background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system.

FIREPLACE FINISHES

Mantels and Trim

It is sometimes best to frame your fireplace
after it is positioned and the chimney is in-
stalled. Frame enclosure for chimney and fire-
place with 2 x 4’s (or heavier) lumber.

Note: The header may rest on the two (2) metal
top spacers on top of the unit but the header
must not be notched to fit around the spacers.

These fireplaces may sit directly on a combus-
tible surface.  A 2" air space is required be-
tween combustible framing and the chimney.
A 1" air space is required between combustible
framing and fireplace outer wrapper.

In Canada, the minimum height for a combus-
tible mantel is 18" (457 mm) above the fire-
place opening.  

Figure 45 shows typical

Canadian installations.  For installations other
than Canada, combustible mantels and trim
may be installed 12" above the fireplace open-
ing as per NFPA 211, Section 7-2.3.3. and
Figure 46.  If a mantel is of a noncombustible
material, it is exempt from these requirements
as long as it does not interfere with the instal-
lation or operation of glass doors.

Figure 46

If you’re installing a gas line, connect it before
the fireplace is framed and enclosed in the
finished wall. The gas knockout is determined
by the indentation located at the bottom and
slightly off center in the side refractories. THE
KNOCKOUT IS ALWAYS REMOVED FROM IN-
SIDE THE FIREPLACE. DO NOT REMOVE THE
KNOCKOUT UNLESS YOU ARE INSTALLING A
GAS LINE.
 If removal is attempted from the
outer wrapper, side refractory damage may
occur. With a medium-sized hammer, lightly
tap the surface of the indentation. The refrac-
tory material is very thin in this area and is easily
removed. Once a small hole has been made,
continue tapping until you have reached suffi-
cient diameter for the gas line to fit through. The
entire knockout does not have to be removed.
Remove insulation in the gas line channel.

IMPORTANT: REPACK INSULATION MATERIAL
IN SQUARE HOLE AROUND GAS LINE, INTE-
RIOR AND EXTERIOR OF FIREPLACE, TO SEAL.

Glass Doors

If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVERLAP
THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS, THERE
MIGHT NOT BE SUFFICIENT CLEARANCE TO
INSTALL THE GLASS DOORS OF YOUR
CHOICE. ENSURE ADEQUATE CLEARANCE IS
MAINTAINED AT ALL TIMES SO AS NOT TO
INTERFERE WITH THE INSTALLATION AND
OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially
important to seal all cracks around the fireplace
opening with noncombustible material and
wherever cold air could enter the room. Sur-
rounding materials must be caulked where it
meets the black metal facing of the fireplace to
avoid cold air intrusion. Use noncombustible
caulking material only on fireplace facing to
seal. Also, the outside air inlet duct should be
wrapped with noncombustible insulation to
minimize the formation of condensation. Do
not place insulation materials on top of fire-
place or against chimney sections.

Note: A 2" air space must be preserved for all
combustible materials extending for any con-
tinuous length adjacent to the chimney.

Figure 45

Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both radiant
heat and sparks. The hearth extension must
extend 8" beyond both sides of the fireplace
opening and 16" beyond the front (

see Figure

47 ). Use a hearth extension constructed of a
durable noncombustible material having an
equal or better (lower k value) insulating value
of k = .43 BTU IN/FT

HR 

°

F or a thermal

resistance that equals or exceeds r = 2.33 HR

°

F FT

2

/BTU IN.  With these values, determine

the minimum thickness/material required us-
ing the formula and 

Page 17.

Note: Any noncombustible material whose k
value is less than .43 or whose r value is more
than 2.33 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fire-
place and half under the hearth extension
(refer to 

Figures 6 & 7).

A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening (

Figure 48 ). Use a 36" W x

36" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than k =
.54 BTU IN/FT

2

 HR 

°

F.  At no time may a

perpendicular side wall be located closer than
9" from the fireplace opening.

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Canadian Installation

Fireplace
Opening

Header

Spacer

8" Max.

(203mm)

18" Min.

(457mm)

Combustible

Mantel

Finished

Wall

Typical Installation

*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 32,000
BTU Or Higher Is Used.  (Maximum 40,000 BTU)

12"*
Min.

9"*

Fireplace
Opening

Combustible
Mantel
and Trim

12"

Max.

1 1/2"

Header

Spacer

Finished Wall

Содержание HC-42

Страница 1: ...modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may...

Страница 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribu...

Страница 3: ...These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance wit...

Страница 4: ...overhead obstructions such as trees power lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also be insulate...

Страница 5: ...l safety strips beneaththefireplaceasillustrated Figures6 7 and 8 The safety strips should overlap for continual coverage of the floor Note Safety strips are not required when fire place rests on a no...

Страница 6: ...ce If a wall covering such as drywall is to be attached to the rear wall then the 23 606 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is t...

Страница 7: ...der Fireplace Framing B A A Outside Chase G H Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Corner Installation...

Страница 8: ...upthroughtheceiling or floor joists to an outside wall The air duct s inlet should be located above any anticipated snow level Note If the fireplace is installed against an inside wall the Class 0 me...

Страница 9: ...sure proper engagement Checkverticalalignmentofchim ney so that it projects from the roof in true vertical position Figure 27 Step 4 Note Chimney sections are con structed with a unique locking tab de...

Страница 10: ...Do not overtighten as this might dam age the chimney section refer to Figure 31 Note If chimney extends more than 8 above roof surface guy wires are also recommended Use three 3 guy wires attach to l...

Страница 11: ...fireplace system is 15 0 The maxi mum height is 60 0 To determine the number of chimney sections and chimney components required follow these steps 1 Determine total vertical height of the fireplace i...

Страница 12: ...23 0 1 0 1 5 278 23 2 0 0 0 6 282 23 6 0 1 1 5 288 24 0 1 0 0 6 294 24 6 0 1 0 6 298 24 10 2 0 0 6 304 25 4 1 1 0 6 312 26 0 0 0 1 6 322 26 10 1 0 1 6 324 27 0 0 0 0 7 328 27 4 0 1 1 6 334 27 10 1 0 0...

Страница 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Страница 14: ...mney section Step 2 Center inner slip section into inner flue pipe slip down Step 3 Center outer locking section over outer chimneypipe Pushdownuntillockingjointhas firmly engaged Step 4 Pull up sligh...

Страница 15: ...per operation before completing any enclo sure around the firebox Failure to do so may result in extensive and costly rework Locate the actuator arm along the right side of the appliance firebox openi...

Страница 16: ...LACE IF THE FIREPLACE HAS BEEN FACED WITHNONCOMBUSTIBLEMATERIALS THERE MIGHT NOT BE SUFFICIENT CLEARANCE TO INSTALL THE GLASS DOORS OF YOUR CHOICE ENSURE ADEQUATE CLEARANCE IS MAINTAINED AT ALL TIMES...

Страница 17: ...5 6 56 6 1 2 Wonderboard 3 23 31 7 51 7 1 2 Super Firetemp M Johns Manville 61 1 64 1 42 1 3 8 Super Firetemp L Johns Manville 54 1 85 Face brick 9 00 111 20 93 20 7 8 Common brick 5 00 20 Cement mort...

Страница 18: ...ptable combinations of materialsbecause Rvalues areadditivewhere r and k values are not R value 1 k r x thickness of material used Example Given that the required R value for a suitable floor protecto...

Страница 19: ...Chase Termination Square 63L48 FTF8 CT1 Firestop Spacer Flat 63L31 F8FS 2 Locking Band 63L60 FLB Forced Air Blower Kits Single Speed 80L84 FBK 100 Variable Speed 80L85 FBK 200 FBK 200 Models Only Outs...

Страница 20: ...ign materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 Chase Termina...

Отзывы: