FIGURE 3

Plumbing

If the HS40 unit is being installed with a new indoor coil and
line set, the plumbing connections should be made as out
lined in this section. If an existing line set and/or indoor coil is
going to be used to complete the HS40 system, refer to the
following section which includes flushing procedures.

Field refrigerant piping consists of liquid and suction lines
from the condensing unit  to the indoor evaporator coil . Use
Lennox L15 series line sets as shown in table 1 or use field−
fabricated refrigerant lines. Refer to Refrigerant Piping
Guide (Corp. 9351−L9) for proper size, type, and applica
tion of field−fabricated lines.

TABLE 1

REFRIGERANT LINE KITS

HS40 UNIT

LIQUID

LINE

SUCTION

LINE

L15 LINE

SETS

HS40−018
HS40−024

5/16 in.

(8 mm)

5/8 in.

(16 mm)

L15−21

15−50 ft.

(4.6 m − 15 m)

HS40−036

3/8 in.

(10 mm)

3/4 in.

(19 mm)

L15−41

15−50 ft.

(4.6 m − 15 m)

HS40−048

3/8 in.

(10 mm)

7/8 in.

(22 mm)

L15−65 

15−50 ft.

(4.6 m − 15 m)

HS40−065

3/8 in.

(10 mm)

1−1/8 in.

(29 mm)

Field

Fabricated

WARNING

Polyol ester (POE) oils used with R407C refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or ser
vice valve stub caps until you are ready to make
connections.

WARNING

Unit contains a NITROGEN holding charge. The hold
ing charge must be purged and the system must be
evacuated prior to charging with R407C.

Plumbing Connections

HS40 Matched with New Indoor Coil and Line Set

If an existing indoor coil which was equipped with an
RFCI metering device is being replaced, the liquid line
must also be replaced prior to the installation of the
HS40 unit.

If refrigerant lines are routed through a wall, seal and iso
late the opening so vibration is not transmitted to the build
ing.

NOTE − Line length should be no greater than 15.2 m. Se
lect line set diameters from table 1 to ensure oil return to the
compressor.

Brazing Connection Procedure

 1 − The end of the refrigerant line must be cut square and its

internal shape must remain round. The line must be free
of nicks or dents and must be deburred (I.D. and O.D.)

 2 − Before making line set connections, use dry nitrogen to

purge the refrigerant piping. This will help to prevent ox
idation and the introduction of moisture into the system.

 3 − Use silver alloy brazing rods (5 or 6 percent silver alloy

for copper−to−copper brazing or 45 percent silver alloy
for copper−to−brass or copper−to−steel brazing) which
are rated for use with R407C refrigerant. Wrap a wet
cloth around the valve body and the copper tube stub.

 4 − Quench the joint with water or a wet cloth to prevent

heat damage to the valve core and opening port.

IMPORTANT − The tube end must stay bottomed in the
fitting during final assembly to ensure proper seating,
sealing and rigidity.

 5 − Install the provided thermal expansion valve (ap

proved for use with R407C refrigerant) in the liquid line
at the indoor coil.

 6 − Install the provided filter drier (approved for use with

R407C refrigerant) in the liquid line as close as pos
sible to the expansion device. 

Do not leave the drier

uncapped for more than 10 to 15 minutes prior to
brazing, evacuation and leak testing.

 7 − Install the sight glass on the liquid line at the outdoor

unit. Wrap the sight glass with a wet rag to protect it
during installation.

Flushing Existing Line Set and Indoor Coil

IMPORTANT

If this unit is being matched with an approved line
set or indoor coil which was previously charged
with R22 refrigerant, or if it is being matched with
a coil which was manufactured before January of
1999, the coil and line set must be flushed prior to
installation. Take care to empty all existing traps.
Polyol ester (POE) oils are used in Lennox units
charged with R407C refrigerant. Residual mineral
oil can act as an insulator, preventing proper heat
transfer. It can also clog the thermal expansion
valve, reducing system performance and capacity.
Failure to properly flush the system per the instruc
tions below will void the warranty.

Содержание HS40 Series

Страница 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Страница 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Страница 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Страница 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Страница 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Страница 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Страница 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Страница 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Страница 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Страница 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Страница 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Страница 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Отзывы: