Checking Unit Charge Using Subcooling when
Outdoor Temperature is > 16°C

 1 − After  the  pressures  have  stabilized, attach the man

ifold gauge hose to the liquid service port, and record
the liquid pressure. At the same time, use a digital ther
mometer to record the liquid line temperature.

 2 − Use table 3 to determine the saturation temperature

that corresponds with the liquid line pressure reading.

 3 − To determine subcooling, subtract the liquid line tem

perature from the saturation temperature (table 3):

Saturation Temperature

−Liquid Line Temperature

=Subcooling

 4 − If the system is operating at subcooling values

 higher

than 4.4 − 5.5°C, recover refrigerant.

 5 − If the system is operating at subcooling values 

lower

than 4.4 − 5.5°C, add refrigerant through the suction
valve in the liquid state. 

Some R407C cylinders are

equipped with a dip tube which allows you to draw
liquid refrigerant from the bottom of the cylinder
without turning the cylinder upside−down. The
cylinder will be marked if it is equipped with a dip
tube.

System Operation

The condensing unit and the indoor blower cycle on de
mand from room thermostat. When the thermostat blower
switch is switched to the ON position, the indoor blower op
erates continuously.

TimedOff Control

Units include a timedoff control which helps equalize sys
tem pressures. The timedoff control delays compressor
startup for five minutes on thermostat demand. This allows
the compressor to start in an unloaded condition and pre
vents compressor shortcycling. The control is located in
the control box and is wired between thermostat terminal
Y" and the compressor contactor.

High Pressure and Low Pressure Switches

Units include a high pressure switch and a low pressure
switch. The pressure switches are located on valve cores
in the liquid line to allow for easy access. The manually re
set high pressure switch protects the system from high
pressure conditions which result from a fan failure or a
blocked or dirty coil. The low pressure switch (SPST, NO)
protects the system compressor from damage due to a
loss of charge. The loss of charge switch trips at 25 + 5
psig (172 + 34 kPa) and automatically resets at 55 + 5 psig
(379 + 34 kPa).

Refrigerant Sight Glass

A refrigerant sight glass is provided (in the bag assembly)
with the unit. The sight glass should be fieldinstalled in the
liquid line to monitor the system refrigerant.

Maintenance

WARNING

Electric shock hazard. Can cause inju
ry or death. Before attempting to per
form any service or maintenance, turn
the electrical power to unit OFF at dis
connect switch(es). Unit may have
multiple power supplies.

At the beginning of each cooling season, the system
should be checked as follows:

 1 − Clean  and  inspect  condenser  coil.  Coil  may  be

flushed with a water hose. Make sure power is off be
fore cleaning.

 2 − Visually inspect connecting lines and coils for evidence

of oil leaks.

 3 − Check wiring for loose connections.

 4 − Check for correct voltage at unit (unit operating).

 5 − Check condenser fan motor ampdraw.

Unit nameplate _________ Actual ____________ .

NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer to
section on refrigerant charging in this instruction.

Evaporator Coil

 1 − If necessary, clean coil.

 2 − Check connecting lines and coils for evidence of oil

leaks.

 3 − Check condensate line and clean, if necessary.

Indoor Unit

 1 − Clean or change filters.

 2 − Adjust blower speed for cooling. The pressure drop

over the coil should be measured to determine the cor
rect blower CFM. Refer to the unit information service
manual for pressure drop tables and procedure.

 3 − Belt Drive Blowers  Check belt for wear and proper

tension.

 4 − Check all wiring for loose connections

 5 − Check for correct voltage at unit (blower operating).

 6 − Check ampdraw on blower motor

Unit nameplate_________ Actual ____________.

Содержание HS40 Series

Страница 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Страница 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Страница 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Страница 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Страница 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Страница 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Страница 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Страница 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Страница 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Страница 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Страница 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Страница 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Отзывы: