed Off Control

 

 

Stand−off Kit

 

 

Sound Cover

 

 

Low Ambient Kit

Start−Up & Performance Check List

Start−up and Performance Check List

Job Name

Job Location
Installer

Unit Model No.

Nameplate Voltage

Rated Load Ampacity

Maximum Fuse or Circuit Breaker

Refrigerant Lines:

Service Valves Fully Opened?

Outdoor Fan Checked?

Job No.

City

City

Serial No.

Date

State

State

Service Technician

Compressor

Outdoor Fan

Indoor Filter Clean?

Electrical Connections Tight?

Supply Voltage (Unit Off)

Vapor Pressure

Thermostat

Refrigerant Charge Checked?

Calibrated?

Properly Set?

Level?

Properly Insulated?

Voltage With Compressor Operating

Leak Checked?

Service Valve Caps Tight?

Indoor Blower RPM

Outdoor Coil Entering Air Temp.

Discharge Pressure

S.P. Drop Over Indoor (Dry)

Содержание HSXA15 SERIES

Страница 1: ...matched with an indoor coil as specified in Lennox Engineering Handbook Coils previously charged with HCFC 22 must be flushed INSTALLATION INSTRUCTIONS HSXA15 SERIES UNITS CONDENSING UNITS 504 668M 0...

Страница 2: ...SXA15 024 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 2 7 8 5 1 2 HSXA15 024 mm 708 657 759 311 570 367 562 73 140 HSXA15 030 HSXA15 036 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8...

Страница 3: ...t avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab plat forms or supports Refer to figure 2 for installation clear ances 36 914 mm 36 914 mm 36 914 mm 36 914...

Страница 4: ...CEC Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Страница 5: ...W Y G C Thermostat Indoor Unit Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is...

Страница 6: ...fty feet 15 m For applications longer than fifty feet consult the Lennox Refrig erant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Inst...

Страница 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Страница 10: ...ls used in this system absorb mois ture quickly Failure to install the filter drier will void the warranty Flushing Existing Line Set Indoor Coil IMPORTANT If this unit is being matched with an approv...

Страница 11: ...ice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap proved for use with R410A refrigerant and may pre vent proper flushing Use a field provided f...

Страница 12: ...or use with R410A refrigerant in the liquid line at the indoor coil Refrigerant Metering Devices Use HSXA15 units in TXV systems systems See the Len nox Engineering Handbook for approved TXV match ups...

Страница 13: ...ning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry ni...

Страница 14: ...he manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid deep vacuum operation Do not use com pressors to e...

Страница 15: ...he colder months The method of charging is deter mined by the unit s refrigerant metering device and the outdoor ambient temperature Measure the liquid line temperature and the outdoor ambi ent temper...

Страница 16: ...quid Line Temp Outdoor Ambient F C HSXA15 024 8 1 4 5 5 HSXA15 030 8 1 4 5 5 HSXA15 036 6 1 3 3 5 HSXA15 042 9 1 5 5 HSXA15 048 8 1 4 5 5 HSXA15 060 12 1 6 7 5 NOTE For best results the same electroni...

Страница 17: ...14 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0 57 161 0 88 266 0 119 412 2 1...

Страница 18: ...necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check condensate line and clean if necessary Indoor Unit 1 Clean or change filters 2 Adjust blower speed for cooling Measure t...

Отзывы: