Page 53
FIGURE 62
COMBUSTION AIR
BLOWER
L.P.G. COMBUSTION AIR ORIFICE
GCS16H-50 UNITS
ORIFICE GASKET
TRANSITION
GASKET
FLUE
TRANSITION
COMBUSTION
AIR ORIFICE
FIGURE 63
COMBUSTION
AIR ORIFICE
ORIFICE GASKET
L.P.G. COMBUSTION AIR ORIFICE
GCS16R-50 UNITS
GCS16-50 and GCS16R-50 units also require a burner air
restrictor plate which is used to cover some of the air in
take holes surrounding the burner. The 50K Btuh burner
restrictor plate is shown in figure 64.
All 75K, 100K and 125K Btuh units require a center air re
strictor plate when converting from Natural to L.P. gas.
The restrictor is used to cover the air intake space immedi
ately surrounding the burner as shown in figure 65. In
units equipped with burner enclosure (figure 12), the en
closure must be carefully disassembled to gain access to
the burner and restrictor plate.
FIGURE 64
INSTALL OUTER RESTRICTOR
PLATE SECURING AT THE TOP
AND BOTTOM WITH EXISTING
BOLTS.
NOTE-Plate must be installed as
shown to ensure proper unit operation.
LPG BURNER RESTRICTOR PLATE
GCS16R-50 AND GCS16-50 UNITS
BURNER
PLATE
CENTER AIR
OPENING
BURNER
PLATE
RESTRICTOR
PLATE
FIGURE 65
BURNER ASSEMBLY
CENTER RESTRICTOR
PLATE
BURNER PLATE
INSTALL CENTER RESTRICTOR PLATE
75K, 100K and 125K Btuh HEAT EXCHANGERS
G-Condenser Coil Guard Kit
Optional condenser coil guard kit is available for all units.
The kit includes PVC coated steel wire coil guard which is
field installed. GCS16H units require one guard,
GCS16-411/413 and GCS16R-411 units require two
guards and GCS16-511/513/651/653 and
GCS16R-511/651 require three guards.