SPECIFICATIONS (contd.)

Model No.

HS29-012

HS29-018

HS29-024

HS29-030

Net face area sq ft (m

2

)

Outer coil

7.56 (0.70)

11.33 (1.05)

11.33 (1.05)

13.22 (1.23)

Condenser

Net face area - sq. ft. (m

2

)

Inner coil

- - - -

- - - -

- - - -

- - - -

Condenser

Coil

Tube diameter  in. (mm) & no. of rows

5/16 (7.9)  1

5/16 (7.9)  1

5/16 (7.9)  1

5/16 (7.9)  1

Fins per inch (m)

22 (866)

22 (866)

22 (866)

18 (748)

Diameter  in. (mm) & no. of blades

18 (457)  3

18 (457)  3

18 (457)  3

18 (457)  3

C

d

Motor hp (W)

1/6 (124)

1/6 (124)

1/6 (124)

1/6 (124)

Condenser

Fan

Cfm (L/s)

2400 (1135)

2400 (1135)

2400 (1135)

2545 (1201)

Fan

Rpm

1105

1105

1105

1110

Watts

180

180

180

195

*Refrigerant charge furnished (HCFC-22)

3 lbs. 1 oz.

(1.38 kg)

3 lbs. 7 oz.

(1.55 kg)

3 lbs. 10 oz.

(1.64 kg)

4 lbs. 1 oz.

(1.83 kg)

Liquid line  in. (mm) o.d. connection (sweat)

3/8 (9.5)

3/8 (9.5)

3/8 (9.5)

3/8 (9.5)

Suction line  in. (mm) o.d. connection (sweat)

5/8 (15.9)

5/8 (15.9)

5/8 (15.9) −1, −2 units

3/4 (19) −3 units

3/4 (19.1)

Shipping weight  lbs. (kg) 1 package

146 (66)

146 (66)

148 (67)

140 (64)

*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines. 

    

3/8 x 5/16 in. (9.5 x 7.9 mm) adaptor furnished for liquid line connection.

SPECIFICATIONS (contd.)

Model No.

HS29-036

HS29-042

HS29-048

HS29-060

Net face area sq ft (m

2

)

Outer coil

15.11 (1.40)

15.11 (1.40)

15.11 (1.40)

15.11 (1.40)

Condenser

Net face area - sq. ft. (m

2

)

Inner coil

- - - -

5.40 (0.50)

5.40 (0.50)

14.40 (1.34)

Condenser

Coil

Tube diameter  in. (mm) & no. of rows

5/16 (7.9)  1

5/16 (7.9)  1.37

5/16 (7.9)  1.37

5/16 (7.9)  2

Fins per inch (m)

22 (866)

18 (748)

18 (748)

Diameter  in. (mm) & no. of blades

18 (457)  4

18 (457)  4

18 (457)  4

18 (457)  4

Condenser

Motor hp (W)

1/6 (124)

1/6 (124)

1/3 (249)

1/3 (249)

Condenser

Fan

Cfm (L/s)

2520 (1190)

2610 (1232)

3115 (1470)

3010 (1420)

Fan

Rpm

1100

1105

1125

1125

Watts

200

200

325

315

*Refrigerant charge furnished (HCFC-22)

1 ph−4 lbs. 6 oz. (1.98 kg)

3 ph−4 lbs 13 oz. (2.17 kg)

1 ph−5 lbs. 7 oz. (2.45 kg)

3 ph−5 lbs 6 oz. (2.43

1ph 5 lbs. 8 oz. (2.48 kg)

3ph 6 lbs 0 oz. (2.72)

1 ph 8 lbs. 0 oz. (3.62 kg)

3 ph 7 lbs 7 oz. (3.36)

Liquid line  in. (mm) o.d. connection (sweat)

3/8 (9.5)

3/8 (9.5)

3/8 (9.5)

3/8 (9.5)

Suction line  in. (mm) o.d. connection (sweat)

3/4 (19.1)

7/8 (22.2)

7/8 (22.2)

1-1/8 (28.6)

Shipping weight  lbs. (kg) 1 package

145 (66)

158 (72)

191 (87)

207 (94)

*Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines.

ELECTRICAL DATA

Model No.

HS29-141

HS29-211

HS29-261

HS29-311

HS29-411

HS29-413

Line voltage data  60 hz

208/230v

1ph

208/230v

1ph

208/230v

1ph

208/230v

1ph

208/230v

1ph

208/230v

3ph

460v

3ph

Rated load amps

4.9

8.6

10.1

11.8

17.5

10.3

4.3

Compressor

Power factor

.97

.97

.96

.92

.90

.83

.83

Locked rotor amps

26.3

48.3

60.0

69.4

96.0

75.0

40.0

Condenser Coil

Full load amps

1.1

1.1

1.1

1.1

1.1

1.1

0.55

Condenser Coil

Fan Motor

Locked rotor amps

1.9

1.9

1.9

1.9

1.9

1.9

1.0

Rec. maximum fuse or circuit breaker size (amps)

15

15

20

25

40

20

10

*Minimum circuit ampacity

7.3

11.0

13.8

15.9

23.8

14.0

6.5

*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.

Содержание HS29-012

Страница 1: ...ssure proper compressor lubrica tion at all times The heater is temperature actuated and operates only when required HS29 024 3 and HS29 030 through 060 units utilize a scroll compressor The scroll op...

Страница 2: ...iquid line connection SPECIFICATIONS contd Model No HS29 411 HS29 413 HS29 461 HS29 463 HS29 511 HS29 513 HS29 651 HS29 653 HS29 681 HS29 683 Net face area sq ft m2 Outer coil 15 11 1 40 15 11 1 40 15...

Страница 3: ...16 7 9 2 Fins per inch m 22 866 18 748 18 748 Diameter in mm no of blades 18 457 4 18 457 4 18 457 4 18 457 4 Condenser Motor hp W 1 6 124 1 6 124 1 3 249 1 3 249 Condenser Fan Cfm L s 2520 1190 2610...

Страница 4: ...ECTRICAL DATA Model No HS29 012 HS29 018 HS29 024 2 HS29 024 3 HS29 030 HS29 036 Line voltage data 60 hz 208 230v 1ph 208 230v 1ph 208 230v 1ph 208 230v 1ph 208 230v 1ph 208 230 v 1ph 208 230v 3ph 460...

Страница 5: ...r for ratings 3 Transformer T5 Transformer T5 is used on all J voltage units T5 is used as a step down transformer for the outdoor fan motor The trans former is located inside the unit control box see...

Страница 6: ...C1 HS29 THREE PHASE UNIT CONTROL BOX TRANSFORMER T5 J VOLT AGE UNITS ONLY GROUNDING LUG COMPRESSOR CONTACTOR K1 HS29 SINGLE PHASE UNIT CONTROL BOX WITH SCROLL COMPRESSOR FIGURE 2 DUAL CAPACITOR C12 CO...

Страница 7: ...s NOTE Compressor noise level may be significantly higher when phasing is incorrect and the unit will not provide cool ing when compressor is operating backwards Continued backward operation will caus...

Страница 8: ...15 21 35 35 11 5 16 7 9 5 8 15 9 HS29 261 L10 15 21 50 50 15 L15 31 20 20 6 HS29 311 L15 31 30 30 9 5 16 7 9 3 4 19 HS29 311 L15 31 40 40 12 5 16 7 9 3 4 19 L15 31 50 50 15 L10 15 41 20 20 6 HS29 410...

Страница 9: ...ce stem cap tighten firmly Tighten finger tight then tighten an additional 1 6 turn Do not attempt to backseat the service valves past the retaining ring Attempts to backseat the service valves past t...

Страница 10: ...E VALVE OPEN SCHRADER VALVE SERVICE PORT SERVICE PORT CAP INSERT HEX WRENCH HERE STEM CAP SCHRADER VALVE OPEN TO LINE SET WHEN VALVE IS CLOSED FRONT SEATED SERVICE PORT SERVICE PORT CAP RETAINING RING...

Страница 11: ...ze with nitrogen to 150 psig 4 Release nitrogen pressure from the system correct any leaks and recheck CAUTION When using dry nitrogen a pressure reducing regulator must be used to prevent excessive p...

Страница 12: ...correct temperature to be read 6 When unit is properly charged liquid line pressures should approximate those in table 6 TABLE 4 HS29 MODEL NO Approach Temperature Liquid Line Outdoor Ambient F C 141...

Страница 13: ...7 10 5 6 85 29 8 4 5 12 6 7 10 5 6 13 7 2 8 4 5 11 6 1 8 4 5 90 32 7 3 9 11 6 1 9 5 12 6 7 7 3 9 10 5 6 7 3 9 95 35 6 3 3 9 5 8 4 5 11 6 1 6 3 3 9 5 7 3 9 100 38 4 2 2 8 4 5 7 3 9 10 5 6 5 2 8 8 4 5...

Страница 14: ...246 72 257 71 261 74 253 75 249 74 249 80 105 40 6 TXV 254 84 269 82 271 279 76 80 276 74 296 72 291 75 291 76 286 75 285 82 These are typical pressures only Indoor evaporator match up indoor air quan...

Страница 15: ...VAC to the thermostat and outdoor unit controls COOLING 2Cooling demand initiates at Y1 in the thermostat 324VAC from indoor unit energizes compressor contactor K1 4K1 1 N O closes energizing terminal...

Страница 16: ...al C of compressor B1 and outdoor fan motor B4 5Outdoor fan motor B4 begins immediate operation 6Compressor B1 begins start up Hard start contactor K31 remains closed during start up and start capacit...

Страница 17: ...y be electromechanical or electronic NOTE Transformer in indoor unit supplies power 24 VAC to the thermostat and outdoor unit controls COOLING 2Cooling demand initiates at Y1 in the thermostat 324VAC...

Страница 18: ...it controls COOLING 2Cooling demand initiates at Y1 in the thermostat 324VAC from indoor unit energizes compressor contactor K1 4K1 1 N O closes energizing terminal C of compressor B1 and outdoor fan...

Страница 19: ...ssor contactor K1 4K1 1 N O closes energizing terminal C of compressor B1 and outdoor fan motor B4 5Outdoor fan motor B4 begins immediate operation 6Compressor B1 begins operation END OF COOLING DEMAN...

Страница 20: ...Page 20 SERVICE NOTES...

Отзывы: