4. Set the air selection jumper for the zone using the per-

cent air determined in step 3. If the percent air falls be-
tween available jumper settings, select the nearest
unit of ten.

5. For each zone, repeat steps 1 through 4.

Continuous Air Reduction Jumpers

During continuous fan mode with no heating or cooling de-
mand, the blower runs at the total percentage of the CFM
jumper settings of the zones calling for continuous fan,
which cannot exceed 100% of blower capacity. The contin-
uous air reduction feature enables the blower speed to be
reduced by a percentage of the blower speed during con-
tinuous fan mode.

The selections are 75%, 50%, 25% and 0%. The factory
places the jumper on 0%. Set the jumper to the position
equal to the amount of continuous air reduction desired.
See figure 13.

NOTE − The blower will not deliver less than it’s minimum
CFM even if the air reduction percentage is less.

CONTINUOUS

HEATING

0%
20%

40%

75%

50%

0%

25%

Figure 13

Air Reduction Jumper Settings

factory

settings

shown

heating jumper
Must be set on 0%
for heat pump
application

Heating Air Reduction Jumpers

The heating air reduction jumper enables the blower
speed, during heating, to be reduced by a percentage of
the cooling blower speed.

The selections are 40%, 20% and 0%. Jumpers are set to
0% from the factory. Set the jumper to the position equal to
the amount of heating air reduction desired. See figure 13.

NOTE − For heat pump applications, 

ALWAYS

 set the

jumper on 0%. High head pressures may result if air is re-
duced during heating mode.

Determining Actual Air Delivered By Blower

The actual CFM delivered to each zone will be determined
by the zone control system settings, blower motor control
board settings, zone thermostat demand status [calling for
heating, cooling, continuous fan, or no demand (zone
damper closed)], and the air distribution system’s duct
size.

When the zone control system is set for a particular zone,
heating reduction jumper, and/or continuous air reduction
settings determine the total CFM available from the unit as
follows:

1.

Determine Total Unit PIAB

Using the formula in

Table 5, calculate the Total Percent into Adjustment
Band. This illustrates how far into the adjustment band
the motor runs when more than one zone is calling for
conditioning, given the following assumptions:

D

Zone 1 Jumper

30%

D

Zone 2 Jumper

10%

D

Zone 3 Jumper

20%

D

Zone 4 Jumper

OFF

D

Zones calling

2 & 3

D

Maximum CFM

2220

D

Minimum CFM

720

Table 5

Total Percent Into Adjustment Band

Formula:

Total
PIAB

= (Sum of Calling Zones

Jumper Positions)

+ (# of Zones Calling − 1)

3

Total
PIAB

= (.10 + .20)

+

(2 − 1)

3

Total
PIAB

= .30

+

.33

Total
PIAB

= 63% (The motor will run 63% into the adjustment

band of the motor.)

2.

Determine Total CFM Delivered

Continuing from

the previous example and assumptions, and using the
formula in Table 6, calculate the total CFM delivered.

Table 6

Determine Total CFM Delivered

Formula:

Total
CFM

= (Total PIAB) X (Max CFM − Min CFM)

+

(Min.
CFM)

Total
CFM

= (.63) X (2220 − 720)

+ (720)

Total
CFM

= (.63) X (1500)

+ (720)

Total
CFM

= 1665

Again, the maximum and minimum CFM values used
in the formula should correspond to the jumper set-
tings on the blower control board. This value repre-
sents the volume of air received if all zones were call-
ing for cooling.

Содержание HARMONY II

Страница 1: ...cs Codes 25 Troubleshooting Diagrams 27 PIAB Calculation Worksheet 30 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Shipping Packing List Items shipped with the Harmony IIIt Zone Control System inclu...

Страница 2: ...ke comfort settings for each zone A programmable thermostat should be used to provide a specialized heating and cooling sequence While the sys tem is in the zone mode a programmable thermostat con tro...

Страница 3: ...nical or electro mechanical thermostats will not work with the Harmony IIIt zone control system Recommended thermostats include S SignatureStatt Thermostat 1 heat 1 cool 81M26 IMPORTANT When using thi...

Страница 4: ...at Pump IMPORTANT LENNOX recommends ONLY Harmony II and Harmony IIIt Zone Control Systems for use with Variable Speed Blower Motor VSM technology 1 Lennox Blower Coil Unit with VSM Use ONLY blower coi...

Страница 5: ...appliances and sunny windows near concealed pipes and chimneys or in unconditioned spaces such as closets or exterior walls Dampers Motorized dampers in the supply duct system regulate air to the zon...

Страница 6: ...RTANT Be sure to cut jumper W914 if not cut the zone con trol board DS fuse will blow WARNING Electrical Shock Hazard Disconnect power from unit and wait at least five minutes to allow capacitors to d...

Страница 7: ...s remove any factory installed jumper between terminal R and W1 W2 or W3 D In all cases cut and tape wire 7 see figure 8 on the VSM harness that runs from the BDC3 board to the motor 9 Figure 8 4 5 1...

Страница 8: ...on Chart Model Equivalent Positions Harmony II 25 35 45 55 65 75 85 95 Harmony IIIt 0 10 30 40 50 70 80 90 When jumpers are set to 0 this corresponds to the mini mum air volume available according to...

