![Lennox Energence LGH Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/lennox/energence-lgh/energence-lgh_manual_1876885029.webp)
Energence
®
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 29
HUMIDITROL
®
DEHUMIDIFICATION SYSTEM RATINGS
88 kW - LGH300S4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
3775
26.9
6.38
0.56 0.77 0.97
22.4
7.00
0.48 0.74 1.00
17.8
7.63
0.39 0.71 1.00
13.3
8.26
0.30
0.68
1.00
4485
28.5
6.45
0.60 0.80 0.99
23.9
7.06
0.52 0.79 1.00
19.3
7.66
0.43 0.77 1.00
14.8
8.28
0.35
0.76
1.00
5195
30.0
6.52
0.63 0.85 1.00
25.4
7.11
0.55 0.84 1.00
20.9
7.70
0.47 0.82 1.00
16.2
8.29
0.40
0.82
1.00
19.4°C
3775
31.1
6.52
0.38 0.56 0.74
26.6
7.16
0.28 0.49 0.73
21.8
7.80
0.17 0.44 0.72
17.1
8.45
0.07
0.38
0.71
4485
32.8
6.57
0.40 0.58 0.77
27.9
7.20
0.30 0.52 0.77
22.9
7.84
0.19 0.48 0.78
17.9
8.47
0.08
0.44
0.79
5195
34.6
6.62
0.41 0.60 0.81
29.3
7.25
0.31 0.56 0.82
24.0
7.87
0.20 0.52 0.83
18.7
8.49
0.09
0.48
0.85
21.7°C
3775
35.4
6.65
0.19 0.35 0.51
30.5
7.32
0.07 0.25 0.46
25.7
7.99 -0.04 0.17 0.40
21.0
8.65
-0.16 0.09
0.35
4485
37.2
6.69
0.19 0.35 0.53
31.9
7.35
0.07 0.27 0.48
26.6
8.01 -0.05 0.19 0.44
21.2
8.67
-0.17 0.11
0.40
5195
39.1
6.74
0.19 0.36 0.55
33.2
7.38
0.07 0.29 0.51
27.3
8.04 -0.07 0.21 0.49
21.4
8.70
-0.19 0.13
0.46
88 kW - LGH300S4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
3775
68.3
12.69 0.68 0.86 1.00
62.0
14.12 0.67 0.88 1.00
55.6
15.55 0.67 0.90 1.00
49.3
16.96 0.66
0.91
1.00
4485
69.8
12.76 0.72 0.91 1.00
63.1
14.19 0.73 0.93 1.00
56.4
15.62 0.73 0.95 1.00
49.8
17.04 0.74
0.97
1.00
5195
71.5
12.84 0.76 0.95 1.00
64.3
14.26 0.78 0.97 1.00
57.3
15.71 0.79 0.98 1.00
50.3
17.13 0.82
0.99
1.00
19.4°C
3775
72.5
12.91 0.49 0.67 0.85
67.0
14.38 0.49 0.67 0.86
61.3
15.86 0.47 0.67 0.87
55.6
17.31 0.44
0.66
0.89
4485
73.3
13.04 0.52 0.70 0.89
67.5
14.48 0.51 0.71 0.91
61.8
15.93 0.50 0.72 0.94
56.0
17.37 0.49
0.72
0.96
5195
74.0
13.17 0.54 0.73 0.92
68.1
14.59 0.54 0.75 0.96
62.2
16.01 0.54 0.78 0.98
56.4
17.43 0.52
0.79
0.99
21.7°C
3775
76.8
13.12 0.33 0.48 0.63
71.9
14.63 0.29 0.47 0.63
67.2
16.17 0.26 0.44 0.62
62.2
17.70 0.23
0.41
0.62
4485
76.9
13.31 0.34 0.50 0.67
72.0
14.78 0.30 0.49 0.67
67.3
16.24 0.26 0.47 0.68
62.5
17.72 0.23
0.47
0.69
5195
76.8
13.50 0.34 0.52 0.70
72.1
14.92 0.31 0.52 0.72
67.5
16.33 0.27 0.51 0.75
62.9
17.74 0.24
0.50
0.77