Page 8
BLOWER DATA
G40UH−60C−110−1, −2, −3 with 3/4 hp motor PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return
Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
2450
1155
1220
2300
1085
1060
2056
970
905
1725
815
735
0.05
12
2410
1135
1205
2265
1070
1045
2040
965
895
1715
810
725
0.10
25
2370
1120
1195
2230
1050
1030
2020
955
890
1710
810
720
0.15
37
2325
1095
1175
2200
1040
1015
1995
940
875
1700
800
715
0.20
50
2280
1075
1165
2170
1025
1005
1975
935
870
1695
800
710
0.25
62
2245
1060
1150
2130
1005
990
1950
920
855
1680
795
705
0.30
75
2205
1040
1135
2095
990
975
1925
910
845
1665
785
700
0.40
100
2115
995
1105
2010
950
940
1860
875
820
1625
770
685
0.50
125
2025
955
1060
1945
920
920
1810
855
805
1605
755
675
0.60
150
1910
900
1015
1850
875
885
1715
810
780
1540
730
670
0.70
175
1835
865
1005
1775
840
865
1655
780
765
1495
705
655
0.80
200
1745
825
975
1655
780
835
1540
725
730
1400
660
635
0.90
225
1610
760
945
1540
725
805
1475
695
715
1310
620
615
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G40UH−60C−110−1, −2, −3 with 3/4 hp motor PERFORMANCE − Single Side Return Air − Air volumes in bold require field fab-
ricated transition to accommodate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air
velocity.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
2395
1130
1230
2260
1065
1085
2015
950
920
1730
815
750
0.05
12
2365
1115
1220
2230
1050
1070
1985
935
905
1720
810
745
0.10
25
2330
1100
1205
2200
1040
1060
1960
925
890
1705
805
750
0.15
37
2285
1080
1190
2170
1025
1045
1030
485
880
1695
800
740
0.20
50
2245
1060
1170
2135
1010
1030
1905
900
870
1675
790
735
0.25
62
2200
1040
1160
2100
990
1020
1890
890
860
1665
785
730
0.30
75
2170
1025
1145
2070
980
1005
1870
880
850
1655
780
720
0.40
100
2085
985
1110
1990
940
975
1825
860
835
1610
760
705
0.50
125
1980
935
1075
1910
900
945
1755
830
810
1555
735
690
0.60
150
1890
890
1045
1835
865
915
1670
790
780
1515
715
680
0.70
175
1800
850
1020
1725
815
885
1615
760
770
1445
685
655
0.80
200
1700
805
995
1645
775
855
1525
720
745
1380
650
645
0.90
225
1590
750
980
1520
720
820
1410
665
710
1300
615
625
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.