background image

Page 7

To Access Service Port:

 1– Remove the stem cap. Use a service wrench

(part #18P66, 54B64 or 12P95) to make sure the ser-
vice valve is backseated.

CAUTION

The service port cap is used to seal the liquid line
service valve. Access to service port requires
backseating the service valve to isolate the
service port from the system. Failure to do so
will cause refrigerant leakage.

IMPORTANT

A schrader valve is not provided on the liquid line
service port. Valve must be backseated to turn off
pressure to service port.

 2– Remove service port cap and connect high pressure

gauge to service port.

 3– Using service wrench, open valve stem (one turn

clockwise) from backseated position.

 4– When finished using port, backseat stem with ser-

vice wrench. Tighten firmly.

 5– Replace service port and stem cap. Tighten finger

tight, then tighten an additional 1/6 turn.

To Close Off Service Port:

 1– Using service wrench, backseat valve.

 a – Turn stem counterclockwise.
 b – Tighten firmly.

To Open Liquid Line Service Valve:

 1– Remove the stem cap with an adjustable wrench.
 2– Using service wrench, backseat valve.

 a – Turn stem counterclockwise until backseated.
 b – Tighten firmly.

 3– Replace stem cap, finger tighten then tighten an

additional 1/6 turn.

To Close Liquid Line Service Valve:

 1– Remove the stem cap with an adjustable wrench.
  2– Turn the stem in clockwise with a service wrench to

front seat the valve. Tighten firmly.

 3– Replace stem cap, finger tighten then tighten an

additional 1/6 turn.

2 – Suction Line (Seating Type) Service Valve

A full service  non-backseating suction line service valve
is used on all HS25 series units. Different manufacturers
of valves may be used. All suction line service valves
function the same way, differences are in construction.
Valves manufactured by Parker are forged assem-
blies. Primore and Aeroquip valves are brazed to-
gether. Valves are not rebuildable. If a valve has
failed it must be replaced. The suction line service
valve is illustrated in figure 8.
The valve is equipped with a service port. A schrader
valve is factory installed. A service port cap is sup-
plied to protect the schrader valve from contamina-
tion and assure a leak free seal.

SUCTION LINE SERVICE VALVE (VALVE OPEN)

FIGURE 8

SCHRADER VALVE

SERVICE PORT

SERVICE PORT

CAP

STEM CAP

SNAP RING

INSERT HEX WRENCH

HERE (PART #49A71 AND

SERVICE WRENCH)

SUCTION LINE SERVICE VALVE (VALVE CLOSED)

INLET

(FROM INDOOR COIL)

OUTLET

(TO COMPRESSOR)

KNIFE EDGE

SEAL

SCHRADER VALVE OPEN

TO LINE SET WHEN

VALVE IS CLOSED

(FRONT SEATED)

SERVICE PORT

SERVICE PORT

CAP

(VALVE

FRONT SEATED)

SNAP RING

STEM

CAP

OUTLET

(TO COMPRESSOR)

KNIFE EDGE SEAL

INLET

(FROM INDOOR COIL)

INSERT

HEX WRENCH HERE

(PART #49A71 AND

SERVICE

WRENCH)

To Access Schrader Port:

 1– Remove service port cap with an adjustable wrench.
 2– Connect gauge to the service port.
 3– When testing is completed, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Suction Line Service Valve:

 1– Remove stem cap with an adjustable wrench.
  2– Using service wrench and 5/16” hex head extension

(part #49A71) back the stem out counterclockwise
until the valve stem just touches the retaining ring.

Do not attempt to backseat this valve. Attempts to
backseat this valve will cause snap ring to explode
from valve body under pressure of refrigerant.
Personal injury and unit damage will result.

DANGER

 3– Replace stem cap tighten firmly. Tighten finger

tight, then tighten an additional 1/6 turn.

To Close Suction Line Service Valve:

 1– Remove stem cap with an adjustable wrench.
 2– Use service wrench and 5/16” hex head extension

(part #49A71) turn stem clockwise to seat the valve.
Tighten firmly.

Содержание HS25-211

Страница 1: ...must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the Engineering Handbook for approved system matchups A misapplied system will cause errat...

Страница 2: ...1 7 1 6 1 1 3 1 3 8 2 0 50 60 45 31 3 37 7 26 1 SPECIFICATIONS Model No HS25 261 HS25 311 HS25 411 Outdoor Coil Condenser Fan HCFC 22 charge furnished Face area sq ft Tube diameter in No of Rows Fins...

Страница 3: ...uring a single orbit several pockets of gas are compressed simulta neously providing smooth continuous compression The scroll compressor is tolerant to the effects of liquid return If liquid enters th...

Страница 4: ...the compressor contactor On initial ther mostat demand the compressor contactor is delayed for 8 5 seconds At the end of the delay the compressor is allowed to energize When thermostat demand is sa t...

Страница 5: ...DISCHARGE TEMPERATURE SENSOR WIRES TO CONTROL BOX TO COMP TERM BOX IN 461 UNITS 3 1 2 TON AND SMALLER ONLY F High Pressure Switch A manual reset single pole single throw high pressure switch located...

Страница 6: ...application of field fabricated lines Separate discharge and suction service ports are pro vided at the compressor for connection of gauge man ifold during charging procedure Model No LIQUID SUCTION L...

Страница 7: ...rences are in construction Valves manufactured by Parker are forged assem blies Primore and Aeroquip valves are brazed to gether Valves are not rebuildable If a valve has failed it must be replaced Th...

Страница 8: ...h gauge manifold and connect vacuum pump with vacuum gauge to center port of gauge manifold With both gauge manifold ser vice valves open start pump and evacuate evapo rator and refrigerant lines IMPO...

Страница 9: ...table 6 as a general guide for performing main tenance checks Table 6 is not a procedure for charg ing the system Minor variations in these pressures may be expected due to differences in installation...

Страница 10: ...erminal Y passes through discharge temperature sensor compressor thermostat and low pressure switch to energize time delay terminal 2 3 Time delay action is at the beginning of a thermostat demand Whe...

Отзывы: