background image

Page 4

DANGER

Danger of explosion.

There are circumstances in which odorant used with
LP/propane gas can lose its scent.  In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.

Do not attempt to bleed the gas lines of air. Call your
local gas provider.

Lighting Information & Operation

WARNING

If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.

BEFORE LIGHTING the unit,

 smell all around the ap-

pliance area for gas. Be sure to smell next to the floor be-
cause some gas is heavier than air and will settle on the
floor.

The gas valve on the G43UF will be equipped with a gas
control switch. Use only your hand to move the switch. Nev-
er use tools. If the switch will not move by hand, do not try to
repair it. Call a licensed professional service technician (or
equivalent). Force or attempted repair may result in a fire or
explosion.

Placing the G43UF furnace into operation:

G43UF units are equipped with an ignition system. Do not
attempt to manually light burners on this furnace. Each
time the thermostat calls for heat, the burners will automati-
cally light. The ignitor does not get hot when there is no call
for heat on units with this ignition system.

Operating the Gas Valve (Figures 2 and 3)

 1 −

STOP

! Read the safety information at the beginning of

this section.

 2 − Set the thermostat to the lowest setting.

 3 − Turn off all electrical power to the unit.

 4 − This furnace is equipped with an ignition device which

automatically lights the burners. Do 

not

 try to light the

burners by hand.

 5 − Remove the upper access panel.

 6 −

White Rodgers 36G Gas Valve − 

 Move gas valve

switch to 

OFF

. See figure 2 for the White Rodgers 36G

valve. 

Honeywell VR8205 Gas Valve − 

Move switch on gas

valve to 

OFF

. See figure 3 for Honeywell VR8205

valve.

 7 − Wait five minutes to clear out any gas. If you then smell

gas, 

STOP

! Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.

 8 −

White Rodgers 36G Gas Valve − 

Move gas valve

switch to 

ON

.

 

See figure 2 for the White Rodgers 36G

valve.

Honeywell VR8205 Gas Valve − 

Move switch on gas

valve to 

ON

. See figure 3 for Honeywell VR8205 valve.

FIGURE 2

White Rodgers 36G Series Gas Valve

GAS VALVE SHOWN IN OFF POSITION

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

OUTLET

PRESSURE

POST

INLET

PRESSURE

POST

Honeywell VR8205 Series Gas Valve

GAS VALVE SHOWN IN ON POSITION

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

MANIFOLD

PRESSURE

OUTLET

FIGURE 3

 9 − Replace the upper access panel.

10 − Turn on all electrical power to to the unit.

11 − Set the thermostat to desired setting.

NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.

12− If the appliance will not operate, follow the section

Turning Off Gas to the Unit" and call your licensed pro-
fessional service technician (or equivalent).

Turning Off Gas to the Unit

 1 − Set the thermostat to the lowest setting.

 2 − Turn off all electrical power to the unit if service is to be

performed.

 3 − Remove the upper access panel.

 4 −

White Rodgers 36G Gas Valve − 

Move gas valve

switch to 

OFF

.

Honeywell VR8205 Gas Valve − 

Move switch on gas

valve 

OFF

.

 5 − Replace the upper access panel.

Содержание G43UF SERIES

Страница 1: ...formed by a qualified installer service agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your building D Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions D If you cannot reach your gas supplier call the fire department D Leave the building immediately GAS FURNACE FIRE OR EXPL...

Страница 2: ...this is not possible the water supply to the house should be shut off and the pipes should be drained This will prevent problems associ ated with a NO HEAT condition frozen pipes etc CAUTION Before attempting to perform any service or mainte nance turn the electrical power to unit OFF at the disconnect switch WARNING Product contains fiberglass wool Disturbing the insulation in this product during...

Страница 3: ...cts into the combustion air These products can cause furnace corrosion 5 DO NOT draw return air from a room where this fur nace or any other gas appliance ie a water heat er is installed When return air is drawn from a room a negative pressure is created in the room If a gas ap pliance is operating in a room with negative pressure the flue products can be pulled back down the vent pipe and into th...

Страница 4: ...pped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 White Rodgers 36G Gas Valve Move gas valve switch to OFF See figure 2 for the White Rodgers 36G valve Honeywell VR8205 Gas Valve Move switch on gas valve to OFF See figure 3 for Honeywell VR8205 valve 7 Wait five minutes to clear out any gas If you then smel...

Страница 5: ...nnually before heating season inspect furnace venting system vent cap heat exchanger and burners for corro sion deterioration or deposits of debris Remove any ob structions Inspect the furnace for obvious signs of deterioration Inspect the furnace venting system to make sure it is in place physically sound and without holes corrosion or blockage Vent pipe must be clear and free of obstructions and...

Страница 6: ...If you suffer from flu like symp toms that are exaggerated at home but seem to sub side while you are away from the house exposure to carbon monoxide could be the cause Your vigilance may pay off in early detection of a problem before either personal injury or property damage occurs Do not hesitate to contact a qualified service technician as an investment in your well being Planned Service You sh...

Страница 7: ...or the gas supplier Cabinet Parts Upper access panel Blower access panel Top Cap Control Panel Parts Transformer Integrated control Door interlock switch Blower Parts Blower wheel Motor Motor mounting frame Motor capacitor Blower housing cutoff plate Heating Parts Flame Sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure sw...

Отзывы: