Page 30

506178−01    05/2009

Blower Performance Data

G60DF−36A−070X PERFORMANCE

External

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure

i

High

Medium−

High

Medium−

Low

Low

in. w.g.

cfm Watt cfm Watt cfm Watt cfm Watt

0.00

1475

616

1345

554

1150

495

990

415

0.05

1450

606

1320

543

1140

481

985

407

0.10

1425

595

1300

532

1125

466

975

398

0.15

1395

585

1275

521

1115

452

970

390

0.20

1375

574

1255

510

1105

437

965

381

0.25

1345

563

1230

494

1090

428

955

371

0.30

1320

552

1205

478

1075

418

945

360

0.40

1250

528

1150

455

1040

395

920

346

0.50

1200

508

1095

432

1000

374

880

331

0.60

1110

475

1035

409

950

354

830

313

0.70

1030

455

970

390

855

338

720

280

0.80

960

434

875

359

735

299

665

266

0.90

770

389

715

321

665

278

590

244

G60DF−36B−090 PERFORMANCE

External

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure

High

Medium−

High

Medium−

Low

Low

in. w.g.

cfm Watt cfm Watt cfm Watt cfm Watt

0.00

1600

608

1410

526

1165

436

965

355

0.05

1580

599

1400

518

1165

428

965

351

0.10

1560

589

1390

509

1160

420

970

346

0.15

1530

573

1370

497

1155

413

965

341

0.20

1495

556

1350

485

1150

406

965

335

0.25

1465

544

1325

473

1135

398

955

329

0.30

1430

532

1300

460

1125

389

945

323

0.40

1370

509

1250

438

1095

373

935

313

0.50

1295

482

1200

420

1055

355

900

302

0.60

1215

456

1140

397

1010

343

860

285

0.70

1140

437

1055

371

915

313

800

272

0.80

1000

401

950

342

850

295

730

251

0.90

900

374

820

313

740

272

− − −

− − −

NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place.

G60DF−48C−110 PERFORMANCE

External

Static

Air Volume / Watts at Different Blower Speeds

Static

Pressure

High

Medium−High Medium−Low

Low

in. w.g.

cfm

Watts

cfm

Watts

cfm

Watts

cfm

Watts

0.00

2035

846

1790

712

1510

595

1225

477

0.05

2000

825

1760

694

1495

581

1225

470

0.10

1970

803

1730

675

1475

567

1220

463

0.15

1925

781

1710

657

1475

555

1220

455

0.20

1880

758

1685

638

1465

542

1215

447

0.25

1835

736

1655

618

1440

528

1200

437

0.30

1795

714

1625

597

1420

514

1185

427

0.40

1680

669

1550

564

1360

483

1135

400

0.50

1620

630

1445

524

1280

447

1065

371

0.60

1445

592

1310

479

1165

404

1000

343

0.70

1290

545

1180

434

1055

369

905

319

0.80

1155

502

1065

406

955

348

815

296

0.90

1010

472

930

372

840

320

690

265

NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not fur-
nished − field provided) in place.

Содержание G60DF(X) Series

Страница 1: ...erformance 30 Heating Sequence of Operation 31 Service 32 Planned Service 33 Ignition Control Diagnostic Codes 34 Troubleshooting 35 Repair Parts List 41 Start Up Performance Check List 42 WHAT TO DO...

Страница 2: ...19 3 4 19 28 1 2 724 19 1 2 495 19 1 4 489 9 1 4 235 4 7 8 124 Right 2 1 4 57 Left 40 1016 3 3 4 95 5 8 16 AIR FLOW 5 8 16 3 4 19 19 1 2 495 5 8 16 B 5 8 16 5 8 16 Supply Air Supply Air Model No A B C...

Страница 3: ...mit Heat Exchanger Combustion Air Pressure Switch Assembly Two Switches Combustion Air Orifice Transformer Two Stage Integrated Control Flue Chase Gasket Door Interlock Switch Limit Shield Circuit Bre...

Страница 4: ...lding codes In the absence of local codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 NFPA 54 The National Fuel Gas Code is available from the following address...

Страница 5: ...hese installation instructions D A room thermostat must control the furnace The use of fixed jumpers that will provide continuous heating is not allowed D The return air duct must be provided and seal...

Страница 6: ...nts as well as all local codes CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the heat exchanger resulting in rust ing and...

Страница 7: ...g must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening must be at least 100 square in...

Страница 8: ...least one square inch 645 mm2 per 4 000 Btu 1 17 kW per hour of the total input rating of all equip ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of a...

Страница 9: ...her combustible ma terial other than wood flooring TABLE 2 ADDITIVE BASE FLOOR OPENING SIZE Model No Front to Rear Side to Side Model No in mm in mm A Cabinet 14 5 22 559 15 3 4 400 B Cabinet 17 5 22...

Страница 10: ...housing Downflow Application Allow for clearances to combustible materials as indi cated on the unit nameplate Minimum clearances for closet or alcove installations are shown in figure 9 Downflow Appl...

Страница 11: ...ansition will cause the unit to operate unsafely and will void the unit certification The vent connector does not require insula tion The G60DF X series units are classified as fan assisted Category I...

Страница 12: ...nto an existing lined masonry chimney if the following conditions are met S The chimney is currently serving at least one drafthood equipped appliance S The vent connectors and chimney are sized accor...

Страница 13: ...chimney has a larger diameter or flow area than the vent connector use the vertical vent diameter to de termine the minimum vent capacity and the vent connector diameter to determine the maximum vent...

Страница 14: ...ory I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems 17 If vent connectors are combined prior...

Страница 15: ...5 136 20 226 22 339 15 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 20 5 21 71 29 143 38 242 47 367 20...

Страница 16: ...8 69 57 136 80 225 115 337 15 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 20 5 50 68 73 14...

Страница 17: ...2 52 146 69 220 1 21 50 33 89 47 142 64 220 15 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 1 21 54 33 99 46 157 62 246 20 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 1 20 62...

Страница 18: ...ing test while each appliance is operat ing and the other appliances which are not operating re main connected to the common venting system If the vent ing system has been installed improperly you mus...

Страница 19: ...iping must be resistant to the actions of liquified petro leum gases NOTE Install a 1 8 inch NPT plugged tap in the field piping upstream of the gas supply connection to the unit The tap must be acces...

Страница 20: ...urnace must be isolated from the gas supply system by closing its individual manual shut off valve during any pressure testing of the gas supply system at pressuresless than or equal to 1 2 psig 3 48...

Страница 21: ...tage HUM 1 4 spade terminal is pro vided on the furnace integrated control Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to o...

Страница 22: ...ooling W951 O to R Heat Pumps Wiring Connections 1 Heat 1 Cool NOTE Use DIP switch 2 to set sec ond stage heat ON delay OFF10 minutes ON 15 minutes ON Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOO...

Страница 23: ...ings and On Board Links See figure 19 Thermostat DIP Switch 1 W915 Y1 to Y2 Two Stage Cooling W951 O to R Heat Pumps Wiring Connections 2 Heat 2 Cool OFF Cut Intact S1 T STAT CONTROL TERM STRIP OUTDOO...

Страница 24: ...Page 24 506178 01 05 2009 G60DF X Schematic Wiring Diagram FIGURE 17...

Страница 25: ...UT TO FLAME SENSER NEUTRALS 120 VAC NEUTRAL PARK DEAD TERMINAL FOR UNUSED BLOWER LEAD HEAT LOW 120 VAC OUTPUT TO CIRC BLWR LOW HT SPEED HEAT HIGH COOL LOW 120 VAC OUTPUT TO CIRC BLWR HIGH HEAT AND LOW...

Страница 26: ...s The heating blower off delay affects comfort and is adjustable to satisfy individual applications Adjust the blower off delay to achieve a sup ply air temperature between 90 and 110 F at the exact m...

Страница 27: ...e upper access panel 6 White Rodgers 36E Gas Valve Move gas valve con trol switch to OFF See figure 20 Honeywell VR8205 Gas Valve Turn knob on gas valve clockwise to OFF Do not force See figure 21 7 W...

Страница 28: ...c for LP propane gas should be maintained 2 After the line pressure has been checked and ad justed check the low fire and high fire manifold pres sures See figures 20 and 21 for the location of the ma...

Страница 29: ...at Heat Anticipation Set the heat anticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit Electrical 1 Check all wiring for loose connecti...

Страница 30: ...1495 556 1350 485 1150 406 965 335 0 25 1465 544 1325 473 1135 398 955 329 0 30 1430 532 1300 460 1125 389 945 323 0 40 1370 509 1250 438 1095 373 935 313 0 50 1295 482 1200 420 1055 355 900 302 0 60...

Страница 31: ...first stage heat is satisfied the gas valve is de energized and the field selected indoor blower off delay begins The combustion air inducer begins a 5 second post purge period 9 When the combustion...

Страница 32: ...m the unit Label the pressure switch wires then disconnect them 3 Remove the four screws that secure the combustion air inducer Carefully remove the combustion air induc er to avoid damaging blower ga...

Страница 33: ...3 and 24 until no leaks are detected 25 Replace front access panel Planned Service The service technician should check the following during an annual inspection Power to the unit must be shut off for...

Страница 34: ...ltage HARD LOCKOUT CODES 5 1 Hard lockout Rollout circuit open or previously opened 5 2 Control failed self check internal error control will restart if error recovers 5 3 No Earth ground control will...

Страница 35: ...VE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON STATUS ERROR CODE 5 1 SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR T STAT IS CYCLED OFF ON FOR 3 SEC MINIMUM NO YES F...

Страница 36: ...CED OR RECONNECTED STATUS ERROR CODE 4 7 YES AT END OF IGNITOR 20 SECOND WARM UP PERIOD 4 SECOND TRIAL FOR IGNITION GAS VALVE OPENS IGNITOR ENERGIZED DURING 4 SECOND TRIAL UNTIL FLAME SENSED YES 4 SEC...

Страница 37: ...O YES FIRST STAGE HEAT DEMAND SATISFIED GAS VALVE OFF COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE INDOOR BLOWER OFF WITH DELAY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SECOND STAGE HEAT DEMAN...

Страница 38: ...RMOSTAT MODE DIP SWITCH SET AT SINGLE YES YES FIRST AND SECOND STAGE HEAT DEMAND SATISFIED SIMULTANEOUSLY STATUS LED HEARTBEAT YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF AFTER 5 SECOND LOW SPEED POS...

Страница 39: ...ENERGIZED NO IS THERE PROPER GROUND YES NO INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY FIRST STAGE DEMAND FOR COOL SATISFIED NO THERMOSTAT CALLS FOR SECOND STAGE COOL COMPR...

Страница 40: ...SWITCHES TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAG...

Страница 41: ...agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Two stage integrated control Door interlock switch Circuit breaker Blower Parts Blower whee...

Страница 42: ...ions Tight Heating Section Thermostat Heat Anticipator Setting Thermostat Level Fuel Type Natural Gas Blower Motor Amps Blower Motor H P Gas Piping Connections Tight Leak Tested Proper Draft State Blo...

Отзывы: