Lennox HARMONY II Скачать руководство пользователя страница 3

Page 3

HARMONY III

T

 SERIES

System Components

Zone Control System

The Harmony III

t

 zone control system monitors electrical

signals and directs control signals between thermostats,
dampers, and HVAC equipment (see figure 1).

JUMPERS:

STAGING

TEMP‘

HEATING−−

 

COOLING−−

AIR 

REDUCTION 

CONT.−−

HEATING−−

Figure 1

EQUIPMENT

CONNECTIONS

THERMOSTAT
CONNECTIONS

24VAC
CONNECTIONS

PIAB

JUMPERS

SYS Config & E−HEAT JUMPERS

DIAGNOSTIC

LEDS

time

delay

override

FAULT
RECALL

BALANCE POINT
SENSOR
CONNECTIONS

PRESSURE

SWITCH CON-

NECTIONS

DISCHARGE
AIR SENSOR
CONNECTIONS

DAMPER
CONNEC
TIONS

FUSES

SYSTEM OPERATION LEDS

Harmony III

t

 Zone Control Board

Discharge Air Sensor

A discharge air temperature sensor (88K38) monitors the
supply air. This electronic sensor’s probe (see figure 2) is
inserted into the discharge air plenum to gather air temper-
ature data for the zone control board.

Discharge Air Sensor (Probe)

Figure 2

Separately-Ordered System Components

Thermostats

For all zones, use thermostats that are of this type:

S

electronic thermostat

S

single-stage

S

non-heat pump

S

non-power robbing

S

autochangeover or non−autochangeover

Lennox recommends that zone 1 thermostat [central
(vacation) mode controller] be programmable. Each ther-
mostat must have a dead band between HEAT and COOL.

IMPORTANT

Use only Electronic thermostats. Mechanical or
electro-mechanical thermostats will not work with
the Harmony III

t

 zone control system.

Recommended thermostats include:

S

SignatureStat

t

 Thermostat − 1 heat / 1 cool (81M26)

[IMPORTANT!

 When using this thermostat, only Pre-

cision Mode dehumidification can be used wherein
2°F of over-cooling is allowed. Also, it cannot reduce
the blower speed because the zone control DS con-
trols the blower. Thermostat D terminal is not used.

S

Elite

® 

Touch Screen Thermostat − 1 heat / 1 cool /

7−day programmable (X4146).

Transformer

The dampers, zone control board, and zone thermostats
are powered by a single, field−provided 24VAC transform-
er. Together, the zone control panel and thermostats re-
quire 10VA; dampers require 10VA each. The transformer
must have an adequate VA rating to serve all components
(see recommendations in table 1).

Table 1

24VAC Transformer Selection Chart

Catalog
No.

Size

Description

VA LOAD =
Panel plus−

10P17

40VA

120/208/240VAC, 24VAC

3 dampers

10P87

50VA

120/208/240VAC, 24VAC

4 dampers

12P61

75VA

120/208/240VAC, 24VAC

6 dampers

83P74

_

Electrical Box (4-in.
square)

Dampers

Motorized 24VAC powered closed/spring return open
dampers are standard for the Harmony III

t

 zone control

system. However, power-open/spring-close" and power-
open/power-close" dampers can be accommodated.

Pressure Switch

A pressure switch [R−22 (21J18); R−410A (51M08)] is re-
quired for applications with a Lennox heat pump (Options 2
and 3). The pressure switch acts as a guard in case of high
head pressures during first− and second−stage heating.

Содержание HARMONY II

Страница 1: ...cs Codes 25 Troubleshooting Diagrams 27 PIAB Calculation Worksheet 30 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Shipping Packing List Items shipped with the Harmony IIIt Zone Control System inclu...

Страница 2: ...ke comfort settings for each zone A programmable thermostat should be used to provide a specialized heating and cooling sequence While the sys tem is in the zone mode a programmable thermostat con tro...

Страница 3: ...nical or electro mechanical thermostats will not work with the Harmony IIIt zone control system Recommended thermostats include S SignatureStatt Thermostat 1 heat 1 cool 81M26 IMPORTANT When using thi...

Страница 4: ...at Pump IMPORTANT LENNOX recommends ONLY Harmony II and Harmony IIIt Zone Control Systems for use with Variable Speed Blower Motor VSM technology 1 Lennox Blower Coil Unit with VSM Use ONLY blower coi...

Страница 5: ...appliances and sunny windows near concealed pipes and chimneys or in unconditioned spaces such as closets or exterior walls Dampers Motorized dampers in the supply duct system regulate air to the zon...

Страница 6: ...RTANT Be sure to cut jumper W914 if not cut the zone con trol board DS fuse will blow WARNING Electrical Shock Hazard Disconnect power from unit and wait at least five minutes to allow capacitors to d...

Страница 7: ...s remove any factory installed jumper between terminal R and W1 W2 or W3 D In all cases cut and tape wire 7 see figure 8 on the VSM harness that runs from the BDC3 board to the motor 9 Figure 8 4 5 1...

Страница 8: ...on Chart Model Equivalent Positions Harmony II 25 35 45 55 65 75 85 95 Harmony IIIt 0 10 30 40 50 70 80 90 When jumpers are set to 0 this corresponds to the mini mum air volume available according to...

Страница 9: ...is re duced during heating mode Determining Actual Air Delivered By Blower The actual CFM delivered to each zone will be determined by the zone control system settings blower motor control board setti...

Страница 10: ...AB 8 x CFM Max 2220 Min 720 x 1500 Min CFM 720 TOTAL 1920 CFM 4 Determine total air delivered during a continuous blower call Calculate these totals using the formu las and example Table 8 which uses...

Страница 11: ...hp 1hp 2 2hp 1hp 2 3 3 DOESN T MATTER Dual fuel heating 1 stage AC heat pump SYSTEM E HEAT Configuration Stages HP GAS df gas df 2cool 1cool 1 2cool 1cool 1 2hp 1hp 2 2hp 1hp 2 3 3 Figure 14 NOTE Vari...

Страница 12: ...g close to AC house wiring If this cannot be avoided limit close parallel of power and control wiring to a few feet Dampers and Damper Transformer Wiring Connect dampers to the zone control board as s...

Страница 13: ...NOTE If not already done remove the wire to K20 blower relay terminal 7 on BDC3 board and tape it off Also be sure the factory installed jumper between terminal R and W1 W2 and W3 has been removed He...

Страница 14: ...11 120 VAC 24 VAC C R IMPORTANT Connectivity is NOT COMPLETE until all electrical adjustments jumpers and wiring changes have been made See Electrical Adjustments for SureLight Board page 6 and for BD...

Страница 15: ...UNDED METAL OBJECT BEFORE TOUCHING THE CIRCUIT BOARD LENNOX Harmony IIIt V3 0 2004 System Configuration E Heat jumper settings page 11 piab jumper settings page 8 air reduction jumper settings page 9...

Страница 16: ...quipment DISCHARGE AIR SENSOR 88K38 included IMPORTANT Connect thermostat gauge wire to SureLight board C terminal HEAT PUMP VARIABLE SPEED FURNACE Figure 21 NOTE Do not wire Y wire s from the Harmony...

Страница 17: ...ing the blower may continue after the end of a demand until the heater is cooled sufficiently Cooling Operation When the Harmony IIIt zone control system receives a thermostat cooling call the followi...

Страница 18: ...p heat or in a dual mode system the heat demand is satisfied by the gas furnace Operation Troubleshooting Indicators Zone Control Board LEDs The zone control system operation is indicated by light emi...

Страница 19: ...ng proper operation Perform the gas and heat pump heating checks on pages 20 through 24 Table 9 Time Delays Delay Time Function Blower Off Delay gas heat only 3 1 2 min Gas Furnace only Dumps air into...

Страница 20: ...e damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Prerequisites S All zone thermostats set to Heat OUTPUT STATUS LEDs DAMPER 2 3 4 OFF W1 on W RED on hEAT...

Страница 21: ...LEDs DAMPER 2 3 4 on DAMPER 1 Off W RED ON event Sequence 1 Y1 ON 2 Y2 IF EQUIPPED ON IF NO SIGNIFICANT WARMING AFTER 4 MIN 3 W1 ON IF NO SIGNIFICANT WARMING AFTER 4 MIN THEN W2 THEN W3 PRESSURE SWITC...

Страница 22: ...ing 3 1 2 minute purge Other zones damper LEDs are on during the 3 1 2 minute purge dampers closed After 3 1 2 minute delay all dampers LEDs go off dampers open Heat Pump Heating Checkout Central Cont...

Страница 23: ...individual zone damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Dual Fuel Option and BPS Prerequisites S All zone thermostats set to Heat S Balance Point...

Страница 24: ...ill produce a faulty reading At 77 F the resistance of the sensor will be 10K ohm at lower probe temperatures ex pect higher resistance at warmer probe temperatures ex pect lower resistance After read...

Страница 25: ...or Some of the errors found in table will cause a fail safe or shutdown condition The system will shutdown after the er ror is present for about five seconds During a shutdown condition all dampers wi...

Страница 26: ...ill cycle from high to off in cooling The compressor will cycle from high to off in heating The furnace will operate normally in gas heat Replace discharge probe If error persists replace zone control...

Страница 27: ...spond to demand 0 volts AC open 24 volts AC closed Dampers should drive closed when 24 volts is jumpered to damper motor Is wiring correct in good condition Figure 23 Line Voltage to transformer 24VAC...

Страница 28: ...n relays may need to be used 24VAC supplied to each thermostat terminal R from zone control system Check each thermostat for output signal when calling Heating output W1 Cooling output Y1 Do dampers r...

Страница 29: ...charge air plenum as de scribed on Page 5 Is it wired cor rectly Does outdoor unit respond to demand Is it operating properly Test Defrost Does outdoor unit initiate and terminate defrost correctly W1...

Страница 30: ...AB 0 2 x 100 20 Zone 1 CFM Required Minimum Maximum Minimum ZONE 1 PIAB x 100 b b ZONE 1 PIAB x 100 b ZONE 1 PIAB x 100 Zone 2 CFM Required Minimum Maximum Minimum ZONE 2 PIAB x 100 b b ZONE 2 PIAB x...