Energence
®
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 19
SPECIFICATIONS
General Data
Nominal kW (Tons)
46 kW
53 kW
61.5 kW
Model Number
LGH156H4B
LGH180H4B
LGH210H4B
Efficiency Type
High
High
High
Blower Type
CAV
(Constant Air Volume)
CAV
(Constant Air Volume)
CAV
(Constant Air Volume)
Cooling
Performance
Gross Cooling Capacity - kW (Btuh)
38.7 (132 000)
44.8 (153 000)
51.3 (175 000)
1
Net Cooling Capacity - kW (Btuh)
37.1 (127 000)
43.4 (148 000)
49.5 (169 000)
Rated Air Flow - L/s (cfm)
2360 (5000)
2475 (5250)
2890 (6125)
Total Unit Power - kW
10.4
12.1
13.9
1
EER (Btuh/Watt) at 35°C (95°F)
12.2
12.2
12.2
2
EER (Btuh/Watt) at 46°C (115°F)
8.1
8.2
8.2
1
IEER (Btuh/Watt)
13.2
13.5
13.0
Refrigerant
Charge
Refrigerant Type
R-410A
R-410A
R-410A
Environ™
Coil System
Circuit 1
2.61 kg (5 lbs. 12 oz.)
2.72 kg (6 lbs. 0 oz.)
3.06 kg (6 lbs. 12 oz.)
Circuit 2
2.49 kg (5 lbs. 4 oz.)
2.55 kg (5 lbs. 10 oz.)
3.12 kg (6 lbs. 14 oz.)
Circuit 3
2.55 kg (5 lbs. 10 oz.)
2.66 kg (5 lbs. 14 oz.)
3.12 kg (6 lbs. 14 oz.)
Environ™
Coil
With
Humiditrol
®
Circuit 1
2.66 kg (5 lbs. 14 oz.)
2.95 kg (6 lbs. 8 oz.)
3.29 kg (7 lbs. 4 oz.)
Circuit 2
2.27 kg (5 lbs. 8 oz.)
2.61 kg (5 lbs. 12 oz.)
3.18 kg (7 lbs. 0 oz.)
Circuit 3
2.61 kg (5 lbs. 12 oz.)
2.98 kg (6 lbs. 9 oz.)
2.83 kg (6 lbs. 4 oz.)
Conventional Fin/Tube
Coil Option
Circuit 1
4.54 kg (10 lbs. 0 oz.)
5.67 kg (12 lbs. 8 oz.)
5.90 kg (13 lbs. 0 oz.)
Circuit 2
4.54 kg (10 lbs. 0 oz.)
5.67 kg (12 lbs. 8 oz.)
5.90 kg (13 lbs. 0 oz.)
Circuit 3
4.31 kg (9 lbs. 8 oz.)
5.67 kg (12 lbs. 8 oz.)
5.90 kg (13 lbs. 0 oz.)
Conventional Fin/Tube
With Humiditrol
®
Dehumidification Option
Circuit 1
5.44 kg (12 lbs. 0 oz.)
6.58 kg (14 lbs. 8 oz.)
6.80 kg (15 lbs. 0 oz.)
Circuit 2
5.44 kg (12 lbs. 0 oz.)
6.58 kg (14 lbs. 8 oz.)
6.80 kg (15 lbs. 0 oz.)
Circuit 3
4.31 kg (9 lbs. 8 oz.)
5.67 kg (12 lbs. 8 oz.)
5.90 kg (13 lbs. 0 oz.)
Gas Heating Options Available
See page 21
Compressor Type (number)
Scroll (3)
Scroll (3)
Scroll (3)
Outdoor
Coils
Environ™
Fin/Tube
Net face area (total) - m
2
(sq. ft.)
3.85 (41.4)
5.13 (55.2)
5.13 (55.2)
No. of rows Environ™
(Fin/Tube)
1 (2)
1 (2)
1 (2)
Fins per meter (Fins per inch)
906 (23)/787 (20)
906 (23)/787 (20)
906 (23)/787 (20)
Outdoor Coil
Fans
Motor - (No.) W (HP)
(3) 250 (1/3)
(4) 250 (1/3)
(6) 250 (1/3)
Motor rev/min
896
896
896
Total Motor watts
840
1146
1490
Diameter - (No.) mm (in.)
(3) 610 (24)
(4) 610 (24)
(6) 610 (24)
Number of blades
3
3
3
Total Air volume - L/s (cfm)
4720 (10 000)
6293 (13 333)
7866 (16 666)
Indoor Coils
Net face area (total) - m
2
(sq. ft.)
1.99 (21.4)
1.99 (21.4)
1.99 (21.4)
Tube diameter - in.
9.5 (3/8)
9.5 (3/8)
9.5 (3/8)
Number of rows
3
3
4
Fins per meter (Fins per inch)
551 (14)
551 (14)
551 (14)
Drain connection - No. and size
(1) 1 in. FPT
(1) 1 in. FPT
(1) 1 in. FPT
Expansion device type
Balance port TXV, removable head
3
Indoor
Blower
and
Drive
Selection
Nominal Motor kW (HP)
1.5 (2)
2.2 (3)
2.2 (3)
Maximum usable motor kW (HP)
1.7 (2.3)
2.6 (3.45)
2.6 (3.45)
Kit # (rev/min range)
#1 (446-604)
#3 (571-721)
#3 (571-721)
#2 (571-721)
#4 (708-871)
#4 (708-871)
Nominal Motor kW (HP)
2.2 (3)
3.7 (5)
3.7 (5)
Maximum usable motor kW (HP)
2.6 (3.45)
4.3 (5.75)
4.3 (5.75)
Kit # (rev/min range)
#3 (571-721)
#3 (571-721)
#3 (571-721)
#4 (708-871)
#4 (708-871)
#4 (708-871)
#5 (788-988)
#5 (788-988)
Nominal Motor kW (HP)
3.7 (5)
5.6 (7.5)
5.6 (7.5)
Maximum usable motor kW (HP)
4.3 (5.75)
6.4 (8.6)
6.4 (8.6)
Kit # (rev/min range)
#3 (571-721)
#6 (708-871)
#6 (708-871)
#4 (708-871)
#7 (788-988)
#7 (788-988)
#5 (788-988)
#8 (871-1071)
#8 (871-1071)
Blower wheel nominal diameter x width - mm (in.)
(2) 381 x 381 (15 x 15)
Filters
Type of filter - Number and size - mm (in.)
Fiberglass, disposable - (6) 610 x 610 x 51 (24 x 24 x 2)
Electrical Characteristics
380/420V - 50 hertz - 3 phase with neutral (No neutral on CE marked models)
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Tested at conditions which are based on AHRI Standard 340/360; 35°C (95°F) outdoor air temperature and 27°C (80°F) db/19°C (67°F) wb entering evaporator air;
minimum external duct static pressure while operating at rated voltage and air volumes.
2
Rated at 46°C (115°F) outdoor air temperature and 27°C (80°F) db/19°C (67°F) wb entering evaporator air (T3 Conditions).
3
Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor output required. Maximum usable output
of motors furnished are shown. See Belt Drive Specification Table for maximum usable motor output. If motors of comparable output are used, be sure to keep within the
service factor limitations outlined on the motor nameplate.