Страница 9: ...is re duced during heating mode Determining Actual Air Delivered By Blower The actual CFM delivered to each zone will be determined by the zone control system settings blower motor control board setti...

Страница 10: ...AB 8 x CFM Max 2220 Min 720 x 1500 Min CFM 720 TOTAL 1920 CFM 4 Determine total air delivered during a continuous blower call Calculate these totals using the formu las and example Table 8 which uses...

Страница 11: ...hp 1hp 2 2hp 1hp 2 3 3 DOESN T MATTER Dual fuel heating 1 stage AC heat pump SYSTEM E HEAT Configuration Stages HP GAS df gas df 2cool 1cool 1 2cool 1cool 1 2hp 1hp 2 2hp 1hp 2 3 3 Figure 14 NOTE Vari...

Страница 12: ...g close to AC house wiring If this cannot be avoided limit close parallel of power and control wiring to a few feet Dampers and Damper Transformer Wiring Connect dampers to the zone control board as s...

Страница 13: ...NOTE If not already done remove the wire to K20 blower relay terminal 7 on BDC3 board and tape it off Also be sure the factory installed jumper between terminal R and W1 W2 and W3 has been removed He...

Страница 14: ...11 120 VAC 24 VAC C R IMPORTANT Connectivity is NOT COMPLETE until all electrical adjustments jumpers and wiring changes have been made See Electrical Adjustments for SureLight Board page 6 and for BD...

Страница 15: ...UNDED METAL OBJECT BEFORE TOUCHING THE CIRCUIT BOARD LENNOX Harmony IIIt V3 0 2004 System Configuration E Heat jumper settings page 11 piab jumper settings page 8 air reduction jumper settings page 9...

Страница 16: ...quipment DISCHARGE AIR SENSOR 88K38 included IMPORTANT Connect thermostat gauge wire to SureLight board C terminal HEAT PUMP VARIABLE SPEED FURNACE Figure 21 NOTE Do not wire Y wire s from the Harmony...

Страница 17: ...ing the blower may continue after the end of a demand until the heater is cooled sufficiently Cooling Operation When the Harmony IIIt zone control system receives a thermostat cooling call the followi...

Страница 18: ...p heat or in a dual mode system the heat demand is satisfied by the gas furnace Operation Troubleshooting Indicators Zone Control Board LEDs The zone control system operation is indicated by light emi...

Страница 19: ...ng proper operation Perform the gas and heat pump heating checks on pages 20 through 24 Table 9 Time Delays Delay Time Function Blower Off Delay gas heat only 3 1 2 min Gas Furnace only Dumps air into...

Страница 20: ...e damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Prerequisites S All zone thermostats set to Heat OUTPUT STATUS LEDs DAMPER 2 3 4 OFF W1 on W RED on hEAT...

Страница 21: ...LEDs DAMPER 2 3 4 on DAMPER 1 Off W RED ON event Sequence 1 Y1 ON 2 Y2 IF EQUIPPED ON IF NO SIGNIFICANT WARMING AFTER 4 MIN 3 W1 ON IF NO SIGNIFICANT WARMING AFTER 4 MIN THEN W2 THEN W3 PRESSURE SWITC...

Страница 22: ...ing 3 1 2 minute purge Other zones damper LEDs are on during the 3 1 2 minute purge dampers closed After 3 1 2 minute delay all dampers LEDs go off dampers open Heat Pump Heating Checkout Central Cont...

Страница 23: ...individual zone damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Dual Fuel Option and BPS Prerequisites S All zone thermostats set to Heat S Balance Point...

Страница 24: ...ill produce a faulty reading At 77 F the resistance of the sensor will be 10K ohm at lower probe temperatures ex pect higher resistance at warmer probe temperatures ex pect lower resistance After read...

Страница 25: ...or Some of the errors found in table will cause a fail safe or shutdown condition The system will shutdown after the er ror is present for about five seconds During a shutdown condition all dampers wi...

Страница 26: ...ill cycle from high to off in cooling The compressor will cycle from high to off in heating The furnace will operate normally in gas heat Replace discharge probe If error persists replace zone control...

Страница 27: ...spond to demand 0 volts AC open 24 volts AC closed Dampers should drive closed when 24 volts is jumpered to damper motor Is wiring correct in good condition Figure 23 Line Voltage to transformer 24VAC...

Страница 28: ...n relays may need to be used 24VAC supplied to each thermostat terminal R from zone control system Check each thermostat for output signal when calling Heating output W1 Cooling output Y1 Do dampers r...

Страница 29: ...charge air plenum as de scribed on Page 5 Is it wired cor rectly Does outdoor unit respond to demand Is it operating properly Test Defrost Does outdoor unit initiate and terminate defrost correctly W1...

Страница 30: ...AB 0 2 x 100 20 Zone 1 CFM Required Minimum Maximum Minimum ZONE 1 PIAB x 100 b b ZONE 1 PIAB x 100 b ZONE 1 PIAB x 100 Zone 2 CFM Required Minimum Maximum Minimum ZONE 2 PIAB x 100 b b ZONE 2 PIAB x...

Отзывы: