HSXA15 Outdoor Unit

HSXA15 outdoor units use R410A which is an ozone friend-
ly HFC refrigerant. This unit must be installed with a match-
ing indoor coil and line set as outlined in the Lennox Engi-
neering Handbook. HSXA15 outdoor units are designed for
use in expansion valve systems only. They are not designed
to be used with other refrigerant flow control devices. An ex-
pansion valve and filter drier approved for use with R410A
have been shipped with the unit. These components must
be installed prior to unit operation.

 Failure to install the

provided filter drier will void the warranty.

Shipping & Packing List

 1 − Assembled HSXA15 outdoor unit
 1 − Filter/Drier (approved for use with R410A systems)
 1 − Expansion valve (approved for use with R410A)
 2 − Grommets (for liquid and suction lines)
 1 − Bushing (for low voltage wiring)

Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.

IMPORTANT

This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook. Coils
previously charged with HCFC−22 must be flushed.

INSTALLATION
INSTRUCTIONS

HSXA15 SERIES UNITS

CONDENSING UNITS

504,668M
02/04
Supersedes 12/02

Table of Contents

HSXA15 Outdoor Unit

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . 

Shipping & Packing List

1

. . . . . . . . . . . . . . . . . . . . . . . . . 

General Information

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Unit Dimensions

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Parts Arrangement

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Setting The Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Electrical

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Piping

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Flushing Existing Line Set & Indoor Coil

6

. . . . . . . . . . . 

Manifold Gauge Set

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Service Valves

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Leak Testing

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Evacuation

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Charging

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Maintenance

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Optional Accessories

13

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up & Performance Check List

13

. . . . . . . . . . . . . . 

Retain These Instructions

For Future Reference

General Information

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.

WARNING

This product and/or the indoor unit it is matched with
may contain fiberglass wool.

Disturbing the insulation during installation, mainte-
nance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiber-
glass wool is known to the State of California to
cause cancer.)

Fiberglass wool may also cause respiratory, skin,
and eye irritation.

To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.

Lennox Industries Inc.

P.O. Box 799900
Dallas, TX 75379−9900

Litho U.S.A.

Содержание HSXA15 SERIES

Страница 1: ...matched with an indoor coil as specified in Lennox Engineering Handbook Coils previously charged with HCFC 22 must be flushed INSTALLATION INSTRUCTIONS HSXA15 SERIES UNITS CONDENSING UNITS 504 668M 0...

Страница 2: ...SXA15 024 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 2 7 8 5 1 2 HSXA15 024 mm 708 657 759 311 570 367 562 73 140 HSXA15 030 HSXA15 036 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8...

Страница 3: ...t avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab plat forms or supports Refer to figure 2 for installation clear ances 36 914 mm 36 914 mm 36 914 mm 36 914...

Страница 4: ...CEC Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Страница 5: ...W Y G C Thermostat Indoor Unit Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is...

Страница 6: ...fty feet 15 m For applications longer than fifty feet consult the Lennox Refrig erant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Inst...

Страница 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Страница 10: ...ls used in this system absorb mois ture quickly Failure to install the filter drier will void the warranty Flushing Existing Line Set Indoor Coil IMPORTANT If this unit is being matched with an approv...

Страница 11: ...ice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap proved for use with R410A refrigerant and may pre vent proper flushing Use a field provided f...

Страница 12: ...or use with R410A refrigerant in the liquid line at the indoor coil Refrigerant Metering Devices Use HSXA15 units in TXV systems systems See the Len nox Engineering Handbook for approved TXV match ups...

Страница 13: ...ning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry ni...

Страница 14: ...he manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid deep vacuum operation Do not use com pressors to e...

Страница 15: ...he colder months The method of charging is deter mined by the unit s refrigerant metering device and the outdoor ambient temperature Measure the liquid line temperature and the outdoor ambi ent temper...

Страница 16: ...quid Line Temp Outdoor Ambient F C HSXA15 024 8 1 4 5 5 HSXA15 030 8 1 4 5 5 HSXA15 036 6 1 3 3 5 HSXA15 042 9 1 5 5 HSXA15 048 8 1 4 5 5 HSXA15 060 12 1 6 7 5 NOTE For best results the same electroni...

Страница 17: ...14 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0 57 161 0 88 266 0 119 412 2 1...

Страница 18: ...necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check condensate line and clean if necessary Indoor Unit 1 Clean or change filters 2 Adjust blower speed for cooling Measure t...

Отзывы: