background image

Page 22

REGULATOR

COVER SCREW

FIGURE 35

WHITE RODGERS 36E GAS VALVE

REGULATOR ADJUSTMENT SCREW LOCATION

ADJUSTING

SCREW

Manifold Pressure Measurement & Adjustment

NOTE - Pressure test adaptor kit (10L34) is available from
Lennox to facilitate manifold pressure measurement.

 1 - Connect test gauge to outlet tap on gas valve.
 2 - Disconnect pressure sensing hose from gas valve and

plug hose by covering opening with tape or equivalent.

Leave  barbed  fitting  on  valve  open  to  atmosphere.

See figure 36.

FIGURE 36

DIFFERENTIAL PRESSURE SWITCH CIRCUITRY

BURNER

BOX

GAS

VALVE

SENSING

HOSE

COMBUSTION

AIR PRESSURE

SENSING HOSE

COMBUSTION

AIR INDUCER

BURNER

BOX

SENSING

HOSE

GAS

VALVE

TEE

PRESSURE

SWITCH

SENSING

HOSE

HOSE

BARB

DIFFERENTIAL

PRESSURE

SWITCH

LEFT SIDE OF PRESSURE SWITCH = MORE NEGATIVE

RIGHT SIDE OF PRESSURE SWITCH = LESS NEGATIVE (Closer to Zero)

 3 - Start unit and allow 5 minutes for unit to reach steady

state.

 4 - Examine the burner flame. The flame should be stable

and should not lift from the burner. Natural gas should

burn blue. L.P./propane gas should burn mostly blue

with some orange streaks.

 5 - After allowing unit to stabilize for 5 minutes, record

manifold  pressure  and  compare  to  values  given  in

table 6.

NOTE - Shut unit off and remove manometer as soon as an

accurate reading has been obtained. Take care to replace

pressure tap plug.
NOTE - During this test procedure, the unit unit will be over-

firing:

D

Operate unit only long enough to obtain accurate reading to

prevent overheating heat exchanger.

D

Attempts to clock gas valve during this procedure will be

inaccurate. Measure gas flow rate only during nor-mal

unit operation.

 6 - When test is complete remove obstruction from hose

and return hose to gas valve barbed fitting.

Gas Flow

To check for proper gas flow to the combustion chamber, deĆ

termine the Btu (kW) input from the unit rating plate. Divide

this input rating by the Btu (kW) per cubic foot (cubic meter)

of available gas. The result is the required number of cubic

feet  (cubic  meter)  per  hour.  Determine  the  flow  of  gas

through the gas meter for two minutes and multiply by 30 to

get the hourly flow of gas.

High Altitude Information

Unit does not need gas pressure adjustment when operating

from 0 to 7500 feet (0 to 2248m). See table 6 for correct manĆ

ifold pressures for LP/propane and natural gases.

Other Unit Adjustments

Natural to LP/Propane Changeover

A natural gas to LP/propane gas changeover kit is required

to convert unit. Refer to installation instructions supplied

with kit for conversion procedure.

Heat Anticipation Settings

Thermostat anticipator setting (if adjustable) should be set

according to amps listed on wiring diagram on unit.

Flame Rollout Switch

Factory set: No adjustment necessary.

Limit Control

Factory set: No adjustment necessary.

Pressure Switch

Factory set: No adjustment is necessary.

Fan Control

The fan-on delay of 45 seconds is not adjustable. The fan-
off delay (time that the blower operates after the heating
demand has been satisfied) can be adjusted by moving the
jumper on the SureLight

t

 integrated control. The unit is

shipped with a factory fan-off delay of 90 seconds. The fan-
off delay will affect comfort and is adjustable to satisfy indiĆ
vidual applications. See figure 37.

FIGURE 37

FANĆOFF TIME ADJUSTMENT

To adjust fan-off timing, flip dip switch to desired setting.

60sec.

90sec.

120sec.

180sec.

Downloaded from 

ManualsNet.com

 search engine

Содержание G26 Series

Страница 1: ...ting 26 Start Up Performance Check List 31 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WHAT TO DO IF YOU SMELL GAS Do not store or use gasoline or other flammable vapors and liquids in the vi cinit...

Страница 2: ...INTAKE 21 3 4 552 7 3 8 187 23 3 4 603 25 635 5 8 16 H G 5 8 16 EXTERNAL SIDE RETURN AIR FILTER KIT Either Side Optional 23 584 D Return Air Knockout Bottom 4 102 Model No A B C D E F G H Model No in...

Страница 3: ...ME SIGHT GLASS DuralokPlusTM HEAT EXCHANGER ASSEMBLY CONDENSER COIL CONTROL TRANSFORMER CONTROL BOX COVER DOOR INTERLOCK SWITCH CONTROL VOLTAGE CIRCUIT BREAKER WARM HEADER COLLECTOR BOX COLD HEADER CO...

Страница 4: ...e hangar or other building that has a hazardous atmosphere the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CAN CGA B149 1 and B1...

Страница 5: ...be installed in areas normally subject to freezing temperatures Return Air Opening Guidelines WARNING Blower door must be securely in place when blower and burners are operating Gas fumes which could...

Страница 6: ...AIR OPENING SIDE FILTER CLIPS 2 FURNACE FRONT FURNACE BACK Side Return Air Applications An external filter rack ordered separately is available from Lennox NOTE The filter door may be shipped in the...

Страница 7: ...American National Standard Institute and the American Society for Testing and Materials ANSI ASTM standards The solvent shall be free flowing and contain no lumps undissolved particles or any foreign...

Страница 8: ...s the intake connection is sized for 3 inch diameter pipe The exhaust connection has a 2 inch nipple A pipe transition piece is shipped with the unit to connect to 3 inch pipe See figure 7 for 2 inch...

Страница 9: ...abric softeners for clothes dryers Masonry acid washing materials Intake Piping 1 Cement intake piping in slip connector located at top of unit 2 Route piping to outside of structure Continue with ins...

Страница 10: ...intake piping upwind prevailing wind from exhaust piping To avoid re circulation of exhaust gas on roof terminations end of exhaust pipe must be higher than intake pipe Exhaust and intake exits must b...

Страница 11: ...all to position above snow accumulation or other ob structions Piping must be supported every 3 feet 91m as shown in figure 15 Refer to figures 13 and 14 for proper piping method WTK wall termination...

Страница 12: ...authorities having local jurisdiction At vent termination care must be taken to maintain protective coatings over building materials pro longed exposure to exhaust condensate can destroy protective co...

Страница 13: ...AKE VENT Side View OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT INSTALLATION WALL TERMINATION KIT WTK Inches mm FIGURE 18 12 MIN 305 Above Grade COVER EXHAUST VENT WITH 1 2 13 FOAM INSULATION Front Vie...

Страница 14: ...UCER BRACKET CONDENSATE TRAP 3 Use the provided adapter 1 2 inch PVC x 1 2 inch MPT and the nipple 1 2 inch PVC to carry drainage outside the cabinet If a field substitute is needed 1 2 inch CPVC x 1...

Страница 15: ...combustion air inducer See figure 23 4 The piping should be sloped 1 4 inch 6 4 mm per 15 feet 4 57 m upward toward the meter from the fur nace The piping must be supported at proper inter vals every...

Страница 16: ...c feet of gas per hour kilo liters of gas per hour and based on 0 60 specific gravity gas The furnace must be isolated from the gas supply system by closing its individual manual shut off valve during...

Страница 17: ...et of the jack See fig ure 27 Any accessory rated up to 4 amps can be con nected to this wire Connect the neutral leg of the acces sory to the neutral white wire in the make up box The ac cessory term...

Страница 18: ...IGHT CONTROL DOOR INTERLOCK SWITCH TRANSFORMER DETACHABLE TERMINAL STRIP SURELIGHT INTEGRATED CONTROL BOARD FIGURE 30 TERMINAL DESIGNATIONS ACB COOL ACB HEAT PARK ACB LOW ACC TX HOT HTG ACC NEUTRALS 2...

Страница 19: ...Page 19 FIGURE 31 TYPICAL G26 WIRING DIAGRAM OUTDOOR UNIT OUTDOOR UNIT B6 COMBUSTION AIR INDUCER MOTOR Downloaded from ManualsNet com search engine...

Страница 20: ...around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Gas valve may be equipped with either a gas control knob or leve...

Страница 21: ...s To Unit and call your service techni cian or gas supplier To Turn Off Gas To Unit 1 Set thermostat to lowest setting 2 Turn off all electrical power to unit if service is to be per formed 3 Remove h...

Страница 22: ...te only during nor mal unit operation 6 When test is complete remove obstruction from hose and return hose to gas valve barbed fitting Gas Flow To check for proper gas flow to the combustion chamber d...

Страница 23: ...applicable is operating Blower Check the blower wheels for debris and clean if necessary The blower motors are prelubricated for ex tended bearing life No further lubrication is needed Filters 1 Filte...

Страница 24: ...he plas tic orifice in the inducer inlet to make sure it has not fallen out See figure 1 Reconnect the 2 pin plug to the wire harness Re install the flue transition in the cabinet and re attach the dr...

Страница 25: ...akes a good seal The burners sit on top of the burner box flanges Make certain that the screws from the underneath the box pass through the larger holes in the flange and engage in the smaller holes i...

Страница 26: ...SLOW FLASH SLOW FLASH SLOW FLASH FAST FLASH Primary or secondary limit switch open Rollout switch open OR 9 pin connector improperly attached Flame sensed without gas valve energized Pressure switch o...

Страница 27: ...D 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence holds until pressure switch closes or thermostat resets control NO NO YES NO IS THERE...

Страница 28: ...ERGIZED YES FLAME STABILIZATION PERIOD GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND IGNITION WATCH...

Страница 29: ...MPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY ACB COOL SPEED TERMINAL IS ENERGIZED ACC TERMINAL IS ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND ACC TERM OFF WITH 0 SECOND...

Страница 30: ...G THERMOSTAT OPENS COMBUSTION AIR INDUCER AND HTG ACC TERMINAL ARE DE ENERGIZED INDOOR BLOWER SWITCHES TO ACB COOL SPEED THERMOSTAT OPENS INDOOR BLOWER SWITCHES TO ACB LOW SPEED ACC TERM REMAINS ENERG...

Страница 31: ...Pressure Job No City City Serial No Date State Technician Flue Connections Tight HEATING SECTION THERMOSTAT Heat Anticipator Properly Set Level Fuel Type Natural Gas LP Propane Gas Blower Motor H P G...

Отзывы: